Lena Lighting Uv-c Sterilon Hepa Lcd Control Panel User Manual

Lena Lighting Uv-c Sterilon Hepa Lcd Control Panel User Manual

LENA LIGHTING logo

 UV-C Sterilon Hepa LCD Control PanelLENA LIGHTING UV C Sterilon Hepa LCD Control PanelUser Manual

UV-C Sterilon Hepa LCD Control Panel

LENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig

GENERAL INFO

LENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 1

The left button is responsible for executing commands on the bar on the left-hand side of the screen, e.g. „ok”
The right button is responsible for executing commands on the bar on the right-hand side of the screen, e.g. „change”

ON/OFFLENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 2

Basic mode – starts the UVC sterilisation with the possibility of adjusting the fan power in steps of 25-100%

FAN WITHOUT UVCLENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 3

Starts the fan without UVC lamps, allowing air purification through the HEPA filter itself Fan power adjustment in steps of 25-100%

DELAY ONLENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 4

Possibility to start sterilisation with a specified power setting after a preset time

DELAY OFFLENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 5

SYSTEM INFOLENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 6

Possibility to check the lifetime of fluorescent lamps – 9000h by default

MENU – ON/OFFLENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 7

– „OFF” is set by default
– the change is made by pressing the „change” button
– all UVC lamps turn on when the fan is runningLENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 8

– the available fan speed settings are as follows: OFF, 25%, 50%, 75% and 100%
– the last selected power setting is remembered and is the default value upon subsequent activations of this mode Power of Fan

MENU – FAN WITHOUT UVC
The same as in the ON/OFF menu, except that the UVC lamps are not turned on

MENU – DELAY ON / Power of FanLENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 9

– setting the power with which the fan is to turn on during sterilisation after a preset time
– set as in the „on/off” menu

MENU – DELAY ON / Time to ONLENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 10

– setting the delay time for switching on

MENU – DELAY ON / Time to ONLENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 11

– after entering the „Time to on” submenu, set the delay time expressed in hours and minutes
– the maximum available values are 24h and 55 min
– the smallest time unit is 5 minutesLENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 12

– pressing „ok” highlights the changed value
– to change the value, press the „change” button
– once 24h is reached, the value goes back to the start – i.e. 0hLENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 13

– pressing „ok” again will take you to setting the minutesLENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 14

– another pressing „ok” will save the set time
– pressing the „back” button will take you back to the previous menu

MENU – DELAY ON / StartLENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 15

– selecting „Start” and pressing „ok” will start the countdown to disinfection LENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 16

– the time remaining to activation is constantly refreshed
– the time can be reset by pressing the „reset” button

MENU – Delay OFF
– the same as in the Delay ON menu, except that the time to turn off the lamp is counted down, and the set fan power is the one with which the lamp is started once the „Start” option is selected

MENU – SYSTEM INFOLENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 17

– the operation time meter shows the approximate lifetime of fluorescent lamps – how much time is left to the recommended replacement
– the default set lifetime of fluorescent lamps is 9000 hours

ALARM MESSAGES LENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 18

– The following alarm messages may be displayed on the display during operation of the device.
– If any of the UVC lamps is damaged, the “UVC broken. Replace!” message is displayed. In this case, disconnect the device from the power supply and replace the  appropriate fluorescent lamp. If not replaced, only the “Fan without UVC” operating mode will be functional.
– The message disappears after any button is pressed or the device is restarted.LENA LIGHTING UV C Sterilon Hepa LCD Control Panel - fig 19

– In the case of continuous lighting of fluorescent lamps for more than 9000h, the message “UVC> 9000h. Replace!” is displayed.
– The message disappears after any button is pressed or the device is restarted.
– The message does not interfere with the normal operation of the device, but it will be displayed again after the next hour.
– To eliminate it, reset the runtime counter in the “System info” menu.

Dustbin Icon We would like to inform you that our product’s are marked in accordance with the European Directive 2002/96/CE and Polish Act o n used electric and electronic equipment with a sign of a crossed-out waste container:
This mark informs abort the fact that the device, after its application use, cannot be placed together with other types of household waste. The user is obliged to return it to  the entities conducting a collection of used electric and electronic equipment. The collection points, including local collection points, shops and municipal entities create a  proper system making it possible for the return of the equipment. Proper proceeding with used electric and electronic equipment contributes to the avoidance of damaging  consequences for the health of the inhabitants and natural environment chick result form the presence of dangerous substances and improper storage and processing of such devices and equipment.

LENA LIGHTING logotel. +48 61 28 60 300
e-mail: [email protected]
www.lenalighting.pl
LENA LIGHTING S.A.
ul.Kornicka 52, 63-000 Sroda Wlkp.
POLAND
Data aktualizacji/Date of update: 6.12.2021

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals