Sje Rhombus 1009207 Tank Alert I Alarm System Owner's Manual

1009207 Tank Alert I Alarm System

Product Information

The Easy to Install Liquid Level Alarm System is designed for
indoor use. It features a power line that reduces the possibility
of shock.

Options

  • Indoor Alarms
  • D.11
  • Part #
  • Description (120V)
  • 1007457
  • 1009207
  • 1003104
  • 1003365
  • 1002235
  • 101-01X (120 VAC no float)
  • Part #
  • Description (230V)
  • 1008009
  • 1003364
  • 1005420
  • 1005419
  • 101-02X (230 VAC no float)
  • H = High Level
  • L = Low Level
  • X = No Float
  • SPKT = Splice Kit
  • MASTER CARTON holds 16 boxed units.
  • Shipping Weight: 3.58 lbs (120V), 2.14 lbs (230V)
  • List Price: $204.00 (120V), $284.00 (230V)

Control Switch Options

No control switch options mentioned in the user manual.

Specifications

  • Voltage for 120VAC Model:
    • Primary: 120 VAC, 50/60 Hz, 5 watts max. (alarm condition)
    • Secondary: 12 VAC
  • Voltage for 230VAC Model (not UL Listed or CSA Certified):
    • Primary: 230 VAC, 50/60 Hz, 5 watts max. (alarm condition)
    • Secondary: 12 VAC
  • Alarm Enclosure: 6 x 4 x 2.5 inch (15.24 x 10.16 x 6.35 cm),
    NEMA 1 metal
  • Alarm Horn: 86 decibels at 10 feet (3 meters)
  • Power Cord: 6 foot (1.8 meter)
  • Float Switch Connection Terminal: For float switch connection
    only. Do not apply power. (Voltage across terminals is 12
    VAC.)
  • Cable: 15 feet (4.57 meters), flexible 18 gauge, 2 conductor
    (UL) SJOW, water-resistant (CPE)
  • Maximum Water Depth: 30 feet (9 meters), 13 psi
  • Electrical: 5 amps, 125 VAC/250 VAC, 50/60 Hz

Product Usage Instructions

To use the Easy to Install Liquid Level Alarm System, follow
these steps:

  1. Ensure that the product is intended for indoor use only.
  2. Connect the power line to a suitable power source to reduce the
    possibility of shock.
  3. Select the appropriate model based on your voltage requirement
    (120VAC or 230VAC).
  4. If using a float switch, connect it to the designated float
    switch connection terminal. Note that no power should be applied to
    this terminal.
  5. Place the alarm enclosure in a suitable location, ensuring it
    is mounted securely.
  6. Ensure the alarm horn is positioned properly to achieve a sound
    level of 86 decibels at a distance of 10 feet.
  7. Connect the power cord to the power source.
  8. If required, use the provided splice kit for any necessary
    connections.
  9. Ensure the cable is properly connected and has a length of 15
    feet.
  10. Ensure the maximum water depth does not exceed 30 feet and the
    pressure does not exceed 13 psi.
  11. Verify that the electrical specifications match your
    requirements (5 amps, 125 VAC/250 VAC, 50/60 Hz).

TANK ALERT® I ALARM SYSTEM
Easy to Install Liquid Level Alarm System for Indoor Use
This alarm system monitors liquid levels in lift pump chambers, sump pump basins, holding tanks, sewage, agricultural, and other water applications. The Tank Alert® I alarm system can serve as a high or low level alarm depending on the float switch model used. The alarm horn sounds when a potentially threatening liquid level condition occurs. The horn can be silenced, but the warning light remains on until the condition is remedied. A green “power on” light indicates power to the alarm panel.
FEATURES
· NEMA 1 enclosure, designed for ease of installation, rated for indoor use · Red “alarm” light, green “power on” light, alarm “test” switch, and horn
“silence” switch · Alarm horn sounds at 86 decibels at 10 feet (3 meters) · Can be used with any UL Listed / Recognized switching mechanism
rated to include 1 amp, 12 VAC load · Alarm system (when installed on separate circuit) operates even if the
pump circuit fails · Switching mechanism operates on low voltage and is isolated from the
power line to reduce the possibility of shock
OPTIONS
When ordered with the alarm, this system is available with: · Alternate float switch models for high or low level warning · 120 VAC primary voltage or 230 VAC primary voltage (230 VAC model is
not UL Listed or CSA Certified)

Indoor Alarms

9500095I-WEB Rev 01/23 © 2020 SJE, Inc. All Rights Reserved. SJE Rhombus is a trademark of SJE, Inc.

www.sjerhombus.com · Toll Free 888-342-5753

D.11

TANK ALERT® I – Easy-to-install liquid level alarm system for indoor use.

Part #

Description (120V)

1007457

101-01H (120 VAC w/15′ SJE SignalMaster® High Level)

1009207

101-01HSPKT (120 VAC w/15′ SJE SignalMaster® High Level) with splice kit

1003104

101-01H (120 VAC w/15′ Sensor Float® High Level)

1003365

101-01L (120 VAC w/15′ Sensor Float® Low Level)

1002235

101-01X (120 VAC no float)

Part #

Description (230V)

1008009

101-02H (230 VAC w/15′ SJE SignalMaster® High Level)

1003364

101-02H (230 VAC w/15′ Sensor Float® High Level)

1005420

101-02L (230 VAC w/15′ Sensor Float® Low Level)

1005419

101-02X (230 VAC no float)

H = High Level L = Low Level X = No Float SPKT = Splice Kit MASTER CARTON holds 16 boxed units.

Shipping Weight 3.58 lbs 3.58 lbs. 3.58 lbs. 3.58 lbs. 2.14 lbs.
Shipping Weight 3.58 lbs. 3.58 lbs. 3.58 lbs. 2.14 lbs.

List Price $204.00 $215.00 $216.00 $216.00 $147.00 List Price $284.00 $297.00 $297.00 $228.00

CONTROL SWITCH OPTIONS
The Tank Alert® I alarm system comes standard with a 15 foot SJE SignalMaster® control switch with mounting clamp. Other float switches are available. See control switch section of the catalog. To determine the price of alarm with an alternate float, add the price of the part number with “no float” to the price of the float switch.

SPECIFICATIONS
VOLTAGE FOR 120 VAC MODEL: PRIMARY: 120 VAC, 50/60 Hz, 5 watts max. (alarm condition) SECONDARY: 12 VAC
VOLTAGE FOR 230 VAC MODEL (not UL Listed or CSA Certified): PRIMARY: 230 VAC, 50/60 Hz, 5 watts max. (alarm condition) SECONDARY: 12 VAC
ALARM ENCLOSURE: 6 x 4 x 2.5 inch (15.24 x 10.16 x 6.35 cm), NEMA 1 metal
ALARM HORN: 86 decibels at 10 feet (3 meters) POWER CORD: 6 foot (1.8 meter)

FLOAT SWITCH CONNECTION TERMINAL: For float switch connection only. Do not apply power. (Voltage across terminals is 12 VAC.)
FLOAT SWITCH: SJE SignalMaster® control switch with mounting clamp
CABLE: 15 feet (4.57 meters), flexible 18 gauge, 2 conductor (UL) SJOW, water-resistant (CPE)
FLOAT: 2.74 inch diameter x 4.83 inch long (7 cm x 12.3 cm), high impact, corrosion resistant polypropylene housing for use in sewage and non-potable water up to 140°F (60°C)
MAXIMUM WATER DEPTH: 30 feet (9 meters), 13 psi
ELECTRICAL: 5 amps, 125 VAC/250 VAC, 50/60 Hz

Indoor Alarms

D.12

www.sjerhombus.com · email: [email protected]

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals