IP-ACOWM200 Air Conditioner for Electrical Enclosure Outdoor Application
AIR CONDITIONER FOR ELECTRICAL ENCLOSURE OUTDOOR
APPLICATION
Product Information
The IP-ACOWM200 series air conditioner is designed to provide
cooling for electrical enclosures. It is suitable for outdoor
applications and has an IP rating of IP-ACOWM200.0X. The product
manual is written in English and contains technical data,
installation instructions, and safety warnings.
Technical Data
- Classification: Not accessible to the general public
- Installation: By qualified personnel only after enclosure power
supply disconnecting - Regulations: National wiring regulations (IEC
60335-2-40:2018) - Disconnection System: Efficient disconnection system must be
provided in compliance with the AS / NSZ 3000 standard upstream of
the electrical connection
Safety Warnings
- The air conditioner must be installed by qualified personnel
only after enclosure power supply disconnecting. - Before any operation, switch off the power supply.
- The air conditioner is not to be used by persons (including
children) with reduced physical, sensory or mental capabilities, or
lack of experience and knowledge, unless they have been given
supervision or instruction. - Children being supervised not to play with the air
conditioner.
Product Usage Instructions
Before using the air conditioner, please read the user manual
carefully and follow all safety warnings and technical data shown
in the manual.
Installation
The air conditioner must be installed by qualified personnel
only after enclosure power supply disconnecting. Follow national
wiring regulations (IEC 60335-2-40:2018) and provide an efficient
disconnection system in compliance with the AS / NSZ 3000 standard
upstream of the electrical connection. Internal and external
components of electrical enclosure don’t have to affect the proper
installation of air conditioner. Inside of electrical enclosure
there must not be components that could affect the proper
ventilation. Provide a proper fixing of the electrical enclosure to
the floor to prevent accidental tipping due to the supplementary
weight of installed AIR CONDITIONER. Installation position of AIR
CONDITIONER must be selected to ensure good ventilation. Take care
that any internal/external components of enclosure don’t obstruct
air passage.
Usage
- The air conditioner must be handled in an upright position and
protected against accidental tipping over. - Do not modify the air conditioner structure if it is not
specified in these instructions or associated instructions. - During transportation of enclosures with installed air
conditioner, a proper bracket must be used to support the cooling
unit weight. - Install only original spare parts and accessories.
- The supply connector of the air conditioner must only be
connected and disconnected when the electrical enclosure is
electrically disconnected.
USER’S MANUAL (PART 2)
AIR CONDITIONER FOR ELECTRICAL ENCLOSURE OUTDOOR APPLICATION
IP-ACOWM200 IP-ACOWM200.0X
Document: UMA-CDZ-IP-ACOWM200-00 Description
Original user’s manual for air conditioner IP-ACOWM200 series Language: English
ISSUE REV. 01 REV. 02 REV. 03
Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
UMA-CDZ-IP-ACOWM200-00
Date 23/05/2021
Name
Page 1/16
WARNING
Safety of AIR CONDITIONER is warranted only by proper use of these instruction which must be kept.
Installation must be done by qualified personnel only after enclosure power supply disconnecting.
Before any operation, switch off the power supply. The appliance is classified as not accessible to the general public The air conditioner is not to be used by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction. Children being supervised not to play with the air conditioner. The air conditioner must be installed in accordance with national wiring regulations (IEC 60335-2-40:2018)
Upstream of the electrical connection, an efficient disconnection system must be provided in compliance with the AS / NSZ 3000 standard
Internal and external components of electrical enclosure don’t have to affect the proper installation of air conditioner.
Inside of electrical enclosure there must not be components that could affect the proper ventilation.
Provide a proper fixing of the electrical enclosure to the floor to prevent accidental tipping due to the supplementary weight of installed AIR CONDITIONER.
Installation position of AIR CONDITIONER must be selected to ensure good ventilation. Take care that any internal/external components of enclosure don’t obstruct air passage. (see section 2.2 GENERAL CHECKS BEFORE INSTALLATION)
The heat loss of the components installed inside of the electrical enclosure must be lower than useful cooling power of the AIR CONDITIONER.
AIR CONDITIONER IP-ACOW series must be handled in upright position and protected against accidental tipping over.
Do not modify the AIR CONDITIONER structure if it is not specified in these instruction or associated instructions.
During transportation of enclosures with installed air conditioner a proper bracket must be used to support the cooling unit weight.
Install only original spare parts and accessories. Protection against access to live parts must be warranty by installer.
The supply connector of the AIR CONDITIONER must only be connected and
disconnected when electrical enclosure is electrically disconnected.
Follow all technical data shown in this manual
Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
UMA-CDZ-IP-ACOWM200-00
Page 2/16
TABLE OF CONTENTS
WARNING ………………………………………………………………………………………………………………….2 1 – TECHNICAL DATA…………………………………………………………………………………………………….3 2 – INSTALLATION ………………………………………………………………………………………………………..4
2.1 PRODUCT HANDLING……………………………………………………………………………………….4 2.2 GENERAL CHECKS BEFORE INSTALLATION ……………………………………………………………4 2.3 FITTING …………………………………………………………………………………………………………5 3 – ELECTRICAL CONNECTION…………………………………………………………………………………………7 3.1 WIRING DIAGRAM…………………………………………………………………………………………..8
3.1.1 IP-ACOWM200 / IP-ACOWM200.0X ……………………………………………………………..8 4 – STARTING AND ADJUSTMENT ……………………………………………………………………………………9
4.1 DIGITAL THERMOSTAT……………………………………………………………………………………..9 5 – SPARE PARTS LIST………………………………………………………………………………………………….12 WARRANTY ……………………………………………………………………………………………………………… 13 UE DECLARATION OF CONFORMITY ……………………………………………………………………………… 14 SAA CERTIFICATE……………………………………………………………………………………………………….15
1 – TECHNICAL DATA
CONTROL TYPE
Digital thermostat
FEATURES
Power supply
Cooling capacity EN14511
A35-A35 A35-A50
Absorbed electric power EN14511
A35-A35 A35-A50
Rated current
Motor circuit breaker / Delayed pre fuse (advised)
Electrical connection
Air flow rate (free blow)
enclosure
Operating temperature
ambient enclosure
Refrigerant
Protection degree EN60529/1
ambient enclosure
casing
Design
cover
Weight Conformity / Certifications
Unit V | ph| Hz
W W W W A A m3/h °C (°F) °C (°F) – | g –
–
–
–
kg –
ARTICLE CODE
IP-ACOWM200
IP-ACOWM200.0X
230 | 1 | 50/60
2000/2100
1200/1250
1060 /1100
1240/1300
6.6/6.9
10
Three-pole connector
600/625
+5 |+55 (+41/+ 131)
+20 |+45 (+68/+ 113)
R134a | 450
IP34
IP54 (when installed on enclosure with the same protection degree)
Galvanised sheet steel
Galvanised sheet steel powder coated RAL7035
AISI304
49
CE, SAA
Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
UMA-CDZ-IP-ACOWM200-00
Page 3/16
2 – INSTALLATION
2.1 PRODUCT HANDLING
AIR CONDITIONER IP-ACOW series must be handled in upright position and protected against accidental tipping over.
Air conditioners IP-ACOW series are fitted with female blind threaded insert to screw male lifting eye bolts.
The air conditioner handling, when unpacked, can be done thanks to lifting eye bolt. If lifting eye bolts are not included, please provide an adequate M6 male lifting eye bolt (2) and screw it inside blind threaded (1) insert placed on top of the air conditioner. (For .0X version remove the rubber plugs or screws placed on the top of AISI304 cover, they cover the threaded inserts)
Check the proper fixing of eye bolts before lift the air conditioner.
2.2 GENERAL CHECKS BEFORE INSTALLATION
Before the installation make sure that the cabinet is disconnected from the electrical supply.
GENERAL CHECKS
– electrical enclosure must be disconnected form power supply
– electrical data shown on rating label pasted on air conditioner side must be
guaranteed
– Electrical enclosure must be sized according to air conditioner dimensions and
weight.
– Electrical enclosure must have at least IP54 protection degree
– Internal and external components of electrical enclosure don’t have to affect the
proper installation of air conditioner
– The installation site must be free from excessive dirt, aggressive ambient
conditions and moisture.
– The installation site must be free from hot air flows
– The internal side of electrical enclosure must be free from dirt and moisture
– The environment temperature must be within the range specified on label pasted
on air conditioner side
– Inside of electrical enclosure there must not be components that could affect the
proper ventilation
– the enclosure positioning with installed air conditioner must be carefully selected to
ensure good ventilation (clearance between the air conditioner and the near walls
must be at least 500 mm in each side).
– Proper disposing of condensate discharge
Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
UMA-CDZ-IP-ACOWM200-00
Page 4/16
2.3 FITTING
1) Make the fixing hole on the enclosure as is shown in the drilling template
Deburr all sharp edges to avoid accidental injuries
Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
UMA-CDZ-IP-ACOWM200-00
Page 5/16
2) Apply the gasket (included in fixing kit) on the back panel of the air conditioner.
3) Lift the air conditioner by lifting eyebolt and place it near the enclosure wall 4) Mount the air conditioner on the electrical cabinet according to the drilling template with
M6X16 screws and washers against unscrewing (included in mounting kit)
5) Connect the condensate drain pipe like is shown in picture below. (Put some glue on aluminium pipe before to insert it)
Air conditioner produces condensate because the moist air inside of the enclosure meets cold heat exchanger (evaporator) and then it becomes water; water production decreases during air conditioner working because enclosure air becomes dry.
The enclosure must be IP 54 protected, if enclosure is not airtight, condensate production could increase.
The enclosure IP54 degree is guaranteed only if the air conditioner is proper mounted.
Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
UMA-CDZ-IP-ACOWM200-00
Page 6/16
3 – ELECTRICAL CONNECTION
The electrical installation must be carried out by a qualified electrician who is responsible for compliance with the applicable standards and regulations.
Wire male plug (included) with an adequate cable as is shown by following picture
Cable section must be at least 1,5mm2
The male plug is fitted with spring terminals:
1) Push the spring with a screwdriver and then insert the wire.
2) Check the proper wire insertion. 3) Connect the unit with the power supply
Electrical data shown on rating label pasted on air conditioner side must be guaranteed.
Install the delayed fuse recommended on rating plate pasted on air conditioner side to protect the line and enclosure components against short-circuit.
Upstream of the electrical connection, an efficient disconnection system must be provided and it must be clearly identified
Air conditioner is already fitted with a temperature controller, no additional temperature control must be connected upstream of the unit.
Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
UMA-CDZ-IP-ACOWM200-00
Page 7/16
3.1 WIRING DIAGRAM 3.1.1 IP-ACOWM200 / IP-ACOWM200.0X
Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
UMA-CDZ-IP-ACOWM200-00
Page 8/16
4 – STARTING AND ADJUSTMENT
After finishing assembly of the conditioner, wait approx. 30 min. before starting it (the oil must collect in the compressor to ensure lubrication and cooling).
The air conditioner operates automatically, that is to say, after insertion, the evaporator fan operates continuously making the air inside the cabinet circulate. This way a uniform distribution of temperature inside the cabinet itself is attained. The built-in thermostat drives compressor and condenser fan according to set point value.
Compressor turns ON when internal enclosure temperature rises up to set point value + hysteresis and the minimum interval of two successive switch-on of the compressor (parameter C2) is elapsed.
Condenser fan turns ON when refrigerant pressure rises up to pressure switch set
Compressor and condenser fan turn OFF when internal enclosure temperature decreases below set point value.
4.1 DIGITAL THERMOSTAT
Indicator Set
Cooling
Symbol set
Status
On Off On Off Flash
Meaning
Set parameters Measuring & controlling
Cooling starts Cooling stops. Cooling delays.
Parameter list
Menu St Po C1
C2
C4
C5
C6
Function Temperature set-point
Admin. password Temperature differential The minimum interval of two successive switch-on of the compressor
Temperature calibration of cabinet sensor
Lower set-point. Min possible set-point
Higher set-point. Max possible set-point
Setting range C5 / C6 0 / 99 1 / 15°C 1 / 30°F
Default 31°C 55
4°C
Unit °C/°F
–
°C/°F
1 / 60
3
min
-10 / +10°C 0°C
-20 / +20°F -50°C/(C6-1)
20 58°F/(C6-1) (C5+1)/90°C
45 (C5+1)/194°F
°C/°F °C/°F °C/°F
Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
UMA-CDZ-IP-ACOWM200-00
Page 9/16
d1
Select evaporator sensor [1]
0 : disable 1 : enable
0
–
-10 / +10°C
d2
Temperature calibration of evaporator sensor [1]
0°C °C/°F
-20 / +20°F
0 / 60
d4
Defrost cycle
0: cancel defrost 0
30min
function
d7
Maximum defrost time
1 / 99
20
min
0 / +45°C
d8
Defrost stop temperature
7°C °C/°F
+32 / +115°F
A1
Compressor start and stop in the mode of “run/stop 00 : disable
in a proportional time”
01 : enable
01
–
A2
Compressor start time in case of cabinet sensor fault
01 /60
10
min
A3
Compressor stop time in case of cabinet sensor fault
01 /60
20
min
0 : disable
A4
Buzzer switch [2]
buzzer beeping 1 : enable
0
–
buzzer beeping
A5
Lower alarm. Min temp alarm value
-50°C/A6
-50°C °C/°F
58°F/A6
A5/90°C
A6
Higher alarm. Max temp alarm value
90°C °C/°F
A5/194°F
A7
Temperature alarm override
0/60
20
min
A8
Power-ON alarm override
0/60
40
min
00 : display
cabinet sensor
U1
Select temperature display sensor [1]
01 : display
0
–
evaporator
sensor
U2
Switch between Fahrenheit and Celsius [3]
00 : Fahrenheit 01 : Celsius
01
–
U3
Select defrost or light relay function
00 : defrost out. 01 : light output
00
–
[1]: no evaporator sensor available [2]: no buzzer available [3]: After switch between Celsius/Fahrenheit, the temperature set-point of parameter item St automatically adjusts to the corresponding temperature value of Celsius/Fahrenheit, and the temperature set-points of other parameter items relatedto Celsius/Fahrenheit automatically adjust accordingly. For example, St is set to 0, and it will automatically adjust to 32 after switch; C4 (calibration value of cabinet sensor) is set to +8,and it will automatically adjust to +20*(8/10)=+16.
Suggestion: Switch Celsius/Fahrenheit first, then adjust the value of related parameter items to ensure correct parameter
configuration.
Button name Set
Function Set parameters
Switch between menu and parameters
Action
Press it for 3 sec.
Press it and the controller responds.
Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
UMA-CDZ-IP-ACOWM200-00
Page 10/16
Button name Function Adjust menu and parameters Adjust menu and parameters Exit setting parameters
Action Press it and the controller responds.
Press it and the controller responds.
Press it and the controller responds.
Set-point adjustment
1) Press the Set button for 3 sec in status of measuring and controlling to enter user menu, the panel will display St.
2) Press the Set button again to display the parameter value of St, and modify the temperature set-
point by pressing or . WARNING: temperature which unit starts to work is St+C1. For example: St=31, C1=4 compressor and condenser fan turn on at 35°C (31°C+4°C)
Parameter adjustment
1) When St shows, press to display Po, and press Set to display 00; at this moment, use the button or to input the password of administrator menu (55).
2) After inputting the password 55, press Set to display Po. The controller will automatically verify
whether the password is correct.
3) When it passes verification, press or to select parameter items St, Po, C1, C2…… (i.e.
any parameter item of user menu and administrator menu); otherwise, the controller will only stay at the parameter items St and Po without displaying other parameter items.
4) After selecting the menu, press Set to enter the current menu and set its parameters. Use or to adjust parameter values, then press Set again to return to menu selection status.
5) Under any parameter setting status, press or press no button for 30 sec to exit parameter setting and save the current parameter value automatically.
Note: The password of administrator menu is valid for once. After exiting parameter settings by pressing , correct password must be entered again before adjusting parameters.
View temperature
1) When U1 (temperature display) =00, the controller displays the current temperature of cabinet
sensor.
2) When U1=01, the controller displays the current temperature of evaporator sensor.
(WARNING: no evaporator probe available on air conditioner)
Control output
Cooling: In normal status:
Refrigeration starts when the cabinet temperature > temperature set-point St + control differential C1, and
the indicated time must elapse between two successive minimum switch-on of the compressor.
Refrigeration stops when the cabinet temperature < temperature set-point St.
In case of cabinet sensor fault,
When A1=0, compressor start and stop time in the mode of “run/stop in a proportional time” is disabled,
refrigeration stops.
When A1=1, compressor start and stop time in the mode of “run/stop in a proportional time” is enabled, refrigeration performs in cycle according to the set refrigeration start A2 and stop A3 time in the mode of
“run/stop in a proportional time”.
Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
UMA-CDZ-IP-ACOWM200-00
Page 11/16
Alarm
Displayed code
E1
Cabinet sensor fault
Cause
E2
Evaporator sensor fault (shown if parameter d1=1)
Evaporator sensor is shut down, but the measured
E2C
temperature value of evaporator sensor is selected to
show. (shown if parameter U1=1)
rH
when temperature >A6 and alarm delay time run out, controller will display rH
rL
when temperature <A5 and alarm delay time run out, controller will display rL
5 SPARE PARTS LIST
REFERRED TO WIRING DIAGRAM 1 2 3 C1 C3 4 Pv
DESCRIPTION
Evaporator fan Compressor
Condenser fan Evaporator fan capacitor Condenser fan capacitor
Regulating thermostat Pressure switch
Supply connector (male plug)
CODE VCENT190D230V
COMPRSC21G VCENT220D230V
CON2UFS2M8F CON2UFS2M8F ALFADT01S1 PRSWO7-C10
SPINALIM3
Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
UMA-CDZ-IP-ACOWM200-00
Page 12/16
WARRANTY
WE IP ENCLOSURES
guarantees that the product is free from any quality defects. The product is guaranteed for a period of 12 months from the date of delivery, provided it operates under the following conditions:
1. value of power supply indicated in the data plate is completely respected; 2. requirements specified on user’s manual are completely respected; 3. cabinet temperature is not higher or lower than its rated temperature; 4. ambient temperature is not higher or lower than its rated temperature; 5. the product is mounted on cabinets with a minimum IP54 protection level; 6. the product is mounted on cabinets that not requiring higher cooling power than
expected; 7. the product is clearly identifiable by serial number.
The warranty does not apply if : 1. the cooling circuit has been modified about type and quantity of refrigerant or composition; 2. the unit operates in acid or corrosive ambient; 3. the unit has been modified without IP ENCLOSURES consent.
This warranty shall become null as soon as the product is altered or modified in its structure or in circuits. The terms of this warranty (commencement and termination dates) are not modified by any repair or replacement of products. For every part that results defective during the period of this warranty, IP ENCLOSURES shall repair or replace it. Any others charges arising from removal, handling and installation of the products shall not be refunded by IP ENCLOSURES. Like is specified on user’s manual, installation, handling, the correct earthing in accordance with all current standards are under the responsibility of costumer. In the event of any damage caused by a defective product shall apply the EEC85.374 standard. The malfunction must be communicated in writing to IP ENCLOSURES. Warranty is void if the costumer is not in good standing with the payments
Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
UMA-CDZ-IP-ACOWM200-00
Page 13/16
UE DECLARATION OF CONFORMITY
WE
IP ENCLOSURES
DECLARE THAT THE AIR CONDITIONER FOR ELECTRICAL CABINETS
IP-ACOW series
DO COMPLY WITH THE FOLLOWING DIRECTIVES
2006/42/CE MACHINERY DIRECTIVE (17 May 2006) 2014/35/UE LOW VOLTAGE DIRECTIVE (26 February 2014)
2014/30/UE EMC DIRECTIVE (26 February 2014) 2011/65/UE ROHS DIRECTIVE (8 June 2011)
STANDARDS APPLIED TO MEET THE PRINCIPAL ELEMENTS OF THE DIRECTIVE
EN 60335-2-40:2003; A1; A2 (IEC 60335-2-40: 2002; A1; A2) EN 60335-1: 2010; A11; A13; A14; A1; A2 (IEC 60335-1; A1; A2)
OTHER STANDARDS APPLIED
EN 55014-1: 2017 EN 55014-2: 2015 EN IEC 61000-3-2: 2019 EN 61000-3-3: 2013
Description Declaration of Conformity for air conditioner IP-ACOW
ISSUE REV. 1 REV. 2 REV. 3
Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
UMA-CDZ-IP-ACOWM200-00
Date 01/06/2020
Name
Page 14/16
SAA CERTIFICATE
Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
UMA-CDZ-IP-ACOWM200-00
Page 15/16
NOTES
Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
UMA-CDZ-IP-ACOWM200-00
Page 16/16