Danfoss Co2 Module Controller Universal Gateway User Guide

Danfoss Co2 Module Controller Universal Gateway User Guide

Danfoss - logoCO2 Module Controller Universal Gateway
User Guide
Danfoss CO2 Module Controller Universal Gateway

Electric Installation

Below is an illustration of the external connections that can be made in the remote control assembly.Danfoss CO2 Module Controller Universal Gateway - Figure 1

Power supply to CDU
230V AC 1,2m cable for this is included.

Danfoss CO2 Module Controller Universal Gateway - Figure 2
Connect Module controller power supply cable to L1 (left terminal) and N (right terminal) of the condensing unit control panel – power
supply terminal block
Caution: If the cable needs to be replaced, it must either be short-circuit proof or it must be protected by a fuse on the other end.
Danfoss CO2 Module Controller Universal Gateway - Figure 3

RS485-1
Modbus interface for connection to the System Manager
RS485-2
Modbus interface for connection to the CDU.
1,8 m cable for this is included.
Connect this RS485-2 Modbus cable to terminal A and B of the condensing unit control panel – Modbus interface terminal block. Do not connect insulated shield to ground Danfoss CO2 Module Controller Universal Gateway - Figure 4

RS485-3
Modbus interface for connection to the evaporator controllers
3x LED Function explanation

  • Blue led is ON when the CDU is connected and polled operation is complete
  • Red led is flashing when there is a communication fault with an evaporator controller
  • Green led is flashing during communication with an evaporator controller The green LED next to the 12V power supply terminals indicates “Power OK”.

Electric noise
Cables for data communication must be kept separate from other electric cables:
– Use separate cable trays
– Keep a distance between cables of at least 10 cm.

Mechanical Installation

  1. Installation in the backside of the unit / backside of e-panel with provided rivets or screws (3 mounting holes provided)

Procedure:

  • Remove CDU panel
    Danfoss CO2 Module Controller Universal Gateway - Figure 5
  • Mount the bracket with provided screws or rivets
  • Fix the e-Box to the bracket (4 screws provided)
  • Route and connect the provided Modbus and power supply cables to the CDU control panel
  • Route and connect the evaporator controller Modbus cable to the Module controller
  • Option: Route and connect the System Manager Modbus cable to the Module controller

Optional installation on the frontside (only for 10HP unit, just beside the CDU control panel, holes to be drilled)
Procedure:

  • Remove CDU panel
    Danfoss CO2 Module Controller Universal Gateway - Figure 6
  • Mount the bracket with provided screws or rivets
  • Fix the e-Box to the bracket (4 screws provided)
  • Route and connect the provided Modbus and power supply cables to the CDU control panel
  • Route and connect the evaporator controller Modbus cable to the Module controller
  • Option: Route and connect the System Manager Modbus cable to the Module controller

Module Controller wiring

Please wire the communication cable from the top of the control bord to the left side. The cable comes along with the module controller.

Danfoss CO2 Module Controller Universal Gateway - Figure 7.

Please pass the power cable through the insulation at the bottom of the control box.

Danfoss CO2 Module Controller Universal Gateway - Figure 8

Note:
The cables should be fixed with the cable ties and should not touch the baseplate to avoid water ingress.

Technical data

Supply voltage110-240 V AC. 5 VA, 50 / 60 Hz
DisplayLED
Electrical connectionPower supply: Max.2.5 mm2 Communication: Max 1.5 mm2
-25 — 55 °C, During operations -40 — 70 °C, During transport
20 – 80% RH, not condensed
No shock influence
ProtectionIP65
MountingWall or with included bracket
WeightTBD
Included in the package1 x Remote control assembly
1 x Mounting bracket
4 x M4 screws
5 x Inox rivets
5 x Sheet metal screws
ApprovalsEC Low Voltage Directive (2014/35/EU) – EN 60335-1
EMC (2014/30/EU)
– EN 61000-6-2 and 6-3

Dimensions
Units in mmDanfoss CO2 Module Controller Universal Gateway - Figure 9

Spare parts

Danfoss Requirements
Parts NameParts NoGross
weight
Unit Dimension (mm)Packing StyleRemarks
KgLengthWidthHeight

CO2 MODULE CONTROLLER UNIVERSAL GATEWAY

MODULE CONTROLLER118U5498TBD18290180Carton box

Operation

Display
The values will be shown with three digits.Danfoss CO2 Module Controller Universal Gateway - Figure 10

Danfoss CO2 Module Controller Universal Gateway - icon 2Active alarm (red triangle)
Scan for Evap. controller is in progress (yellow clock)

When you want to change a setting, the upper and the lower button will give you a higher or lower value depending on the button you are pushing. But before you change the  value, you must have access to the menu. You obtain this by pushing the upper button for a couple of seconds – you will then enter the column with parameter codes. Find the parameter code you want to change and push the middle buttons until value for the parameter is shown. When you have changed the value, save the new value by once  more pushing the middle button. (If not operated for 10 seconds, the display will change back to showing the suction pressure in temperature).

Examples:
Set menu

  1. Push the upper button until parameter code r01 is shown
  2. Push the upper or the lower button and find that parameter you want to change
  3. Push the middle button until the parameter value is shown
  4. Push the upper or the lower button and select the new value
  5. Push the middle button again to freeze the value.

See alarm code
A short press of the upper button
If there are several alarm codes they are found in a rolling stack.
Push the uppermost or lowermost button to scan the rolling stack.
Set point

  1. Push upper button until display shows parameter menu code r01
  2. Select and change par. r28 to 1, which defines the MMILDS UI as the reference set device
  3. Select and change par. r01 to the required lower pressure setpoint target in bar(g)
  4. Select and change par. r02 to the required upper pressure setpoint target in bar(g)

Remark: The arithmetic middle of r01 and r02 is the target suction pressure.
Get a good start
With the following procedure you can start regulation as soon as possible.

  1. Connect the modbus communication to CDU.
  2. Connect the modbus communication to evaporator controllers.
  3. Configure the address in each evaporator controller.
  4. Perform a network scan in the module controller (n01).
  5. Verify that all evap. controllers have been found (Io01-Io08).
  6. Open parameter r12 and start the regulation.
  7. For connection to a Danfoss System Manager
    – Connect the modbus communication
    – Set the address with parameter o03
    – Perform a scan in the System Manager.

Survey of functions

FunctionParameterRemarks
Normal display
The display shows the suction pressure in temperature.
Regulation
Min. Pressure
The lower setpoint for suction pressure. See instructions for CDU.
r01
Max. Pressure
The upper set point for suction pressure. See instructions for CDU.
r02
Demand Operation
Limits the compressor speed of the CDU. See instructions for CDU.
r03
Silent Mode
Enable/disable silent mode.
Operating noise is suppressed by limiting the speed of the outdoor fan and compressor.
r04
Snow Protection
Enable/disable snow protection functionality.
To prevent snow from building up on the outdoor fan during winter shutdown, the outdoor fan is operated at regular intervals to blow off the snow.
r05
Main Switch Start/stop the CDUr12
Reference source
The CDU can either use a reference that is configured with rotary switches in the CDU, or it can use the reference as defined by parameter r01 and r02. This parameter configures which reference to use.
r28
For Danfoss Only
SH Guard ALC
Cut-out limit for ALC control (oil recovery)
r20
SH Start ALC
Cut-in limit for ALC control (oil recovery)
r21
011 ALC setpol M LBP (AK-CCSS parameter P87,P86)r22
SH Close
(AK-CC55 parameter —)
r23
SH Setpolnt
(AK-CCSS parameter n10, n09)
r24
EEV force low OD after oil recovery (AK-CCSS AFidentForce =1.0)r25
011 ALC setpol M MBP (AK-CCSS parameter P87,P86)r26
011 ALC setpoint HBP (AK-CC55 parameter P87,P86)r27
Miscellaneous
If the controller is built into a network with data communication, it must have an address, and the system unit of the data communication must then know this address.
The address is set between 0 and 240, depending on the system unit and the selected data communication.3
Evaporator controller addressing
Node 1 Address
Address of the first evaporator controller
Will only be shown if a controller has been found during scan.
lo01
Node 2 Address See parameter lo011002
Node 3 Address See parameter lo01lo03
Node 4 Address See parameter lo011004
Node 5 Address See parameter 10011005
Node 6 Address See parameter lo011006
Node 7 Address See parameter 10011007
Node 8 Address
See parameter lo01
Ion
Node 9 Address See parameter 10011009
FunctionParameterRemarks
Node 10 Address See parameter lo011010
Node 11 Address See parameter lo01lol 1
Node 12 Address See parameter 10011012
Node 13 Address See parameter 10011013
Node 14 Address See parameter lo011014
Node 15 Address See parameter 1001lo15
Node 16 Address See parameter 10011016
Scan Network
Initiates a scan for evaporator controllers
nO1
Clear Network List
Clears the list of evaporator controllers, may be used when one or several controllers are removed, proceed with a new network scan (n01) after this.
n02
Service
Read discharge pressureu01Pc
Read gascooler outlet temp.U05Sgc
Read receiver pressureU08Prec
Read receiver pressure in temperatureU09Trec
Read discharge pressure in temperatureU22Tc
Read suction pressureU23Po
Read suction pressure in temperatureU24To
Read discharge temperatureU26Sd
Read suction temperatureU27Ss
Read controller software versionu99
Operating status(Measurement)
Push briefly (Is) the upper button. A status code will be shown on the display. The individual status codes have the following meanings:Ctrl. state
CDU not operationalSO0
CDU operationalSi1
Other displays
Oil recoveryOil
No communication with CDU

Fault message
In an error situation an alarm symbol will flash..
If you push the top button in this situation you can see the alarm report in the display.
Here are the messages that may appear:

Code/Alarm text via data communkationDescriptionAction
E01 / COD offlineCommunication lost with CVCheck CDU connection and configuration (SW1-2)
E02 / CDU communication errorBad response from CDUCheck CDU configuration (SW3-4)
Al7 /CDU alarmAn alarm has occurred in the CDUSee instructions for CDU
A01 / Evap. controller 1 offlineCommunication lost with evap. controller 1Check Evap. controller controller and connection
A02 / Evap. controller 2 offlineCommunication lost with evap. controller 2See A01
A03 / Evap. controller 3 offlineCommunication lost with evap. controller 3See A01
A04 / Evap. controller 4 offlineCommunication lost with evap. controller 4See A01
A05 / Evap. controller 5 offlineCommunication lost with evap. controller 5See A01
A06/ Evap. controller 6 offlineCommunication lost with evap. controller 6See A01
A07 / Evap. controller 7 offlineCommunication lost with evap. controller 7See A01
A08/ Evap. controller 8 offlineCommunication lost with evap. controller 8See A01
A09/ Evap. controller 9 offlineCommunication lost with evap. controller 9See A01
A10 / Evap. controller 10 offlineCommunication lost with evap. controller 10See A01
All / Evap. controller 11 offlineCommunication lost with evap. controller 11See A01
Al2 / Evap. controller 12 offlineCommunication lost with evap. controller 12See A01
A13 /Evap. controller 13 offlineCommunication lost with evap. controller 13See A01
A14 /Evap. controller 14 offlineCommunication lost with evap. controller 14See A01
A15 /Evapt controller 15 offlineCommunication lost with evap. controller 15See A01
A16 / Evapt controller 16 offlineCommunication lost with evap. controller 16See A01

Menu survey

FunctionCodeMinMaxFactoryUser-Setting
Regulation
Min. Pressurer010 bar126 barCDU
Max. Pressurer020 bar126 barCDU
Demand Operationr03030
Silent Moder04040
Snow Protectionr050 (OFF)1 (ON)0 (OFF)
Main Switch Start/stop the CDUr120 (OFF)1 (ON)0 (OFF)
Reference sourcer28011
For Da nfoss Only
SH Guard ALCr201.0K10.0K2.0K
SH Start ALCr212.0K15.0K4.0 K
011 ALC setpoint LBPr22-6.0K6.0 K-2.0 K
SH Closer230.0K5.0 K25 K
SH Setpointr244.0K14.0K6.0 K
EEV force low OD after oil recoveryr250 min60 min20 min
Oil ALC setpoint MBPr26-6.0K6.0 K0.0 K
011 ALC setpoint HBPr27-6.0K6.0K3.0K
Miscellaneous
CDU Addresso0302400
Evap. controller Addressing
Node 1 Addresslo0102400
Node 2 Addresslo0202400
Node 3 Addresslo0302400
Node 4 Addresslo0402400
Node 5 Addresslo0502400
Node 6 Address10602400
Node 7 Addresslo0702400
Node 8 Addresslo0802400
Node 9 AddressloO802400
Node 10 Addresslo1002400
Node 11 Addressloll02400
Node 12 Addresslo1202400
Node 13 Addresslo1302400
Node 14 Address1o1402400
Node 15 Addresslo1502400
Node 16 Address1o1602400
Scan Network
Initiates a scan for evaporator controllers
nO10 OF1 ON0 (OFF)
Clear Network List
Clears the list of evaporator controllers, may be used when one or several controllers are removed, proceed with a new network scan (n01) after this.
n020 (OFF)1 (ON)0 (OFF)
Service
Read discharge pressureu01bar
Read gascooler outlet temp.UOS°C
Read receiver pressureU08bar
Read receiver pressure in temperatureU09°C
Read discharge pressure in temperature1122°C
Read suction pressure1123bar
Read suction pressure in temperatureU24°C
Read discharge temperatureU26°C
Read suction temperatureU27°C
Read controller software versionu99

Danfoss A/S Climate Solutions  danfoss.com • +45 7488 2222
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

© Danfoss | Climate Solutions | 2023.01

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals