Renatta Type 485 Light Temperature And Humidity Transmitter Illuminance Transmitter Instruction Manual

type 485 Light Temperature and Humidity Transmitter Illuminance Transmitter

Product Information

Product Name: Illuminance Transmitter (Modbus
type) V2.1

Product Type: Light Temperature and Humidity
Transmitter

Manufacturer: Renatta Control Technology

Document Version: V2.1

Description: The illuminance transmitter is a
high-precision photosensitive device that measures light intensity
in Lux. It is designed with a wall-mounted waterproof shell and
offers high protection level. The transmitter uses 485
communication and standard ModBus-RTU communication protocol. The
communication address and baud rate can be set, and the maximum
communication distance is 2000 meters. It operates on a wide
voltage power supply of 10-30V and is suitable for applications
such as agricultural greenhouses, flower cultivation greenhouses,
agricultural fields, and electronics equipment production lines
where light intensity monitoring is required.

Features:

  • High-precision illuminance detection with a measurement range
    of 0-6 million Lux (0-20 million Lux optional)
  • 485 communication with standard ModBus-RTU communication
    protocol
  • Wall-mounted waterproof shell with high protection level for
    outdoor or harsh environments
  • Wide voltage power supply of 10-30V DC

Main Specifications:

  • DC Power Supply: 10-30VDC (default)
  • Maximum Power Consumption: 0.4W
  • Humidity Accuracy: -40~+60°C, 0-80%RH
  • Temperature and Humidity Range: -40~+60°C, 0-80%RH
  • Long-term Stability: Temperature – 0.1%/year, Humidity –
    1%/year, Light intensity – 5%/year
  • Response Time: Light intensity – 0.1s
  • Output Signal: RS485 (Modbus protocol)

Product Model: RSGZ-GZWS-N01265535 200000

System Framework Diagram:

System Framework Diagram

Product Usage Instructions

1. Equipment Installation Instructions

1.1 Check before Installation

Equipment List:

  1. 1 transmitter device
  2. USB to 485 (optional)
  3. Warranty card, certificate, wiring instructions, etc.

1.2 Installation Method

Follow the installation instructions provided in the user
manual.

1.3 Interface Description

The wide voltage power input can be 10-30V. When connecting the
485 signal line, make sure that the A/B lines are not reversed and
that the addresses of multiple devices on the bus do not
conflict.

Thread ColorExplanation
BrownPositive power supply (10-30V DC)
BlackNegative power supply
Yellow485-A
Blue485-B

1.4 485 Field Wiring Instructions

When multiple 485 model devices are connected to the same bus,
there are specific requirements for field wiring. Please refer to
the examination data package 485 equipment field wiring manual for
detailed instructions.

2. Configuration Software Installation and Use

Follow the instructions provided in the user manual for
installing and using the configuration software.

Instruction manual of illuminance transmitter (Modbus type) V2.1
Light Temperatureand Humidity Transmitter
Instruction Manual (type 485)
ILLUMINANCE TRANSMITTER

Renatta Control Technology

Document versionV2.1
1

Table of Contents 1. product description……………………………………………………………………………………………………4 2. Equipment installation instructions……………………………………………………………………………. 5 3. Configuration software installation and use…………………………………………………………………7 4. letter of agreement……………………………………………………………………………………………………8 5. Common problems and solutions…………………………………………………………………………….. 13 6. contact details…………………………………………………………………………………………………………14 7. Document history……………………………………………………………………………………………………14 8. Appendix: Shell dimensions…………………………………………………………………………………….14

Renatta Control Technology

2

1. product description
1.1 product description

It is a high-precision photosensitive transmitter, the output value measurement unit is Lux, the

device adopts a wall-mounted waterproof shell, wall-mounted installation, and high protection

level. 485 communication, standard ModBus-RTU communication protocol, communication

address and baud rate can be set, the longest communication distance is 2000 meters, the product

power supply is 10-30V wide voltage power supply, mainly used in agricultural greenhouses,

flower cultivation greenhouses, agricultural fields, electronics Equipment production lines and

other occasions that require light intensity monitoring.
1.2 Features

1. High-precision illuminance detection measurement range of 0-6 million Lux, 0-20 million Lux

optional.

2.485 communication, standard ModBus-RTU communication protocol, communication address

and baud rate can be set, the longest communication distance is 2000 meters

3. Wall-mounted waterproof shell, high protection level, can be used in outdoor or harsh on-site

environment

4.10-30V DC wide voltage power supply
1.3 Main Specifications

DC power supply

10-30VDC

(default)

Maximum power

0.4W

consumption

humidity

±3%RH(5%RH~95%RH,25)

Accuracy

temperature

±0.525

Light intensity

±7%(25)

Light intensity range

0-65535Lux0-200000Lux

Temperature and

-40~+600%RH~80%RH

humidity range

Long-term stability

temperature

0.1/y

humidity

1%/y

Light intensity

5%/y

temperature

18s(1m/s Wind speed)

humidity

6s(1m/s Wind speed)

Response time

Light intensity

0.1s

Renatta Control Technology

3

output signal
1.4product model
RSGZ-
GZWS-
N01265535 200000
1.5System framework diagram

RS485(Modbus protocol)
Company code Light intensity transmission sensor Light intensity, temperature and humidity three in one transmission, sensor
RS485 (M0dbus protocol) Wall-mounted king character shell
Range 0-65535 Range 0-20W

AC220V mains

UPS power supply (optional)

Monitor computer

10~30V DC

485 bus

USB to 485 or 232 to 485

Device 2nt No. 1

Device 2

Device 3

System solution block diagram
2. Equipment installation instructions
2.1 Check before installation
Equipment List: 1. 1 transmitter device 2. USB to 485 (optional) 3. Warranty card, certificate, wiring instructions, etc.

Renatta Control Technology

4

Device n

2.2installation method

2.3Interface Description

Wide voltage power input can be 10 ~ 30V. When connecting the 485 signal line, please note

that the A / B lines cannot be reversed, and the addresses of multiple devices on the bus must not

conflict.

Thread color

Explanation

power supply

brown

Positive power supply (10 ~ 30V

DC)

black

Negative power supply

Communication

yellow

485-A

blue

485-B

2.4 485Field wiring instructions
When multiple 485 model devices are connected to the same bus, there are certain requirements for field wiring. For details, please refer to

Renatta Control Technology

5

Examination data package “485 equipment field wiring manual”.

3. Configuration software installation and use
3.1 Software selection
Open the data package, select “Debug software” — “485 parameter configuration software”, find “485 parameter configuration tool” Just open it.
3.2parameter settings
, select the correct COM port (“COM”-“Properties-Device Manager-Port” to view the COM port), the following figure lists the driver names of several different 485 converters.
, only connect one device and power on, click the test baud rate of the software, the software will test the current device baud rate and address, the default baud rate is 4800bit / s, the default address is 0x01.

Modify the address and baud rate according to the needs of use, and at the same time, you can query the current functional status of the device.
If the test is unsuccessful, please recheck the device wiring and 485 driver installation.

Renatta Control Technology

6

4. letter of agreement
4.1 Communication basic parameters

Coding

8-bit binary

Data bit

8 bit

Parity bit

no

Stop bit

1 person

Error checking

CRC (Redundant Cyclic Code)

Renatta Control Technology

7

Baud rate 2400bit / s, 4800bit / s, 9600 bit / s can be set, the factory default is 4800bit / s
4.2 Data frame format definition
Using Modbus-RTU communication protocol, the format is as follows: Time for initial structure 4 bytes Address code = 1 byte Function code = 1 byte Data area = N bytes Error check = 16-bit CRC code End structure 4 bytes of time Address code: the address of the transmitter, which is unique in the communication network (factory default 0x01). Function code: the instruction function instruction issued by the host, this transmitter only uses the function code 0x03 (read register data). Data area: The data area is specific communication data, pay attention to the high byte of 16bits data first! CRC code: two-byte check code. Host inquiry frame structure:

address code

function code

Register start address

Register length

Check digit high Check digit low

1byte

1byte

2byte

2byte

1byte

1byte

Slave response frame structure:

address code

function code

Effective bytes

Second data Data area
area

Nth data area

Check code

1byte

1byte

1byte

2byte

2byte

2byte

2byte

4.3 Register address

Register address PLC or configuration

content

operating

address

0000 H

40001

humidity

Read only

0001 H

40002

temperature

Read only

0002 H

40003

Illuminance

Read only

0003 H

40004

(Only enabled in

0~200000Lux, unit is

1Lux)

Renatta Control Technology

8

0006 H

40007

Illuminance

Read only

(0~65535 unit 1Lux

0~200000 unit

hundred Lux)

4.4 Communication protocol example and explanation

4.4.1 Read the temperature and humidity value of device address 0x01

Inquiry frame

starting addre

Check digit lo Check digit hi

address code function code

Data length

ss

w

gh

0x01

0x03

0x00 0x00 0x00 0x02

0xC4

0x0B

Response frame (for example, read temperature is -10.1 , humidity is 65.8% RH)

address co function co Effective byt Humidity va Temperature Check digit Check digit

de

de

es

lue

value

low

high

0x01

0x03

0x04

0x02 0x92 0xFF 0x9B 0x5A

0x3D

Temperature: When the temperature is lower than 0 , upload in the form of complement FF9B H (Hexadecimal) = -101 => Temperature = -10.1 humidity: 292 H (hex) = 658 => humidity = 65.8% RH
4.4.2Read the illuminance value at device address 0x01 (0 ~ 65535 is read in units of 1 Lux or 0 ~ 200000 is read in units of 100 Lux)
Inquiry frame

function cod starting addres

Check digit lo Check digit hi

address code

Data length

e

s

w

gh

0x01

0x03

0x00 0x06 0x00 0x01

0x64

0x0B

Acknowledge frame (for example, read the illuminance of 30000 Lux)

address cod function cod Returns the numb

Check digit lo Check digit hi

Data area

e

e

er of valid bytes

w

gh

0x01

0x03

0x02

0x05 0x30

0xBB

0x00

Illumination calculation instructions: 1) The product is a 0~65535 range transmitter, the unit is 1Lux
0530 H (hexadecimal) = 1328 => illuminance = 1328 Lux

Renatta Control Technology

9

2) The product is a 0~200000 range transmitter, the unit is 100 Lux 0530 H (hexadecimal) = 1328 => illuminance = 132800 Lux
4.4.3 Read the illuminance value of the device address 0x01 (0 ~ 200000 is read in units of 1 Lux)
Inquiry frame

function cod starting addres

Check digit lo Check digit hi

address code

Data length

e

s

w

gh

0x01

0x03

0x00 0x02 0x00 0x02

0x65

0xCB

Acknowledge frame (for example, read the illumination of 200,000 Lux)

address c function co Effective byte High illumin Low illumin Check digit Check digit

ode

de

s

ation

ation

low

high

0x01

0x03

0x04

0x00 0x03 0x0D 0x40

0x0F

0x53

Illumination calculation instructions: This protocol is only used under 0 ~ 200000Lux range transmitter, the unit is 1Lux
30D40 H (Hexadecimal) = 200000 => Illumination = 200000 Lux
4.4.4 Read the temperature, humidity and illuminance value of the device address 0x01 (0~65535 are read in units of 1Lux)
Inquiry frame

starting addre

Check digit lo Check digit hi

address code function code

Data length

ss

w

gh

0x01

0x03

0x00 0x00 0x00 0x07

0x04

0x08

Reply frame

addre functio Numb Humidi Temperatu 000 000 000 000 illu Che High

ss

n code er of ty value re value 2 3 4 5 min ck bit

code

bytes

atio cod of

n e chec

low k

bit code

0x01 0x03 0x0E 0x01 0x00

Inv Inv Inv Inv 0x8 0xB 0X4

0x7E 0xE7

alid alid alid alid 5 3 D

data data data data 0x1

F

Renatta Control Technology

10

humidity

17E H (hexadecimal) = 382 => humidity = 38.2%RH

temperature

0E7 H(hexadecimal)=231=> temperature = 23.1

illumination

851F H(Hexadecimal)=34079=> Illumination=34079Lux

(0~200000 is read in units of 1Lux and hundreds of Lux)

Interrogation frame

address code unction code initial address Data length Check code High bit of

low bit

check code

0x01

0x03

0x00 0x00

0x00 0x07

0x04

0x08

Reply frame

addre functi Num Humid Tempera Hi Lo 0004 0005 illuminat Che Hig

ss on ber of ity

ture

gh w

ion

ck h

code code bytes value value

lig lig

Hundred code bit

ht ht

Lux

low of

bit che

ck

cod

e

0x01 0x03 0x0E 0x01 0x00

0x 0x8 Inval Inval 0x01

0x2 0x2

0x7E 0xE7

00 5 id id 0x54

DC

0x 0x1 data data

00 F

humidity

017E H (hexadecimal) = 382 => humidity = 38.2%RH

temperature

00E7 H(hexadecimal)=231=> temperature = 23.1

illumination

0000 851F H(Hexadecimal)=34079 => Illumination =34079Lux

Light (100 Lux)

0154H (hexadecimal) = 340 => light = 340 hundred Lux = 34000 Lux

4.4.5 Read the temperature, humidity and illuminance value of device address

0x01(0 ~ 200000 is read in 1 Lux unit)

Renatta Control Technology

11

starting addre

Check digit lo Check digit hi

address code function code

Data length

ss

w

gh

0x01

0x03

0x00 0x00 0x00 0x04

0x44

0x09

Reply frame

address function code code

Bytes Humidity v Temperatur High light

Check cod

Low light

alue

e value

e

0x01 0x03 0x08 0x02 0x92 0x80 0x65 0x00 0x03 0x0D 0x40 0x01 0x6F
5. Common problems and solutions
5.1 Device cannot be connected to PLC or computer
possible reason: 1) The computer has multiple COM ports, and the selected port is incorrect. 2) The device address is wrong, or there are devices with duplicate addresses (the factory default is all 1). 3) Baud rate, check mode, data bit, stop bit error. 4) The host’s polling interval and waiting time for answering are too short, and both need to be set above 200ms. 5) The 485 bus is disconnected, or the A and B lines are reversed. 6) If the number of devices is too large or the wiring is too long, power should be supplied nearby, and a 485 booster should be added, and 120 terminal resistance should be added at the same time. 7) The USB to 485 driver is not installed or damaged. 8) The equipment is damaged.