Honeywell Home Tf428wnm/u Communicating Thermostat User Manual

Honeywell Home Tf428wnm/u Communicating Thermostat User Manual

Honeywell Home TF428WNM/U Communicating Thermostat User Manual
Honeywell Home TF428WNM/U Communicating Thermostat

Operating Your Thermostat

power on off Power on/Off
Time OFF Time OFF

  • Presspower on off to switch on/off thermostat. When in off mode, “OFF” icon will display.
  • PressTime OFF could set the automatical turn off time when the thermostat is working. PressTime OFF and hold for more than 3s. After timer icon flashes, press or to set turn off time, then press 0 button to save and exit.
Temperature Setting

In or or mode, press or to set the target room temperature.

Operating Mode
  • Ventilation
  • Heating
  • Cooling
  • Auto

Fan Speed

LCD DISPLAY

LCD DISPLAY

Trouble Shooting Tips

If….Then….
Doesn’t work·   Set the mode to(heating mode) by press

·   Make sure the temperature is set above the room temperature.

·   Make sure shows on the display.

·   Wait 5 minutes for the system to respond.

Doesn’t work·   Set the mode to :i: (cooling mode) by press.

. Make sure the temperature is set below the room temperature.

·  Make sure  shows on the display.

·  Wait 5 minutes for the system to respond.

Doesn’t work·  Make sure keypad is unlocked.

·  Check the thermostat is on.

Doesn’t work·   Make sure keypad is unlocked.

– Make sure the system isn’t in mode.

·   Check the thermostat is on.    —

The system turns off automatically.Make sure the memorized turn off time value isn’t set to Ir.
Display ·   Check the Modbus address and Baud rate, use master to read registers.

·   Check the wiring.

4 Pipes Valve doesn’t work-Check 151J setup.

·                  Check the wiring.

Installation Guide

Must be installed by a trained and experienced installer

Read instruction carefully. Failure to follow instruction will damage the product or cause a hazardous condition.

Caution: ELECTRICAL HAZARD can cause electrical shock or equipment damage. Disconnect power before installation, reparation and detachment.

Installation Tips

TF428WNM/U is designed for standard 75x75x50mm wall mounting box . Install the thermostat about 5 feet (1.5m) above the floor in an area with good air circulation at average temperature.
Installation Tips

Do not install in locations where the thermostat can be affected by:

  • Dead spots behind doors and in corners
  • Not or cold air from ducts
  • Sunlight or radiant heat from appliances
  • Concealed pipes or chimneys
Wiring and Installation

The screw must be locked tightly to avoid wire break off from the terminal. The wire should not be tangled and stucked between front case assembly and back case.

Request Shielded Twisted Pair(STP) wire for R5485 communication. Separate the low voltage and high voltage wiring. Max 32 pcs in one loop, do not connect to unauthorized devices. Select proper terminal resistor based on application environment.

Wiring and Installation

Modbus Requirements

Physical layerEIA485
ProtocolMaster-Slave
Baud rate9600 (Default) /4800/19200
ParityNone
Signal TransmissionRTU
Error Checking MechanismCRC

Terminal Designations

TerminalSymbolDescription
1D-Modbus 485-
2D+Modbus 485+
3FLLow speed fan
4EMMedium speed fan
5FHHigh speed fan
6V22-pipe-VC6013:Valve close 4-pipe-VC4013:Cooling Vavle open
7v12-pipe-VC4013NC6013:Valve open 4-pipe-VC4013:Heating Vavle open
8LLive wire
9NNeutral wire

The temperature of mounting box and wall should be in the operating temperature range.

VC401 3/VN401 3NS401 6 Wiring (2-pipe) 


VC6013/VN6013 Wiring(2 pipe)


VC4013/VN4013VS4016 Wiring(4 pipe)

ISU (INSTALLATION SETUP)

Enter or exit Installation Setup Mode

ISU CodeDescriptionOptions
0Modbus Address1-64 1(Default)
1System Type0-Heat only
1-Cool only
2-2-pipe manual (Default)
4-4-pipe manual
5-4-pipe auto change over
2Temperature Scale0-°F 1-°C (Default)
3Fan Control Type0-Auto only
1-Manual only (3 speed: Low –,Med->High-.Low)
2-Users can choose auto or cycle (Default)
4Switching Differential For 4-pipe Auto Changeover Eith Single Set point1°C (2°F)
1.5°C (3°F) (Default)
2°C (4°F)
3°C (5°F)
5CPH Value (Heat)1-12 4(Default)
6CPH Value (Cool)1-6 3(Default)
7Display Temperature Adjustment-2-2°C, Step 0.5°C 0°C (Default) ( -4-4° F, Step 1°F 0°F (Default))
8Temperature Display0-Room temperature (Default)
1-Setpoint
9Heating Range Stops10-32 °C32 °C (Default) (50-90 °F 90 °F (Default))
10Cooling Range Stops10-32 °C 10 °C (Default) (5090°F 50 °F (Default))
11Keypad Lockout0-All keys are available (Default)
1-System button is locked
2-Fan and System button are locked
3-All buttons are locked except power button
4-All buttons are locked
12Freeze Protection0-Disable       1Enable (Default)
13Power Recovery Status0-OFF 1-Previous status (Default)
14Modbus Baud rate0-Baudrate 9600 (Default)
1-Baudrate 4800
2-Baudrate 19200

NOTE: When the thermostats are integrated into building automation system, user is able to change the setting value above in “Communicating Parameter Setting” list as well.

Communicating Parameter Setting

When the thermostat is integrated into building automation system, you can make configuration refer below list.

AddrConfiguration ParametersSignificance and adjustmentProperties
1Power0-OFF; 1-ONR/W
2Room TempRoom temperatureR
3Temperature Scale0-°F; 1-°CR/W
4SetpointSetpointR/W
5Fan S peed0-Auto; 1-Low speed; 2-Med speed; 3-High speedRNV
6System Mode0-Ventilation; 1-Heat; 2-Cool; 3-AutoR/W
7V1 Valve Status0-Closed; 1-OpenR
8V2 Valve Status0-Closed; 1-OpenR
9Error Code0-None; 1-Sensor; 2-EEprom; 3-Sensor+EEpromR
10Fan Operation Status0-Off; 1-Low speed; 2-Med speed: 3-High speedR
25Time Off Time0-12; Unit: hourRAN
26Remain Time To Turn Off0-12; Unit: hourR
Internal settings (User is able to change the setting value of below parameters on site, see details in “ISU” part)
11Address1-64 1 (Default)R/W
12System Type0-Heat only; 1-Cool only; 2-2-pipe heating/cooling manual(Default);4-4-pipe manual; 5-4-pipe Auto changeoverR/W
13Fan Control Type0-Auto; 1-Manual; 2-Auto+Manual (Default)RAN/
14Switching Differential For 4-Pipe Auto Change Over With Single Setpoint2-1°C (2°F); 3-1.5 °C (3°F) (Default); 4-2°C (4°F); 5-3°C (5°F)RNV
15CPH Valve For Heat1-12 4 (Default)R/W
16CPH Valve For Cool1-6       3 (Default)R/W
17Dis play Temp . Adjustment0-8 ( -2-2°C ) Step 1 (0.5°C)           4 (Default)

0-8 ( -4-4°F ) Step 1 (1°F) 4 (Default)

R/W
18Temp. Display0-Room Temp.(Default);        1-SetpointR/W
19Heating Range Stops100-320 (10-32°C) Step 5 (0.5°C) 320 (Default) (50-90°F) Step 10 (1°F) 900 (Default) R/W 
20Cooling Range Stops100-320 (10-32°C) Step 5 (0.5°C) 100 (Default) 500-900 (50-90°F) Step 10 (1°F) 500 (Default)Fuw
21Keypad Lockout0-All Keys are available (Default)R/W
1-System button locked
2-Fan and system button locked
3-All button locked except power button
4-All button are locked
22Freeze Protection0-Disable;         1-Enable (Default)R/W
23Power Recovery Status0-OFF; 1-Previous status (Default)R/W
24Modbus Baudrate0-9600 (Default);       1- 4800; 2-19200R/W

 

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals