Ajax Fireprotect Wireless Indoor Fire Detector User Manual

Ajax Fireprotect Wireless Indoor Fire Detector User Manual

AJAX LogoFireProtect Wireless Indoor Fire Detector
User ManualAJAX FireProtect Wireless Indoor Fire Detector

FireProtect Wireless Indoor Fire Detector

FireProtect (FireProtect Plus) is a wireless indoor fire detector with an in-built buzzer and a battery, ensuring up to 4 years of autonomous operation.
FireProtect can detect smoke and rapid temperature increase.
Aside from these functions, FireProtect Plus additionally can alert of dangerous CO levels. Both detectors can function independently from the hub.
Connecting to the Ajax security system via a secured radio protocol, FireProtect (FireProtect Plus) communicates with the at a distance of up to 1,300 m in line of sight.
The detector can be a part of third-party security systems, connecting to them via the integration module.
Buy a fire detector with a carbon monoxide sensor FireProtect Plus
The detector is set up for iOS, Android, macOS, and Windows. The system notifies the user of all events through push notifications, SMS, and calls (if activated).
Buy fire detector FireProtect

Functional Elements

AJAX FireProtect Wireless Indoor Fire Detector - Fig 1

  1. Siren hole
  2. Light indicator (acts as the sensor and Test button)
  3. Smoke chamber hole with the temperature detector behind the net
  4. SmartBracket attachment panel
  5. Power button
  6. Tamper button
  7. QR code

Operating Principle

When smoke penetrates the detector chamber, it distorts infrared light between the emitter and the photoelectric receiver. This distortion triggers a smoke alarm. When the temperature exceeds 60°С or rises by 30°С during 30 minutes (not necessary to reach 60°С), the detector registers a temperature increase, which triggers a fire alarm.
AJAX FireProtect Wireless Indoor Fire Detector - Icon 1 The life span of the FireProtect Plus detector lasts up to 7 years (up to 10 years for the FireProtect). In the event of a detector failure, you will receive a corresponding notification — it will need to be replaced or submitted for comprehensive diagnostics.
FireProtect Plus has an additional sensor to detect dangerous CO levels. If the concentration of CO in the air exceeds a certain level, the detector generates an alarm.
The detector is triggered:

  • within 60–90 min at carbon oxide concentration 50 ppm / 0.005%
  • within 10–40 min at CO concentration 100 ppm / 0.01%
  • within 3 min at carbon oxide concentration 300 ppm / 0.03%.

In case of an alarm, the detector activates the built-in buzzer (the siren sound can be heard from afar) and blinks with the light indicator. When connected to a security system, both the user and the security company are notified of the alarm.
The siren of the device can be turned off using three ways:

  1. Press the Ajax logo on the device lid (there is a touch button under the logo).AJAX FireProtect Wireless Indoor Fire Detector - Fig 2
  2. Through the Ajax app. In case of fire alarm, you will see a pop-up message in.AJAX FireProtect Wireless Indoor Fire Detector - Fig 3
  3. Using the KeyPad (if the Interconnected FireProtect Alarms feature is enabled).
    To turn off the built-in sirens in case of fire alarm, press the “*” button on the KeyPad.AJAX FireProtect Wireless Indoor Fire Detector - Fig 4Please note that for this to work you need to priorly select the Mute Interconnected Fire Alarm command for this button in the KeyPad settings.
    If smoke and/or temperature levels do not restore to normal values, in 10 minutes, the FireProtect/FireProtect Plus turns on the siren again.

Connecting the Detector to the Ajax Security System

Before starting the connection:

  1. Following the hub user guide, install the Ajax app. Create the account, add the hub, and create at least one room.
  2. Switch on the hub and check the internet connection (via Ethernet cable and/or GSM network).
  3. Make sure that the hub is disarmed and does not update by checking its status in the Ajax app.

AJAX FireProtect Wireless Indoor Fire Detector - Icon 1 Only users with administrator rights can add the device to the hub
Pairing the detector with the hub:

  1. Select Add Device in the Ajax app.
  2. Name the device, scan or type the QR Code (located on the detector body and packaging), and select the location room.AJAX FireProtect Wireless Indoor Fire Detector - Fig 5
  3. Tap Add — the countdown will start.AJAX FireProtect Wireless Indoor Fire Detector - Fig 6

To make sure that the detector is on, press the on/off button — the logo will light up red for a second.
For detection and pairing to occur, the detector should be located within the coverage area of the wireless network of the hub (at a single protected object). The connection request is transmitted for a short time: at the moment of switching on the device.
If pairing with the hub fails, the detector operates autonomously; switch off the detector for 5 seconds and retry.
The detector connected to the hub is displayed in the list of devices in the app. The update of the detector status in the list depends on the device inquiry time set in the hub settings (the default value is 36 seconds).

Connecting to Third Party Security Systems
To connect the detector to a third-party security central unit using the Ajax cartridge or Ajax Oxbridge Plus integration module, follow the recommendations in the manual of the respective device.
The smoke detector always operates in active mode. When connecting FireProtect to third-party security systems, it is appropriate to place it in a permanently active protection zone.

ParameterState
TemperatureThe temperature of the device. Measures on the device processor and changes gradually
Jeweler Signal StrengthSignal strength between the hub and the detector
ConnectionConnection status between the hub and the device
Battery ChargeThe battery level of the device. Two states available:
• OK
• Battery discharged
How battery charge is displayed in Ajax apps
LidThe tamper state of the device — reacts to the detachment
ReXDisplays the status of using the ReX range extender
SmokeShows if smoke is detected
Temperature Threshold ExceededThe state of the temperature threshold exceeded the alarm
Rapid Temperature RiseThe state of rapid temperature increase alarm
High CO Level (FireProtect Plus only)The state of dangerous CO level alarm
Backup Battery ChargeThe backup battery level of the device
Smoke sensorThe state of the smoke detector
Smoke Sensor Dust LevelThe dust level in the smoke chamber
Temporary DeactivationShows the status of the device: active, completely disabled by the user, or only notifications about triggering the device tamper buttons are disabled

Settings

  1. Devices AJAX FireProtect Wireless Indoor Fire Detector - Icon 2
  2. FireProtect | FireProtect Plus
  3. Settings AJAX FireProtect Wireless Indoor Fire Detector - Icon 3
SettingValue
First fieldThe device name can be edited
RoomSelecting the virtual room to which the device is assigned
If active, the detector alerts of exceeding the
limits of carbon monoxide concentration
High-Temperature AlarmIf active, the detector reacts when the
temperature is 60°C and higher
Rapid Temperature Rise AlarmIf active, the detector reacts to rapid
temperature increase (30°С for 30 minutes or
less)
Alert with a siren if smoke is detectedIf active, sirens added to the system are activated in case of a smoke alarm
If active, sirens added to the system are activated in case the temperature threshold exceeded
If active, sirens added to the system are activated in case of rapid temperature rise detected
If active, sirens added to the system are activated in case CO concentration is dangerous
Jeweler Signal Strength TestSwitches the device to the signal strength test mode
FireProtect Self TestStarts FireProtect selftest
Temporary DeactivationAllows the user to disconnect the device
• Lid only — the system will ignore only notifications about the triggering of the device tamper button
Learn more about the temporary deactivation of devices
Note: that a disabled device does not trigger an interconnected alarm of fire detectors. But if smoke is detected, the built-in siren will sound
User GuideOpens the detector User Guide
Unpair DeviceDeletes the device and its settings

Interconnected FireProtect Alarms Setup

The function activates built-in sirens of all fire detectors if at least one of them is triggered. Sirens are activated within the hub—detector ping interval according to the Jeweller settings.
To enable Interconnected Alarms:

  1. Open the Devices tab AJAX FireProtect Wireless Indoor Fire Detector - Icon 2 in the Ajax app
  2. Select a hub
  3. Go to its Settings by pressing AJAX FireProtect Wireless Indoor Fire Detector - Icon 3
  4. Select the Service item
  5. Go to the Fire detectors settings menu and activate the Interconnected FireProtect Alarms option

AJAX FireProtect Wireless Indoor Fire Detector - Icon 4 Interconnected alarms are supported by FireProtect and FireProtect Plus detectors with firmware versions 3.42 and later. Please note that when you turn on the interconnected alarms, you cannot set the hub—detector ping interval (Jeweller settings) to more than 48 seconds.
The function works as follows:

  1. One of the FireProtect/FireProtect Plus detectors detects an alarm.
  2. Delay of Interconnected Alarms starts.
  3. The built-in siren of the fire detector informs the alarm. Users receive notifications in the Ajax app (if appropriate notifications are enabled). At the object, Ajax sirens are activated (if the corresponding settings are enabled).AJAX FireProtect Wireless Indoor Fire Detector - Fig 7
  4. An alarm confirmation event is sent to the monitoring station and security system users, and the system starts the interconnected alarm for fire detectors if:
    • The interconnected alarm delay time has passed, and the triggered detector is still registering an alarm.AJAX FireProtect Wireless Indoor Fire Detector - Fig 14• During the delay of the interconnected alarms, the triggered detector reports a different type of alarm (for example, the detector reports the exceeding of the temperature threshold after a smoke alarm).AJAX FireProtect Wireless Indoor Fire Detector - Fig 15 • During the interconnected alarm delay, another fire detector in the system raised an alarm.AJAX FireProtect Wireless Indoor Fire Detector - Fig 10• Through Ajax apps.AJAX FireProtect Wireless Indoor Fire Detector - Fig 11• By pressing the KeyPad function button (in the interconnected fire alarm muting mode).
    • By pressing the Button in the interconnected fire alarm muting mode.
    • By eliminating the cause of the alarm (fire detectors at the facility no longer detect an alarm).
    • By pressing the touch button of the triggered fire detector.
    AJAX FireProtect Wireless Indoor Fire Detector - Icon 1If a triggered detector does not return to a normal state within 10 minutes after the user postponed the interconnected alarm, another fire detector reports an alarm, or a triggered detector reports an alarm of another type (for example, temperature and smoke), the system will send an alarm confirmation and activate an interconnected alarm for fire detectors.AJAX FireProtect Wireless Indoor Fire Detector - Fig 12
  5. If necessary, activate the Ignore First Alarm option. This setting is recommended for premises with potential sources of false alarms. For example, if the device is installed in a place where dust or steam can get into the detector.

The option functions as follows:

  1. The detector reports a smoke alarm.
  2. The built-in 30-second timer of the detector starts.
  3. If after 30 seconds the detector still detects a threat, an alarm is sent to the hub.

Indication

EventIndication
Detector switching onThe logo lights up green for 1 second
Detector switching offThe logo blinks red three times and the device switches off
Registration failedThe logo blinks green for a minute, then the device switches to the autonomous mode
Smoke or temperature increase detectedThe siren switches on, and the logo lights red during the fire/smoke alarm
• One short sound signal per 90 sec — main batteries low (CR2)

The tests do not start straight away but within a period of 36 seconds when using the standard settings. The test time starts depending on the settings of the detector scanning period (the paragraph on “Jeweller” settings in hub settings).
Jeweler Signal Strength Test
FireProtect Self-Test
Attenuation Test
According to the requirements of the EN50131 standard, the level of the radio signal sent by wireless devices is decreased during the test mode.

Detector Testing
Before installing the detector, check the smoke sensor. To test it, switch on the detector and press the sensor button (the logo center) for a few seconds – the detector will test the smoke chamber with the electronic simulation of smoke generation and then will switch on the siren for 6 seconds.
You will receive a notification in the Ajax app regarding the test result and detector status.

Installation

Selecting the Location
AJAX FireProtect Wireless Indoor Fire Detector - Icon 1 Check the Jeweller signal level at the installation location
If the detector has low or unstable signal strength even after moving, use a ReX radio signal range extender.
Install the detector at the ceiling in the highest point where hot air and smoke are concentrated in case of fire.
If there are any beams at the ceiling, protruding by 30 or more centimeters from the ceiling level, install the detector between every two beams.
How to install FireProtect fire detector correctly
Where and how to install FireProtect Plus

Installation procedure
Before installing the detector, make sure that you have selected the optimal location that follows the guidelines of this manual!AJAX FireProtect Wireless Indoor Fire Detector - Fig 13

AJAX FireProtect Wireless Indoor Fire Detector - Icon 1 Use double-side adhesive tape only for temporary attachment of the detector. The tape runs dry with time, which can cause falling, false triggering, and detector malfunction.

  1. Put the detector on the attachment panel by turning it clockwise on SmartBracket. When the detector is fixed in SmartBracket, it blinks with LED, signaling that the tamper is closed.

If LED doesn’t blink after fixing in SmartBracket, check the status of the tamper in the Ajax app and then the fixing tightness of the panel.
If someone detaches the detector from the surface or takes it off the attachment panel, the security system notifies you.
Do not install the detector:

  1. Outside the premises (outdoors);
  2. Nearby any metal objects or mirrors causing attenuation or screening of the signal;
  3. At any place with fast air circulation (air fans, open windows or doors);
  4. Closer than a meter to the cooking surface;
  5. Inside premises with temperature and humidity beyond the range of permissible limits;

In case of autonomous use, the detector notifies of the detected fire/smoke with the siren sound and light of the logo. To switch off the siren, press the logo (there is a sensor button) or eliminate the cause of the actuated alarm.

Maintenance and Battery Replacement

Check the operational capability of the detector regularly. Clean the detector body from dust, spider web, and other contaminants as they appear. Use a soft dry napkin suitable for tech equipment.
Do not use any substances containing alcohol, acetone, gasoline, and other active solvents to clean the detector.
To a certain level, the detector ignores the dust in the smoke chamber. When the chamber becomes too dusty, the detector notifies the user of the need to clean it via the app (and beeps every minute and a half). Such maintenance is compulsory for the detector to operate correctly.
How to clean up the smoke chamber
Pre-installed batteries ensure up to 4 years of autonomous operation. If the batteries are discharged, the security system sends the respective notifications and the detector signal with a sound every 90 seconds:

  • If the main batteries are low — a single short signal;
    Smoke-sensitive elementPhotoelectric sensor
    Temperature sensitive elementThermocouple
    Sound notification volume85 dB at a distance of 3 m
    Alarm threshold at the temperature+59°С ±2°С
    Tamper protectionYes
    Frequency band868.0 – 868.6 MHz or 868.7 – 869.2 MHz depending on the region of sale
    CompatibilityOperates independently or with all Ajax hubs, range extenders, and Oxbridge Plus. cartridge
    Maximum RF output powerUp to 20 mW
    Radio signal modulationGFSK
    Radio signal rangeUp to 1,300 m (any obstacles absent)
    Power supply2 × CR2 (main batteries), CR2032 (backup battery), 3 V
    Battery lifeUp to 4 years

Complete Set

  1. FireProtect (FireProtect Plus)
  2. SmartBracket mounting panel
  3. Batteries CR2 (pre-installed) — 2 pcs
  4. Battery CR2032 (pre-installed) —1 pcs
  5. Installation kit
  6. Quick Start Guide

Warranty

Warranty for the “AJAX SYSTEMS MANUFACTURING” LIMITED LIABILITY COMPANY products is valid for 2 years after the purchase and does not apply to the pre-installed battery.
If the device does not work correctly, you should first contact the support service — in half of the cases, technical issues can be solved remotely!
The full text of the warranty

AJAX LogoUpdated April 22, 2021

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals