Evco Ev3h94 Controller For Dhw Heat Pump Heaters Instruction Manual

Evco Ev3h94 Controller For Dhw Heat Pump Heaters Instruction Manual

EVCO EV3H94 Controller for DHW Heat Pump Heaters LOGO

EVCO EV3H94 Controller for DHW Heat Pump Heaters

EVCO EV3H94 Controller for DHW Heat Pump Heaters IMAGE

OVERVIEW

  • power supply 115… 230 VAC
  •  DHW tank upper and lower probe, evaporator probe (PTC/NTC/Pt 1000)
  •  photovoltaic, HP, and multi-purpose digital input (see i0)
  •  compressor relay 16 A res. @ 250 VAC
  •  alarm buzzer
  •  TTL MODBUS slave port for EVconnect app, Epoca remote monitoring system or for BMS.

MEASUREMENTS AND INSTALLATION

Measurements in mm (inches). To be fitted to a panel, snap-in brackets provided.

EVCO EV3H94 Controller for DHW Heat Pump Heaters FIG 1

INSTALLATION PRECAUTIONS 

  •  the thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in);
  •  ensure that the working conditions are within the limits stated in the TECHNICAL SPECIFICATIONS section;
  •  do not install the device close to heat sources, equipment with a strong magnetic field, in places subject to direct sunlight, rain, dampness, excessive dust, mechanical vibrations, or shocks;
  •  in compliance with safety regulations, the device must be installed properly to ensure adequate protection from contact with electrical parts. All protective parts must be fixed in such a way as to need the aid of a tool to remove them.

ELECTRICAL CONNECTION

  •  use cables of an adequate section for the current running through them.
  •  to reduce any electromagnetic interference locate the power cables as far away as possible from the signal cables.

EVCO EV3H94 Controller for DHW Heat Pump Heaters FIG 2

PRECAUTIONS FOR ELECTRICAL CONNECTION 

  •  if using an electrical or pneumatic screwdriver, adjust the tightening torque;
  •  if the device is moved from a cold to a warm place, humidity may cause condensation to form inside. Wait for about an hour before switching on the power;
  •  make sure that the supply voltage, electrical frequency and power are within the set limits. See the section TECHNICAL SPECIFICATIONS;
  •  disconnect the power supply before carrying out any type of maintenance;
  •  do not use the device as a safety device;
  •  for repairs and for further information, contact the EVCO sales network.

FIRST-TIME USE 

  •  Carry out the installation following the instructions given in the section MEASUREMENTS AND INSTALLATION.
  • Power up the device as set out in the section ELECTRICAL CONNECTION: an internal test will startup.
  • The test normally takes a few seconds; when it is finished the display will switch off.
  • Configure the device as shown in the section Setting configuration parameters. Recommended configuration parameters for first-time use:
PAR.DEF.PARAMETERMIN… MAX.
SP155.0setpoint in economy moder3… r4
SP265.0setpoint in comfort moder1… r2
P01type of probe0 = PTC              1 = NTC 2 = Pt 1000
P20temperature measurement unit0 = °C                1 = °F
P31enabled probes0 = DHW tank upper probe + high pressure input

1 = DHW tank upper and  lower  probe

d12type of defrost0 = electric 1 = hot gas

2 = compressor stopped

3 = hot gas balancing the pressure

Then check that the remaining settings are appropriate; see the section CONFIGURATION PARAMETERS.

  • Disconnect the device from the mains.
  •  Make the electrical connection as shown in the section ELECTRICAL CONNECTION without powering up the device.
  •  For the connection in an RS-485 network connect the interface EVIF22TSX or EVIF23TSX, to activate real-time functions connect the module EVIF23TSX, to use the device with the EPoCA remote monitoring system, connect the EVIF25TWX module, to use the device with the APP EVconnect connect the interface EVIF25TBX; see the relevant instruction sheets. If EVIF22TSX or EVIF23TSX is used, set parameter bLE to 0.
  •  Power up the device.

USER INTERFACE AND MAIN FUNCTIONS 

EVCO EV3H94 Controller for DHW Heat Pump Heaters FIG 3

Switching the device on/off

  • `If the device is switched on, the display will show the P5 value (“DHW tank upper temperature” default); if the display shows an alarm code, see the section ALARMS.
LEDONOFFFLASHING
 compressor switched oncompressor switched off– compressor protection active

–  setpoint being set

 defrost active
fans switched onfans switched off
HACCPalarm active
 compressor         mainte-

nance request

operation with EVconnect APP ac-

tive

°C/°Ftemperature display
AUXheaters switched onheaters switched off
 device switched offdevice switched on

EVCO S.p.A. | EV3H94 | Instruction sheet ver. 1.0 | Code 1043H94E104 | Page 2 of 6 | PT 05/21
Unlocking the keypad
Touch a key for 1 s: the display will show the label “URL”.

Setting the setpoint Economy 

Check that the keypad is not locked.

 

 

1.

  

Touch the SET key: the display will show the label “SP1”.

 

2.

  

Touch the SET key.

 

3.

 Touch the UP or DOWN keys within 15s to set the value within the limits r3 and r4 (default “40… 55”).
 

4.

  

Touch the SET key (or take no action for 15s).

5. Touch the ON/STAND-BY key.

Setting the Comfort setpoint
Check that the keypad is not locked.

 

1.

  

Touch the SET key: the display will show the label “SP1”.

2. Touch the UP or DOWN key to select the label “SP2”.
3. Touch the SET key.
 

4.

 Touch the UP or DOWN keys within 15s to set the value within the limits r1 and r2 (default “40… 70”).
 

5.

  

Touch the SET key (or take no action for 15s).

 

6.

  

Touch the ON/STAND-BY key.

Setting the over post activation threshold
Check that the keypad is not locked

 

1.

  

Touch the SET key: the display will show the label “SP1”.

 

2.

  

Touch the UP or DOWN key to select the label “SP3”.

 

3.

  

Touch the SET key.

 

4.

 Touch the UP or DOWN keys within 15s to set the value within

the limits 10 and r2 (default “10… 70”).

 

5.

  

Touch the SET key (or take no action for 15s).

 

6.

  

Touch the ON/STAND-BY key.

Activating manual defrost
Check that the keypad isn’t locked and that the anti-legionella and over-boost functions aren’t active.

Touch the UP key for 4s. If P4 = 1 or 2 (default), defrost is activated provided that the evaporator temperature is lower than the d2 threshold.

Silencing the alarm buzzer (if u9 = 1) 

Touch a key.

FUNCTIONS AND LOAD OPERATIONS 

Economy

  • the compressor on if DHW tank lower temperature < “SP1 setpoint – r0 differential” and off if DHW tank lower temperature > “SP1 setpoint”
  •  fans on if compressor on
  •  heaters switched off in normal operation (on if needed during defrosting)

Comfort 

  •  the compressor on if DHW tank lower temperature < “SP5 setpoint – r0 differential” and off if DHW tank lower temperature > “SP5 setpoint”
  •  fans on if compressor on
  •  heaters on, with a single probe configured (P3 = 0), if DHW tank upper temperature < “SP2 – r6 threshold – r7 differential” and off if DHW tank upper temperature > “SP2 – r6 threshold”.
  •  heaters on, with two probes configured (P3 = 1), if DHW tank upper temperature < “SP2 – r0 differential” and off if DHW tank upper temperature > “SP2”.

 Anti-legionella
It activates at “H0 intervals” or at “Ant time”, provided that DHW tank lower temperature > “SP1 setpoint” and > “SP2 setpoint”

  • compressor switched off
  •  fans switched off
  •  heaters switched on until DHW tank upper temperature > “H1 threshold” and then for “H3 time”.

Overboost

  • It activates in manual mode, provided that DHW tank upper and lower temperature < “SP3 threshold”
  •  compressor, fans and heaters on until DHW tank upper temperature > “SP1 setpoint”.

Defrosting
It activates with evaporator temperature < “d17 threshold” for “d18 time” or in manual mode, provided that the anti-legionella and over-boost functions are not active

  • compressor switched on if d1 = 1
  •  defrost relay active if d1 = 1 or 2
  •  fans switched on if d1 = 2
  •  heaters switched on to prevent too high-temperature drop in the storage tank

 Photovoltaic system

  • It activates with photovoltaic input active
  • operation as in comfort mode, except for “SP2 setpoint” which becomes “SP6 setpoint”.

 Green

  •  It activates with multi-purpose input active and DHW tank upper and lower temperature > “SP8 setpoint”
  •  compressor switched off
  •  fans switched off
  •  heaters switched off.

Antifreeze

  • This function is used to prevent water freezing. It is activated when tank upper temperature < “SP7 setpoint” – “r0 differential” and this function is deactivated when tank upper temperature > “SP7 setpoint”
  •  heaters are switched on.
  • This function can be activated only if the controller is on standby.

Pre-opening hot gas defrost valve

  • This function is used to balance the pressure at the compressor start-up, and it is activated only if “d1” = 3.
  • This function switch on the defrost output “i11” seconds before the start-up of the compressor, this occurs every time the compressor started, even if there is no defrost request.

5.10 Fan operation

  • The fan operates depending on the active function, normally C12 seconds before the switch-on of the compressor. There are some exceptions:
  • defrost: in the case of hot gas (d1=1) compressor is active but the fan is off. In case of com-pressor stop (d1=2), the compressor is off but fan is active
  •  alarms: in case of LHP compressor is off but fan is active.

ADDITIONAL FUNCTIONS 

Activating/deactivating comfort operation in manual mode 

 

1.

  

Touch the DOWN key for 1 s: the display will show a code.

 

2.

  

Touch the UP or DOWN key within 15s to select a label.

 COD.DESCRIPTION
Autoactivates comfort operation
ECOdeactivates comfort operation
 

3.

  

Touch the SET key.

 

4.

 Touch the ON/STAND-BY key (or take no action for 60s) to exit

the procedure.

 

Activating the overboost function 

 

1.

  

Touch the DOWN key for 1 s: the display will show a code.

 

2.

  

Touch the UP or DOWN key within 15s to select “ObS”.

 

3.

  

Touch the SET key.

 

4.

 Touch the ON/STAND-BY key (or take no action for 60s) to exit the procedure.

Displaying the operating mode

 

1.

 

 

 

Touch the DOWN key: the display will show a code.

 COD.DESCRIPTION
ECOeconomy
ObSoverboost
Autocomfort
Antianti-legionella; if flashing, DHW tank lower temperature > “SP1 setpoint” and

> “SP2 setpoint”

dEFrdefrost
in2photovoltaic function
 

2.

 

 

Touch the ON/STAND-BY key (or take no action for 60s) to exit the procedure.

 

Displaying/deleting compressor functioning hours 

 

1.

 

 

 

Touch the DOWN key for 1 s: the display will show a code.

 

2.

 

Touch the UP or DOWN key within 15s to select a label.

 COD.DESCRIPTION
CHdisplay compressor working hours in hundreds
rCHdelete compressor working hours
 

3.

 

 

 

Touch the SET key.

 

4.

 

Touch the UP or DOWN key to set “149” (to select rCH).

 

5.

 

 

 

Touch the SET key.

 

6.

 

 

Touch the ON/STAND-BY key (or take no action for 60s) to exit

the procedure.

SETTINGS

 

1.

 

 

 

Touch the SET key for 4 s: the display will show the label “PA”.

 

2.

 

 

 

Touch the SET key.

 

3.

 

Touch the UP or DOWN key within 15s to set -19”.

 

4.

 

 

Touch the SET key (or take no action for 15s): the display will

show the label “SP”.

 

5.

 

Touch the UP or DOWN key to select a parameter.

 

6.

 

 

 

Touch the SET key.

 

7.

 

Touch the UP or DOWN key within 15s to set the value.

 

8.

 

 

 

Touch the SET key (or take no action for 15s).

9.   Touch the SET key for 4s (or take no action for 60s) to exit the

procedure.

 

Set the date, time and day of the week (if module EVIF23TSX, EVIF25TWX or interface EVIF25TBX is connected) 

  •  Do not disconnect the device from the mains within two minutes since the setting of the time and day of the week.
  •  if the device communicates with the connect app, the date, time, and day of the week will be automatically set by the smartphone or tablet.
1. 

 

Touch the UP key.
 

2.

 

Touch the UP or DOWN key within 15s to select the label “rtc”.

 

3.

 

 

Touch the SET key: the display will show the label “yy” followed

by the last two figures of the year.

 

4.

 

Touch the UP or DOWN key within 15 s to set the year.

 

5.

 

Repeat actions 3. and 4. to set the next labels.

 LAB.DESCRIPTION OF THE NUMBERS FOLLOWING THE LABEL
nmonth (01… 12)
dday (01… 31)
htime (00… 23)
nminute (00… 59)
6. 

 

Touch the SET key: the display will show the label for the day of the week.
 

7.

Touch the UP or DOWN key within 15 s to set the day of the week.
 LAB.DESCRIPTION
MonMonday
tuETuesday
UEdWednesday
thuThursday
FriFriday
SatSaturday
SunSunday
 

8.

 

 

 

Touch the SET key: the device will exit the procedure.

 

9.

 

 

 

Touch the ON/STAND-BY key to exit the procedure beforehand.

 

Restoring factory settings (default) 

  •  check that the factory settings are appropriate; see the section CONFIGURATION PARAMETERS.
 

1.

 

 

 

Touch the SET key for 4 s: the display will show the label “PA”.

 

2.

 

 

 

Touch the SET key.

 

3.

 

Touch the UP or DOWN key within 15s to set “149”.

 

4.

 

 

Touch the SET key (or take no action for 15s): the display will

show the label “dEF”.

 

5.

 

 

 

Touch the SET key.

 

6.

 

Touch the UP or DOWN key within 15s to set “1”.

 

7.

 

 

Touch the SET key (or take no action for 15 s): the display will show “– – –” flashing for 4 s, after which the device will exit the

procedure.

8.Disconnect the device from the power supply.
9. 

 

Touch the SET key for 1s before action 6 to exit the procedure

beforehand.

 CONFIGURATION PARAMETERS

 

 

 

No.PAR.DEF.SETPOINTMIN… MAX.
1SP155.0setpoint in economy moder3… r4
2SP265.0setpoint in comfort moder1… r2
3SP345.0overboost activation threshold10 °C/°F… r2
4SP555.0heat pump switch-off thresholdr1… SP2
5SP675.0photovoltaic system setpoint40… 100 °C/°F
6SP75.0setpoint in antifreeze mode0… 40 °C/°F
7SP840.0setpoint in green mode0… 100 °C/°F
8SP9-7.0cold evaporator alarm threshold-25… 25 °C/°F
9SPA-25evaporator failure alarm thresh- old-50… 25 °C/°F
 

 

 

 

 

 

 

 

No.PAR.DEF.ANALOGUE INPUTSMIN… MAX.
10CA10.0DHW tank upper probe offset-25… 25 °C/°F
11CA20.0DHW tank lower probe offset-25… 25 °C/°F
12CA30.0evaporator probe offset-25… 25 °C/°F
13P01type of probe0 = PTC

2 = Pt 1000

1 = NTC 
14P11enable decimal point °C0 = no1 = yes 
15P20temperature measurement unit0 = °C1 = °F 
16P31enabled probes0 = DHW tank upper probe

+ high pressure input

1 = DHW tank upper and lower probe

17P42evaporator probe function0 = disabled (defrost every d18 minutes)

1 = defrost activation and defrost end

2 = defrost activation

18P50value displayed0 = DHW tank upper tem- perature

1 = setpoint in  comfort mode

2 = DHW tank lower tem- perature

3 = evaporator temperature

19P85display refresh time0… 250 s: 10
 

 

 

 

 

No.PAR.DEF.REGULATIONMIN… MAX.
20r03.0setpoint differential1… 30 °C/°F
21r140.0minimum

mode

setpointincomfort10 °C/°F… r2
22r270.0maximum modesetpointincomfortr1… 100 °C/°F
23r340.0minimum modesetpointineconomy10 °C/°F… r4
24r455.0maximum setpoint in economy

mode

r3… 100 °C/°F
25r50enable setpoint blocking in economy and comfort modes0 = no1 = yes 
26r615.0heater modethresholdincomfort0… 50 °C/°F
27r715.0heater threshold differential in

comfort mode

1… 30 °C/°F
 

 

 

 

 

 

No.PAR.DEF.COMPRESSORMIN… MAX.
28C05compressor on delay from pow- er-on0… 240 min
29C15minimum time between two power-ons of compressor0… 240 min
30C25minimum compressor-off time0… 240 min
31C30minimum compressor-on time0… 240 s
32C10400compressor hours for mainte-

nance

0… 999 h x 100

0 = disabled

33C11120interval for cold evaporator con- trol0… 999 min
34C1260compressor-on delay from fan

on for cold evaporator control

0… 240 s
35C1320compressor-on delay from green multi-purpose input reset0… 240 min
36C1420compressor-on consecutive time for evaporator failure control-1… 240 min

-1 = disabled

 

 

 

 

 

 

No.PAR.DEF.DEFROSTMIN… MAX.
37d12type of defrost0  = electric

1  = hot gas

2 = compressor stopped

3 = hot gas balancing pressure

 

 

 

the

38d23.0defrost end threshold-50… 50 °C/°F
39d330defrost duration0… 99 min

0 = defrost disabled

If P4 = 1, maximum duration default 0 in map 3 of EV3H94N9PXRX01 and

EV3H94N9VXRX01

40d17-2.0evaporation threshold for defrost interval count-50… 50 °C/°F
41d1830defrost interval0… 240 min

0 = manual only

 

 

 

 

 

 

 

 

 

 

No.PAR.DEF.ALARMSMIN… MAX.
42A00select value for low temperature alarm0 = DHW tank upper temperature

1 = DHW tank lower temperature

2 = evaporator temperature

 

43

 

A1

 

10.0

low-temperature alarm threshold 

0… 50 °C/°F

44A20low temperature alarm type0  = disabled

1  = absolute

45A30select value for high tem- perature alarm0 = DHW tank upper tempera- ture

1 = DHW tank lower tempera- ture

2 = evaporator temperature

46A490.0high-temperature alarm threshold0… 199 °C/°F

default 75.0 in

EV3H94N9PXRX01 and EV3H94N9VXRX01

47A50high-temperature alarm type0  = disabled

1  = absolute

48A6120high-temperature alarm de-

lay from power-on

0… 240 min
49A715high/low-temperature alarm

delay

0… 240 min
50A10120power failure duration for

alarm recording

0… 240 min
51A112.0high/low-temperature alarm

reset differential

1… 30 °C/°F
 No.PAR.DEF.FANMIN… MAX.
52F01enable fan0 = no                1 = yes
 

 

No.PAR.DEF.ANTI-LEGIONELLAMIN… MAX.
53H030anti-legionella interval0… 99 d (days)

0 = none

 

54

 

H1

 

70.0

anti-legionella                thermal threshold 

10… 199 °C/°F

 

55

 

H3

 

2

anti-legionella                thermal

threshold maintenance duration

 

0… 240 min

0 = function disabled

 

 

 

 

 

 

 

 

 

No.PAR.DEF.DIGITAL INPUTSMIN… MAX.
56i00multi-purpose input function0 = disabled

1 = pressure switch

2 = green

57i20compressor-on delay from pressure switch alarm reset0… 120 min
58i30enable photovoltaic system0 = no                1 = yes
59i41photovoltaic system input activation0 = with contact closed 1 = with contact open
 

60

 

i5

 

1

high-pressure input activa- tion 

0 = with contact closed 1 = with contact open

 

61

 

i8

 

3

number of the pressure switch

alarms for unit blocked alarm

 

0… 15

0 = disabled

62i9240counter reset time for pressure switch alarms1… 999 min
63i1024pressure switch alarm delay from compressor-on0… 240 sx10
64i1160time pre-opening hot gas

defrost valve

0… 240 s
65i120fan off during pressure switch/unit blocked alarm0 = no                1 = yes default 1 in EV3H94N9PXRX01 and

EV3H94N9VXRX01

 No.PAR.DEF.DIGITAL OUTPUTSMIN… MAX.
66u01enable relay K2 and relay K4

inversion

0 = no (defrost on K2)

1 = yes (defrost on K4)

67u91enable alarm buzzer0 = no                1 = yes
 

 

 

 

 

 

 

 

N.PAR.DEF.CLOCKMIN… MAX.
68Hr00enable clock0 = no                1 = yes
69Hd11time for switch-on on Mon-

day

1  = with On1 e OF1

2  = with On2 e OF2

70Hd21time for switch on Tues- day1  = with On1 e OF1

2  = with On2 e OF2

71Hd31time for switch-on on

Wednesday

1  = with On1 e OF1

2  = with On2 e OF2

72Hd41time for switch-on on Thurs-

day

1  = with On1 e OF1

2  = with On2 e OF2

73Hd51time for switch-on on Friday1  = with On1 e OF1

2  = with On2 e OF2

74Hd62time for switch on Satur-

day

1  = with On1 e OF1

2  = with On2 e OF2

75Hd72time for switch on Sun-day1  = with On1 e OF1

2  = with On2 e OF2

76HOn1– – –time for time band 1 on00:00… 23:59 h: min

00:00 = disabled

77HOF1– – –time for time band 1 off00:00… 23:59 h: min

00:00 = disabled

78HOn2– – –time for time band 2 on00:00… 23:59 h: min

00:00 = disabled

79HOF2– – –time for time band 2 off00:00… 23:59 h: min

00:00 = disabled

 80Ant– – –time antilegionella on00:00… 23:59 h:min

00:00 = disabled

 N.PAR.DEF.SAFETIESMIN… MAX.
81PA1426level 1 password-99… 999
82PA2824level 2 password-99… 999
 

 

 

N.PAR.DEF.DATA-LOGGING EVLINKMIN… MAX.
83bLE1enable Bluetooth0 = no                1 = sì

>1 reserved

84rE015data-logger sampling inter-

val

0… 240 min
85rE11recorded temperature0 = nessuna

1  = DHW tank upper

2  = DHW tank lower

3 = evaporator

4 = DHW tank upper and lower

5 = tutte

 

 

N.PAR.DEF.MODBUSMIN… MAX.
86LA247MODBUS address1… 247
87Lb2MODBUS baud rate0  = 2.400 baud

1  = 4.800 baud

2  = 9.600 baud

3 = 19.200 baud

88LP2parity0 = none            1 = odd

2 = even

 

ALARMS

CODEDESCRIPTIONRESETTO CORRECT
Pr1DHW tank upper probe

alarm

automatic–   check P0

–   check probe integrity

–   check the electrical connection

Pr2DHW tank lower probe

alarm

automatic
Pr3evaporator probe alarmautomatic
rtcclock alarmmanualset date, time, and day of the week
ALlow-temperature alarmautomaticcheck A0, A1 and A2
AHhigh-temperature alarmautomaticcheck A3, A4 and A5
PFpower failure alarmmanual–   touch a key

–   check the electrical connection

LHPpressure                  switch/unit

blocked alarm

automatic/

manual

–   switch the device off and on

–   check i0, i8 and i9

HPhigh-pressure alarmmanual–   switch the device off and on

–   check P3

FiLcompressor         maintenance alarmautomaticcheck C10

by silencing the buzzer you delete the compressor functioning hours

UtLevaporator failure alarmmanual–   switch the device off and on

–   check SPA and C14

 

 

TECHNICAL SPECIFICATIONS

Purpose of the control devicefunction controller
Construction of the control devicebuilt-in electronic device
Containerblack, self-extinguishing.
Category of heat and fire resistanceD.
Measurements
75.0 x 33.0 x 59.0 mm (2 15/16 x 1 5/16 x 2

5/16 in) with fixed screw terminal blocks

75.0 x 33.0 x 81.5 mm (2 15/16 x 1 5/16 x

3 3/16 in) with plug-in screw terminal blocks

Mounting methods for the control deviceto be fitted to a panel, snap-in brackets pro-

vided

Degree of protection provided by the coveringIP65 (front)
Connection method
fixed screw terminal blocks for wires up to 2.5 mm²plug-in screw terminal blocks for wires up to

2.5 mm² (on request).

Maximum permitted length for connection cables
power supply: 10 m (32.8 ft)analogue inputs: 10 m (32.8 ft)
digital inputs: 10 m (32.8 ft)digital outputs: 10 m (32.8 ft).
Operating temperatureFrom 0 to 55 °C (from 32 to 131 °F)
Storage temperaturefrom -25 to 70 °C (from -13 to 158 °F)
Operating humidityrelative humidity without condensate from

10 to 90%

Pollution status of the control device2.
Compliance:
RoHS 2011/65/ECWEEE 2012/19/EUREACH (EC) Regulation no.

1907/2006

EMC 2014/30/EULVD 2014/35/EU
Classification of the control device according to protection from electrical shockclass II according to standard EMC EN 60730-1 §2.7.5.
Power supply115… 230 VAC (+10% -15%), 50/60 Hz (±3

Hz), max. 3.2 VA insulated

Earthing methods for the control devicenone
Rated impulse-withstand voltage2.5 KV
Over-voltage categoryII.
Software class and structureA.
Analogue inputs2 for PTC, NTC or Pt 1000 probes (DHW tank

upper probe and evaporator probe)

PTC probesSensor type:KTY 81-121 (990 W @ 25 °C, 77 °F)
Measurement field:from -50 to 150 °C (from -58 to 302 °F)
Resolution:0.1 °C (1 °F).
NTC probesSensor type:ß3435 (10 KoW @ 25 °C, 77 °F)
Measurement field:from -40 to 105 °C (from -40 to 221 °F)
Resolution:0.1 °C (1 °F).
Pt 1000

probes

Measurement field:from -100 to 650 °C (from -148 to 999 °F)
 Resolution:0.1 °C (1 °F).
Digital inputs2 dry contact (photovoltaic and multi-

purpose input)

Dry contactContact type:5 VDC, 1.5 mA
Power supply:none
Protection:none.
Other inputscan be configured for analogue input (DHW tank lower probe)

or for digital input (high pressure input)

Digital outputs4 with electro-mechanical relay (compressor, defrost, fans

and heaters)

Compressor relay (K1)SPST, 16 A res. @ 250 VAC
Relay K2SPST, 8 A res. @ 250 VAC
Fan relay (K3)SPST, 5 A res. @ 250 VAC
Relay K4SPST, 5 A res. @ 250 VAC
Type 1 or Type 2 ActionsType 1
Additional features of Type 1 or Type 2 ac-

tions

C.
Displayscustom display, 3 digit, with function icons
Alarm buzzerBuilt-in
Communication ports1 TTL MODBUS slave port for EVconnect app,

EPoCA remote monitoring system or for BMS

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals