Fire-Rated CleanMount Cleanroom Windows
Product Information
Installation Guide
Document No.: 1790-20
Manufacturer: Terra Universal, Inc.
Proprietary Notice: This manual pertains to
proprietary devices manufactured by Terra Universal, Inc. Neither
this document nor any portion of it may be reproduced in any way
without prior written permission from Terra Universal.
Safety Notice: A thorough familiarity with all
operating guidelines is essential to safe operation of the product.
Failure to observe safety precautions could result in poor
performance, damage to the system or other property, or serious
bodily injury or death.
Manufacturer’s Warranty: Terra Universal makes
no warranties applying to information contained in this manual or
its suitability for any implied or inferred purpose. Terra
Universal shall not be held liable for any errors this manual
contains or for any damages that result from its use.
CAUTION
Cautions are used when failure to observe instructions could
result in significant damage to equipment.
WARNING
Warnings are used when failure to observe instructions or
precautions could result in injury or death.
1. Introduction
The design features medical-grade, USP-compliant 316L stainless
steel, compatible with all areas of hospitals and aseptic
environments. The easy-to-clean seamless and flush-mount frame
eliminates crevices where particles and contaminants can
accumulate.
This manual provides information to safely and properly install
the fire-rated window assembly. Read it thoroughly before unpacking
and commencing work.
2. Specifications
| Specification | Description |
|---|---|
| Window Frame Assemblies | Single Pane Flush Mount Fire Window Frame Assemblies |
| Fire Rating | 45 min. Tested under positive pressure conditions, with hose stream |
| Installation Options | Steel stud/gypsum board, masonry or concrete assemblies with a minimum of 1 hour fire rating |
| Wall Assembly | Constructed in accordance with UL Wall Design No. U419 as described in UL’s ProductiQ. Minimum No. 20 steel studs (structural steel), minimum 3-5/8 in. wide, spaced maximum 16 in. OC and faced with a single layer of nominal 5/8 in. thick Type X (Classified for Fire Resistance) gypsum board. |
| Glass Sizes Max. Exposed Area | 3,302 sq.in. |
| Glass Sizes Max. Exposed Width | 70-5/8 |
| Glass Sizes Max. Exposed Height | 46-3/4 |
| Fire-Rated Glazing Options | Pilkington PyroStop 60-101, nominal 7/8 thick |
| Window Assembly Model Designation | Powder-coated steel: 6612-02-PC Stainless steel: 6612-02-SS |
IMPORTANT INSTALLATION NOTES: Terra Universal
does not accept any warranty or liability for installations not in
compliance with this document, or use in any application other than
that for which it is specified. Due to widely varying building
codes, it is the responsibility of the architect/owner and
installer to ensure the window assembly, glazing material, and
other hardware complies with all applicable local building codes
and laws.
3. Installation
Exploded View:
1. INSPECT ALL CRATES FOR DAMAGE IMMEDIATELY UPON ARRIVAL.
Carefully check for any concealed damage. If glass or frame is
damaged, take photos and notes and immediately contact Terra.
WARNING: Read separate instructions for unpacking glass before
opening crate with glass. Any glass or frame damage must be
recorded and reported to Terra immediately.
Installation Guide
Document No. 1790-20
Fire-Rated CleanMount® Cleanroom Windows
© Copyright 2023 Terra Universal Inc. All rights reserved. · Revised March 2023
Installation Guide
Fire-Rated CleanMount® Cleanroom Windows
© Copyright 2023 Terra Universal Inc. All rights reserved. · Revised January 2022 · Document No. 1790-20
Proprietary Notice
This manual pertains to proprietary devices manufactured by Terra Universal, Inc. Neither this document nor any portion of it may be reproduced in any way without prior written permission from Terra Universal.
Safety Notice
A thorough familiarity with all operating guidelines is essential to safe operation of the product. Failure to observe safety precautions could result in poor performance, damage to the system or other property, or serious bodily injury or death.
Terra Universal makes no warranties applying to information contained in this manual or its suitability for any implied or inferred purpose. Terra Universal shall not be held liable for any errors this manual contains or for any damages that result from its use.
CAUTION
Cautions are used when failure to observe instructions could result in significant damage to equipment.
The following symbols are intended to call your attention to two levels of hazard involved in operation:
The information presented here is subject to change without notice.
WARNING
Warnings are used when failure to observe instructions or precautions could result in injury or death.
1. Introduction
Terra Universal’s Fire-Rated CleanMount® Cleanroom Window is Certified to ANSI/UL 9 (positive pressure) for 45-minute fire exposure.
The design features medical-grade, USP-compliant 316L stainless steel, compatible with all areas of hospitals and aseptic environments. The easyto-clean seamless and flush-mount frame eliminates crevices where particles and contaminants can accumulate.
This manual provides information to safely and properly install the fire-rated window assembly. Read it thoroughly before unpacking and commencing work.
Terra Universal, Inc. · TerraUniversal.com · 800 S. Raymond Ave. · Fullerton, CA 92831 · TEL: (714) 578-6000 · FAX: (714) 578-6020
Installation Guide
Fire-Rated CleanMount® Cleanroom Windows
© Copyright 2023 Terra Universal Inc. All rights reserved. · Revised January 2022 · Document No. 1790-20
2. Specifications
Listings Classified and labeled by Underwriters Laboratories, Inc.® (UL). Frame tested in accordance with UL 9 Fire Tests of Window Assemblies, UL File No. R39784:
Single Pane Flush Mount Fire Window Frame Assemblies intended for 45 min. Tested under positive pressure conditions, with hose stream. Window assemblies may be installed in steel stud/gypsum board, masonry or concrete assemblies having a minimum of 1 hour fire rating.
o The 1 hour fire rated steel stud/gypsum board wall assembly is to be constructed in accordance with UL Wall Design No. U419 as described in UL’s ProductiQ. The wall assembly should be minimum No. 20 steel studs (structural steel), minimum 3-5/8 in. wide, spaced maximum 16 in. OC and faced with a single layer of nominal 5/8 in. thick Type X (Classified for Fire Resistance) gypsum board.
Glass Sizes Max. Exposed Area: 3,302 sq.in. Max. Exposed Width: 70-5/8″ Max. Exposed Height: 46-3/4″ Fire-Rated Glazing Options Pilkington PyroStop 60-101, nominal 7/8″ thick Window Assembly Model Designation Powder-coated steel: 6612-02-PC Stainless steel: 6612-02-SS
IMPORTANT INSTALLATION NOTES Terra Universal does not accept any warranty or liability for installations not in compliance with this document, or use in any application other than that for which it is specified. Due to widely varying building codes, it is the responsibility of the architect/owner and installer to ensure the window assembly, glazing material, and other hardware complies with all applicable local building codes and laws.
Terra Universal, Inc. · TerraUniversal.com · 800 S. Raymond Ave. · Fullerton, CA 92831 · TEL: (714) 578-6000 · FAX: (714) 578-6020
Installation Guide
Fire-Rated CleanMount® Cleanroom Windows
© Copyright 2023 Terra Universal Inc. All rights reserved. · Revised January 2022 · Document No. 1790-20
3. Installation
Exploded View
1. INSPECT ALL CRATES FOR DAMAGE IMMEDIATELY UPON ARRIVAL. Carefully check for any concealed damage. If glass or frame is damaged, take photos and notes and immediately contact Terra. WARNING: Read separate instructions for unpacking glass before opening crate with glass. Any glass or frame damage must be recorded and reported to Terra immediately.
2. Rough Opening: Rough opening size may be 1/4″ to 1″ greater than overall dimensions of frame (1/8″-1/2″ gap on each side). Ensure the rough opening is dry, clean, and free of any loose debris. Check the opening for plumb and level. Confirm frame will fit in the rough opening.
3. Install frame into rough opening a. Unpack frame from crate b. Place the frame into the rough opening with the “Clean” side of the window mounted flush against the drywall of the “Clean” side of the wall. c. To center the frame in the rough opening, sandwich fire-resistant shims between the outer trim and the window frame. Horse-shoe opening of shims should face the “clean” side aka “flush-mount” side. d. Install 4 trim pieces around perimeter of the window frame. The flat portion of the shim should be touching the rough opening of the wall, with the bend facing the flush mount side aka fire- side. The shims should be stacked between the window frame and the trim. See green highlighted trim in below screenshot, and below photos for reference.
e. Measure to make sure frame is level and straight.
Terra Universal, Inc. · TerraUniversal.com · 800 S. Raymond Ave. · Fullerton, CA 92831 · TEL: (714) 578-6000 · FAX: (714) 578-6020
Installation Guide
Fire-Rated CleanMount® Cleanroom Windows
© Copyright 2023 Terra Universal Inc. All rights reserved. · Revised January 2022 · Document No. 1790-20
Terra Universal, Inc. · TerraUniversal.com · 800 S. Raymond Ave. · Fullerton, CA 92831 · TEL: (714) 578-6000 · FAX: (714) 578-6020
Installation Guide
Fire-Rated CleanMount® Cleanroom Windows
© Copyright 2023 Terra Universal Inc. All rights reserved. · Revised January 2022 · Document No. 1790-20
View from “Clean” Side AKA Flush-Mount Side:
View from “Dirty” Side
Terra Universal, Inc. · TerraUniversal.com · 800 S. Raymond Ave. · Fullerton, CA 92831 · TEL: (714) 578-6000 · FAX: (714) 578-6020
Installation Guide
Fire-Rated CleanMount® Cleanroom Windows
© Copyright 2023 Terra Universal Inc. All rights reserved. · Revised January 2022 · Document No. 1790-20
CAUTION: Unlevel frame can compromise safety of glass. f. Loosely install anchor screws to allow for adjustment.
Recommended anchor screws: Steel stud/gypsum board: Flat Head Drilling Screw for Metal, 410 Stainless Steel, Number 12 Size, 4″ Long Concrete/masonry: Flat Head Drilling Screw for Concrete/Masonry, 410 Stainless Steel, 1/4 in. Size, 4″ Long. To be installed after pre-drilling with appropriate masonry drill bit.
g. Use diagonal measurements to make sure frame is 100% square. Make adjustments as needed until frame is perfectly square.
Terra Universal, Inc. · TerraUniversal.com · 800 S. Raymond Ave. · Fullerton, CA 92831 · TEL: (714) 578-6000 · FAX: (714) 578-6020
Installation Guide
Fire-Rated CleanMount® Cleanroom Windows
© Copyright 2023 Terra Universal Inc. All rights reserved. · Revised January 2022 · Document No. 1790-20
4. Remove glass from Crate as shown in below diagram: The crate is designed to be opened from only one side. Position the crate against a wall. Place 4″x4″ blocks underneath on one side to tilt back and prevent the glass from falling forward/out. WARNING: To safely uncrate glass, see separate glass handling instructions included with glass.
5. Before installing Glass: a. Remove glazing beads from the frame. b. Check that the white glazing tape is installed on both the frame and 4 glazing beads, and that the tape is not damaged. Replace any sections of damaged glazing tape.
c. To properly support the glass, use the supplied setting blocks at quarter points of daylight opening. Setting blocks must rest flush on the frame. Ensure the setting blocks are centered underneath the glazing. The glazing should not overhang.
Terra Universal, Inc. · TerraUniversal.com · 800 S. Raymond Ave. · Fullerton, CA 92831 · TEL: (714) 578-6000 · FAX: (714) 578-6020
Installation Guide
Fire-Rated CleanMount® Cleanroom Windows
© Copyright 2023 Terra Universal Inc. All rights reserved. · Revised January 2022 · Document No. 1790-20
Terra Universal, Inc. · TerraUniversal.com · 800 S. Raymond Ave. · Fullerton, CA 92831 · TEL: (714) 578-6000 · FAX: (714) 578-6020
Installation Guide
Fire-Rated CleanMount® Cleanroom Windows
© Copyright 2023 Terra Universal Inc. All rights reserved. · Revised January 2022 · Document No. 1790-20
CAUTION: DO NOT PEEL OR TAMPER WITH GREY TAPE AROUND GLASS. It is intumescent tape part of the fireproofing on the glass
6. Install Glass CAUTION: 7/8″ thick glass is very heavy (10.86 lb / ft^2 or 53.00 kg / m^2). Check weight of the glazing and if necessary, use special equipment to safely lift the glass into the frame.
a. If using suction-cup glass-lifter, check the glass-lifter meets the necessary weight capacity and lifting height requirements.
Terra Universal, Inc. · TerraUniversal.com · 800 S. Raymond Ave. · Fullerton, CA 92831 · TEL: (714) 578-6000 · FAX: (714) 578-6020
Installation Guide
Fire-Rated CleanMount® Cleanroom Windows
© Copyright 2023 Terra Universal Inc. All rights reserved. · Revised January 2022 · Document No. 1790-20
b. Carefully raise glass into frame, place centered in frame, and on top of setting blocks. c. Check glass is centered inside frame and that edges are not in contact with the steel frame. There should be
approx. ¼” gap on each side between the glass edge and the frame
d. Secure glass into frame with qty(4) retainer brackets around perimeter of frame
Terra Universal, Inc. · TerraUniversal.com · 800 S. Raymond Ave. · Fullerton, CA 92831 · TEL: (714) 578-6000 · FAX: (714) 578-6020
Installation Guide
Fire-Rated CleanMount® Cleanroom Windows
© Copyright 2023 Terra Universal Inc. All rights reserved. · Revised January 2022 · Document No. 1790-20
i. Press retainer brackets to form a SNUG fit on glass, so there is no extra space for glass to “wiggle” inside frame. Once snug fit is achieved, tighten screws on retainer brackets.
WARNING: GLASS MUST NOT BE OVERLY TIGHTENED OR PINCHED. Eliminate large gaps between glass and glazing tape, but apply very minimal pressure. Any pressure must be low and uniform, no greater than 11.5lbf/in.
7. Tightly pack empty cavities between wall and frame with ceramic fiber insulation or fire-rated caulk. Repeat around entire perimeter of frame. a. For gaps smaller than 3/8″, install fire-rated 3M CP25 intumescent caulk. b. For gaps larger than 3/8″, install fire-rated ceramic fiber insulation
Terra Universal, Inc. · TerraUniversal.com · 800 S. Raymond Ave. · Fullerton, CA 92831 · TEL: (714) 578-6000 · FAX: (714) 578-6020
Installation Guide
Fire-Rated CleanMount® Cleanroom Windows
© Copyright 2023 Terra Universal Inc. All rights reserved. · Revised January 2022 · Document No. 1790-20
8. Apply fire-rated caulk to the front “Clean” side, on top of the trim (see below photo for example).
10.1 fl. oz. Red Fire Barrier CP 25WB Plus Sealant
https://www.homedepot.com/p/3M-10-1-fl-oz-Red-Fire-Barrier-CP-25WB-Plus-Sealant-CP25WB10/100166701#overlay
9. Install drywall ledge on “dirty side” of window, around entire perimeter of window (see below screenshot and photo for example). a. For masonry or concrete walls, in lieu of a drywall ledge, a stainless steel trim can be applied around the perimeter of the “dirty” side to cover shims and insulation/caulking.
Drywall-stud wall
Masonry wall
Terra Universal, Inc. · TerraUniversal.com · 800 S. Raymond Ave. · Fullerton, CA 92831 · TEL: (714) 578-6000 · FAX: (714) 578-6020
Installation Guide
Fire-Rated CleanMount® Cleanroom Windows
© Copyright 2023 Terra Universal Inc. All rights reserved. · Revised January 2022 · Document No. 1790-20
10. Apply final paint to drywall and finishing touches to frame, such as silicone caulking. Make sure all sealants are compatible with materials they come in contact with.
11. Clean glass after installation. See separate glass cleaning and maintenance instructions.