Danfoss Ak-rc 305w-sd Temperature Controller For Walk In Coolers And Freezers Installation Guide

Danfoss Ak-rc 305w-sd Temperature Controller For Walk In Coolers And Freezers Installation Guide

Danfoss LOGOAK-RC 305W-SD Temperature Controller for
Walk-In Coolers and Freezers
Installation Guide
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers

Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - BAR CODEWarning icon Warnings

  • If the equipment is used without adhering to the manufacturer’s instructions, the device safety requirements could be compromised. Only probes supplied by Danfoss must be used for the unit to operate correctly.
  • From -40 – +20 °C, if the NTC probe is extended to 1000 m with at least 0.5 mm 2 cable, the maximum deviation will be 0.25 °C
  • It should be installed in a place protected from vibrations, water and corrosive gases, where the ambient temperature does not exceed the value indicated in the technical data.
  • For the reading to be correct, the probe should be used in a place without heat influences apart from the temperature you want to measure or control.
  • The IP65 protection degree is only valid with the protection cover closed.
  • The IP65 protection degree is only valid if the cables enter the device using a tube for electric conductions + gland with IP65 or above.
    The size of the glands should be suitable for the diameter of the tube used.
  • Do not spray the unit directly with high-pressure hoses, as this could cause damage.

IMPORTANT:

  • Before starting the installation, you must take the advice of local regulations in force.
  • The AUXILIARY relays are programmable, and their operation depends on the configuration.
  • The function of the digital inputs depends on the configuration.
  • The recommended currents and powers are the maximum working currents and powers.

Wiring
Electric Warning IconAlways disconnect the power supply to do the wiring.
The probes and their cables should NEVER be installed in a conduit together with power, control, or power supply cables.
For disconnection, the power supply circuit must be equipped with at least a 2 A, 230 V switch, located near the device. The power supply cable shall be of the H05VV-F or NYM 1×16/3 type. The cross-section to be used will depend on the local regulations in force, but must never be less than 1.5 mm 2.
Cables for relay or contactor outputs must have a cross-section of 2.5 mm 2 and allow working temperatures equal to or over 70 °C and must be installed with as little bending as possible.
The 120/230 V~ wiring area must be kept clear of any other external element.
The wiring to be undertaken depends on the option selected in the initial configuration wizard. Use the appropriate diagram based on the option selected. Check the available options on the diagrams included in the controller’s packaging. Wizard refers to a built-in tool to guide the user through the setup process.

Maintenance

  • Clean the surface of the unit with a soft cloth, water, and soap.
  • Do not use abrasive detergents, petrol, alcohol, or solvents, as this might damage the unit.

Keypad

Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - ESEPressing it for 3 seconds activates/deactivates Stand-By mode. In this mode, regulation is paused and the Ardes AR1K3000 Air Fryer Oven - Icon 10icon is displayed.
In the programming menu, this exits the parameter without saving changes, returns to the previous level, or exits programming.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - ESPressing once without holding displays the temperature of probe S2 for 2 seconds (if it is enabled).
Pressing it for 3 seconds starts/stops the defrost.
In the programming menu, this allows scrolling around the different levels, or, during the setting of a parameter, changing its value.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - RETREYA brief press shows the ADAPTIVE mode operating alerts.
Pressing it for 3 seconds activates/deactivates continuous cycle mode.
In the programming menu, this allows scrolling around the different levels, or, during the setting of a parameter, changing its value.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - ressingPressing once without holding activates/deactivates the cold room light.
Pressing it for 3 seconds accesses the condensed programming menu.
Pressing it for 6 seconds accesses the expanded programming menu.
In the programming menu, this accesses the level shown on the display or, during the setting of a parameter, accepts the new value.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - displaysPressing once without holding displays the current effective value of the Set Point, taking into consideration temporary modifications by other parameters (C10 or  C12).
When an alarm is in progress, pressing once without holding mutes the acoustic alarm. Pressing for 3 seconds accesses the Set Point setting.

Indicators

Ardes AR1K3000 Air Fryer Oven - Icon 10Fixed: Stand-by Mode activated. Regulation is paused.
Flashing: Controlled shutdown process for the regulation in progress.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - doorFixed: Cold room door open.
Flashing: The door has been open for a greater time than has been defined in parameter A12.
warning 2There is an active alarm, but not an active HACCP alarm.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - HACCPFixed: HACCP alarm active.
Flashing: HACCP alarm registered and unconfirmed.
Press theDanfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - MUTE key to confirm a HACCP alarm.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - FixedFixed: The ADAPTIVE mode is active.
Flashing: An error has been detected in the ADAPTIVE mode.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - fansFixed: Evaporator fans active.
Flashing: The evaporator fans should be active but a delay is preventing this.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - solenoidFixed: The cold solenoid is active.
Flashing: The solenoid should be active but a delay or protection is preventing this.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - CompressorFixed: Compressor active.
Flashing: The compressor should be active but a delay or
protection is preventing this.
Defrost relay active.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - cycleContinuous cycle mode is active.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - room lightCold room light active.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - MUTEThe alarm in progress is muted.
°F°CTemperature displayed in ° Fahrenheit / ° Centigrade.
PRGProgramming mode active.

STAND-BY
Warning iconIf the temperature regulation cannot be instantly stopped due to its configuration, a controlled stop process starts, and theArdes AR1K3000 Air Fryer Oven - Icon 10 icon flashes. To stop the controlled stop process and force the step to Stand-by, press the Stand-by key again for 3 seconds.

Installation of the probes

To achieve maximum performance from the advanced controller, the correct installation of the probes is key, as they are responsible for calculating the evaporator’s thermal transfer coefficient, evaluating the start and end of the defrosts, and diagnosing problems in the evaporator.

Material included

  • 4 mm hermetic evaporator probe, 1.5 m of cable.
  • Ambient probe
  • 1 mounting clip for 10 – 13 mm coil
  • 1 mounting clip for 14 – 18 mm coil
  • 1 mounting clip for 19 – 21 mm coil
  • 1 mounting clip for 22 – 25 mm coil

Location of the ambient probe
The probe should be located in a place that does not directly receive the flow of cold air from the evaporator.
Preferably in its air aspiration area.
Location of the evaporator probe
The probe must be located as near as possible to the inlet of refrigerant from the evaporator (close to the expansion valve) in the finned area. In certain evaporators, for example, cubic ones, this inlet may be located on the front part of the battery, just behind the fan.
If defrosting is done by electric heat, the probe must be located far away from them and, if possible, in the area of the evaporator where defrosting is slower, in other words, in the last area to defrost.
If the two conditions are not possible, the best possible compromise must be looked for.

Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - appropriateDanfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - pipeDanfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - fixin
Select the appropriate clip depending on the size of its evaporator pipe.Attach the probe to the pipe using the clip, making sure that its end is in direct contact with the tube.Bend the fins of both ends of the probe to increase the fixing and contact surface.

Initial configuration (wizard)

The first time the unit receives the power supply, it will enter into ASSISTANT mode. The display will show the messageDanfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - ICON flashing with 0.Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - wizard)

Step 1:
Select the most suitable InI option based on the type of installation to be carried out and press SET. The available options will be shown in the following table:

InlType of installationParametersDiagram
to be used
Cold regulationPump
Down
DefrostEvap.
fans
Pdo00100110111120121dld7F3
0Demo Mode: it displays the temperature but does not regulate the temperature or activate relays
1SolenoidNoElectricYes00200002000A
2Solenoid + compressorYesElectricYes11271002000B
3Solenoid + compressorNoElectricYes01200002000B
4SolenoidNoAirYes00100002011A
5Solenoid + compressorYesAirYes11171002011B
6Solenoid + compressorNoAirYes01100002011B
7Solenoid + compressorYesHot gasYes1127191520C
8Solenoid + compressorNoHot gasYes0120091520C

Note: If options 2, 5, or 7 are chosen, check the configuration of parameter I11 according to the pressure switch type used. (See diagram included with the device).

Step 2:
Use keysDanfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - ICON1 andDanfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - ICON 2 to enter the desired Temperature Set Point value and press SET. The configuration wizard has finished. The unit will begin to regulate the temperature.
If this is not the first time you use the wizard, after completing the last step the display will show the message dFp (default parameters). You may choose between two options:
0: Only changing the parameters which affect the wizard. The other parameters will remain the same.
1: All parameters return to their factory setting except those which have been modified by the wizard.Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - Step 2Important: The wizard will not reactivate. To enter the wizard mode, initiate Stand-by mode by pressing the key for 3 seconds and wait until the unit completely halts the temperature regulation (the indicator will light up permanently) and press the following keys in sequence one after the other, Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - ICON1, Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - ICON 2, SET.
Warning icon Stand-by: If the regulation cannot be instantly stopped due to its configuration, a controlled stop process starts and the icon flashes.
To stop the controlled stop process and force the step to Stand-by, press the Stand-by key again for 3 seconds.

Operation

Display messages

Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - Display messagesPump down malfunction error (stop), the time configured in parameter C20 has been exceeded.
Only displayed on the screen.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - Display messages2Pump down malfunction error (start-up), the time configured in parameter C19 has been exceeded.
Only displayed on the screen.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - Display messages3Probe 1/2/3 failure (open circuit, crossed circuit, or temperature outside the limits of the probe) (Equivalent limits in °F).
Only E2 and E3: Damp evaporator probe.
Activates the alarm relay and the audible alarm.
Flashing with temperature: Probe error 1/2/3 in ADAPTIVE mode.
Flashing with CAL: Probe error 1/2/3 during the calibration.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - Display messages4Open door alarm. Only if the door remains open for a longer time than defined in parameter A12.
Activates the alarm relay and the audible alarm.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - Display messages5Maximum temperature in control probe alarm. The temperature value programmed in A1 has been reached.
Activates the alarm relay and the audible alarm.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - Display messages6The minimum temperature in the control probe alarm. The temperature value programmed in A2 has been reached.
Activates the alarm relay and the audible alarm.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - Display messages7External alarm activated (by digital input).
Activates the alarm relay and the audible alarm.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - Display messages8Severe external alarm activated (by digital input).
Activates the alarm relay and the audible alarm.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - Display messages9The alarm for defrosting was completed due to a time-out. The time set in d1 has been exceeded.
Activates the alarm relay and the audible alarm.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - Display messages10HACCP alarm. The temperature has reached the value of parameter h1 during a longer period than established in h2.
Activates the alarm relay and the audible alarm.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - Display messages11HACCP alarm due to a power supply failure. The temperature established in h1 has been reached, following a power
supply failure. Activates the alarm relay and the audible alarm.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - Display messages12Indicates that a defrost is being performed.
Only displayed on the screen.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - PASPassword request. See parameters b10 and PAS.
Only displayed on the screen.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - 51Shown sequentially with the temperature: The controller is in demo mode, and the configuration has not been made.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - CALCalibration is ongoing, therefore, avoid, as far as possible, opening the cold room during the process.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - E 16Flashing with temperature: Configuration has been changed from 1 to 2 evaporators or vice versa.

ADAPTIVE MODE ALERT MESSAGES (Only shown pressing theDanfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - ICON 2 key)

Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - ADAPTIVE MODE ALERT MESSAGES 1Defrost end error in the 1/2 evaporator during the calibration, defrost has not ended due to temperature.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - ADAPTIVE MODE ALERT MESSAGES 2Error during calibration in 1/2 evaporator. There is not enough difference in temperature between the cold room probe and the evaporator probe.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - ADAPTIVE MODE ALERT MESSAGES 3It has not been possible to carry out the calibration due to a lack of stability in the system
(Excessive door opening, excessive oscillations in the lower pressure, etc.).
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - ADAPTIVE MODE ALERT MESSAGESError during normal operation (ADAPTIVE Mode active) in 1/2 evaporator. There is not enough difference in
temperature between the cold room probe and the evaporator probe.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - ADAPTIVE MODE ALERT MESSAGES 4A lack of stability has been detected in the system (Excessive door opening, excessive oscillations in the low pressure,
etc.) during normal operation (ADAPTIVE Mode active).
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - ADAPTIVE MODE ALERT MESSAGES 5The persistent lack of stability has led to the deactivation of the ADAPTIVE mode.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - ADAPTIVE MODE ALERT MESSAGES 6Excessive door openings have been detected during calibration and it has not been possible to calibrate.
Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers -ADAPTIVE MODE ALERT MESSAGES 7Excessive door openings have been detected and the device cannot regulate in ADAPTIVE mode.

Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - Fixed ADAPTIVE mode
If the ADAPTIVE mode is activated (default configuration), the device periodically evaluates the evaporator’s heat transfer, managing the available resources to maximize it.
The defrosts are minimized, adapting to the changing conditions of the cold room, reducing heat input into the refrigerated space, thermal stress in the evaporator, and energy consumption.
Operation of the evaporate fans is optimized taking into account the compressor status, evaporate temperature, frost level, the opening of the door, etc.
The control function of the drainage resistor minimizes its activation (moments before starting a defrost), thereby reducing energy consumption.
To achieve correct operation of the ADAPTIVE mode, it is very important for the probes to be correctly installed, as described on page 3.

Calibration
During the first hours of operation, the device performs two calibrations automatically, during which the display shows the CAL message.
Calibration may take several hours and include several refrigerations and defrost cycles.
Warning iconDuring the calibration processes, the following should be avoided:Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - CAL3

  • Opening the cold room door
  • Turning the controller off or putting it on standby
  • Changing controller parameters, including the set point

IMPORTANT:
While the calibration process is active:

  • Manual defrost cannot be activated ( key)
  • The continuous cycle cannot be activated
  • The set point change function cannot be activated

If calibration cannot be performed, or if an important part of the installation is replaced (compressor, evaporator, etc.) it is advisable to perform a manual calibration.
It is also recommended (not essential) to perform a manual calibration, once the installation has completed its commissioning, with a load inside it and when its operating temperature has been stabilized, after several days of operation, in this way calibration is optimal.
In the event of changing the set point or hysteresis, the device performs a calibration again automatically, except if the set point change is made using the “set point change mode” function.
To perform a manual calibration, access the parameter menu and follow the sequence indicated below:

  • Access parameter b30
  • A security code is requested, enter code 63
  • Using keys Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - ICON1and Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - ICON 2 select option 1 and press SET

Configuration

Condensed programming menu
This allows for the most-used parameters to be quickly configured.
Press the SET key for 3 seconds to access it.

Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - Condensed programming menu

Parameters

Lv 2DescriptionVal.Min.Def.Max.
SPTemperature setting (Set Point)°C/°F-500.099
CEADAPTIVE Mode O=Deactivated, 1= Activated011
ClProbe 1 differential (Hysteresis)°C/°F0.12.020.0
dODefrost frequency (Time between 2 starts)H.0696
d 1Maximum defrost duration (0=defrost deactivated)Min.0*255
d4Final defrost temperature (by the probe) (If P4 #1)°C/°F-508.050
F3Status of the fans during the defrost: O=Shut down, 1=Running001
AlAlarm for the maximum in probe 1 (It should be higher than the SP)°C/°FA29999
A2Alarm for minimum in probe 1 (It should be lower than the SP)0C/7-50-50Al
d30Defrost strategy in ADAPTIVE mode0510

Extended programming menu
Use the extended programming menu to configure all of the unit’s parameters in order to adapt it to your installation requirements.
Press the SET key for 6 seconds to access it.
Important:

  • If the password function has been configured as a keypad lock (b10=2), or as access to parameters block (b10=1), you will be requested to enter the password programmed in PAS when attempting to access either of the two functions. If the entered password is not correct, the unit will go back to showing the temperature.
  • Certain parameters or menus may not be visible depending on the configuration of the rest of the parameters.Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - Extended programming menu

Regulation and control

Level 1Level 2DescriptionValuesMin.Def.Max.
rESPTemperature setting (Set Point)°C/°F-500.099
CEADAPTIVE Mode: 0=Deactivated, 1= Activated011
COProbe 1 & 2 calibration (Offset)°C/°F–4.00.04.0
ClProbe 1 differential (Hysteresis)°C/°F0.12.020.0
C2Set Point top locking (it cannot be set above this value)°C/°FC39999
C3Set Point bottom locking (it cannot be set below this value)°C/°F-50-50C2
C4Type of delay for the protection of the compressor:
0=Minimum time of compressor in OFF
1=Minimum time of compressor in OFF and in ON in each cycle
001
CSProtection delay time (value of the option selected in parameter C4)Min.00120
C6COOL relay status with fault in probe 1:
0=OFF; 1=0N; 2=Average according to last 24 h prior to probe error 3=0N-OFF according to prog. C7 and C8
023
C7Relay time in ON in the event of probe 1 failure
(If C7=0 and C8*0, the relay will always be disconnected in OFF)
Min.010120
CSRelay time in OFF in the event of probe 1 failure
(If C8=0 and C70, the relay will always be connected in ON)
Min.05120
C9Maximum duration of the continuous cycle mode (0=deactivated)H.0048
C10Variation of the Set Point (SP) in continuous cycle mode. When it reaches this point (SP+CI 0), it reverts to the normal mode. (SP+CI 0 a C3).
The value of this parameter is always negative unless it is O. (0=OFF)
°C/°F0-50C3-SP
CUVariation of the Set Point (SP) when the change Set Point function is active. (SP+C12 s C2) (0= deactivated)°C/°FC3-SP0.0C2-SP
C19Maximum start time from Pump Down
(Values between 1 and 9 seconds will not be accepted) (0=deactivated)
Sec00120
C20The maximum time for pump down (0= deactivated)Min.0015
C21Probe to be displayed: 0=All probes (sequential), 1=Probe 1 (Cold Room), 2=Probe 2 (Evaporator), 3= Probe 3 (According to 120), 4=Weighted temperature of the cold room013
C22Stop fans and compressor on opening door 0=No, 1=Yes001
C23Start-up delay for fans and compressor with the door openMin.00999
C24Delay time of cold stop with the door open.Seg.00C23
C25Influence of probe S3 when regulating with two temperature probes (120=10)%0095
C27Probe 3 calibration (Offset)°C/°F–4.00.04.0
EPExit to level 1

Defrost

Level 1Level 2DescriptionValuesMin.Def.Max.
dEFdODefrost frequency (Time between 2 starts)H.0696
dlMaximum defrost duration (0=defrost deactivated)Min.0255
d2Type of message during the defrost:
O=Displays the real temperature; 1=Displays the temperature at the start of the defrost; 2=Displays the dEF message
022
d3The maximum duration of the message
(lime added at the end of the defrost process)
Min.05255
d4Final defrost temperature (by the probe) (If 100 * 1)°C/°F-508.050
d5Defrost on connecting the unit:
O=NO First defrost according to d0; 1=YES, First defrost according to d6
001
d6Delay of the defrost start on connecting the unitMin.00255
drType of defrosting:
0=Resistors; 1=Air/fans, 2=Hot gas; 3=Reversal of cycle
03
d8Count of time between defrost periods:
Total real-time, 1 =Sum of compressor connected time
001
d9Drip time when completing defrost (Shutdown of compressor and fans)Min.01255
d30Defrost strategy in ADAPTIVE mode0510
d31Maximum time without defrosting (O=Deactivated)H.096999
d32Maximum time of cold room outside the temperature regulation range (O=Deactivated)H.0210
EPExit to level 1

* According to the wizard.
1) It can only be modified using the configuration wizard (InI).

Evaporator fans

Level 1Level 2DescriptionValuesMin.Def.Max.
FAnFOShutdown temperature of fans°C/°F-504550
FlProbe 2 differential if fans are shut down°C/°F0.12.020
F2Shut down fans when the compressor shuts down: 0=No, 1=Yes001
F3Status of the fans during the defrost: 0=Shut down, 1=Running001
F4Delay of start-up after defrost (If F3=0) It will only actuate if it is higher than d9Min.0299
EPExit to level 1

Alarms

Level 1Level 2DescriptionValuesMin.Def.Max.
ALAOConfiguration of the temperature alarms: O=Relative to SR 1=Absolute011
AlAlarm for the maximum in probe 1 (It should be higher than the SP)°C1°FA29999
A2Alarm for minimum in probe 1 (It should be lower than the SP)°C/°F-50-50Al
A3Delay of temperature alarms in the start-upMin.00120
A4Delay of temperature alarms from the end of a defrostMin.0099
ASDelay of temperature alarms from when the Al or A2 value is reached03099
A6Delay of the external alarm/Severe external alarm on receiving a signal in digital input (110 or 120 = 2 or 3)Min.00120
A7Delay of external alarm deactivation/Severe external alarm deactivation when the signal in digital input disappears (110 or 120 = 2 or 3)Min.00120
A8Show warning if the defrost ends for maximum time: 0=No, 1=Yes001
A9Relay alarm polarity
0= Relay ON in alarm (OFF without alarm); 1= Relay OFF in alarm (ON without alarm)
001
Al 0The differential of temperature alarms (Al and A2)°C/°F0.11.020.0
Al2Delay of open door alarm (If 110 or 120=1)Min.010120
EPExit to level 1

Basic configuration

Level 1Level 2DescriptionValuesMin.Def.Max.
BCNb00Delay of all functions on receiving power supplyMin.00255
b01Cold room light timingMin.00999
b10Function of password
0=Inactive, 1=Block access to parameters, 2=Block keypad
002
PMAccess code (Password)0099
b20MODBUS address00247
b21Communication speed:
0=9600 bps, 1=19200 bps, 2=38400 bps, 3=57600 bps
bps023
b22Acoustic alarm enabled: 0= No, 1=Yes011
b30Activation of manual calibration: 0=Deactivated, 1=Activated Requires security code, see page 6.001
UntWork units: 0=°C, 1=°F011
EPExit to level 1

Inputs and outputs

Level 1Level 2DescriptionValuesMin.Def.Max.
In0100Connected probes
1=Probe 1 (Cold room), 2=Probe 1 (Cold room) + Probe 2 (Evaporator)
122
110′)Configuration of digital input 1
0= Deactivated, 1=Door contact, 2=External alarm,
3=Severe external alarm, 4=Change of SP, 5=Remote defrost, 6=Defrost block, 7= Low-pressure switch, 8=Remote Stand-by
08
IllThe polarity of the digital input 1
0=Activates on closing contact; 1=Activates on opening contact
01
120Configuration of digital input 2
0= Deactivated, 1=Door contact, 2=External alarm,
3=Severe external alarm, 4=Change of SP, 5=Remote defrost,
6=Defrost block, 7=Register probe, 8=Probe 2° evaporator”,
9=High pressure switch for Hot Gas, 10=2nd cold room temperature probe, 11=Product temperature, 12=Remote Stand-by
0012
121The polarity of the digital input 2
0=Activates on closing contact; 1=Activates on opening contact
001
000¹)Configuration of relay AUX1
0=Deactivated, 1=Compressor/Resistor sump, 2=Light. 3=Virtual control
03
ol 0Configuration of relay AUX2
0=Deactivated, 1=Alarm, 2=Light, 3=Virtual control,
4=Door frame resistance, 5=Defrost 2° evaporator,
6=Same as solenoid status, 7=Same as unit status, 8=Drainage resistor
028
EPExit to level 1

* According to the wizard.

  1. It can only be modified using the configuration wizard (InI).
  2. Option not available in AK-RC 305W-SD

HACCP alarm

Level 1Level 2DescriptionValuesMin.Def.Max.
HCPhlMaximum temperature of HACCP alarm°C/°f-509999
h2Maximum permitted time for activation of the HACCP alarm (O=Disabled)H.00255
EPExit to level 1

Information (reading only)

Level 1Level 2DescriptionValuesMin.Def.Max.
tidInlThe option is chosen in the configuration wizard
Pd'”Pump down active? 0=No, 1=Yes
PUProgram version
PrProgram revision
bUBootloader version
brBootloader revision
PArParameter map revision
EPExit to level 1
  1. It can only be modified using the configuration wizard (InI).

Troubleshooting

Errors during calibration
The error message is displayed alternately with the CAL message. The Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - Fixedicon flashes.

ErrorDescriptionSolution
El /E2/E3Probe error 1 / 2 / 3Check the condition and wiring of the affected probe.
El 0Evaporator defrost errorCheck defrost operation, it must end by temperature (d4).
0.00E+00Idem for El 0 but relating to the second evaporator
El 1The similar temperatures in probes S1 and S2Check the position of both probes following the recommendations on page 3.
0.00E+00Idem for El 1 but relating to probe 53
0.00E+00It has not been possible to carry out the calibration due to a lack of stability in the systemAvoid opening the cold room door during calibration.
Check the main components of the refrigeration circuit, in particular the aspiration part.
0.00E+00Idem for E12 but relating to the second evaporator
El 7Excessive door openings have been detected during calibration and it has not been possible to calibrate.Avoid opening cold room doors during calibration.

Errors during operation
The error message is displayed alternately with the temperature. The Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - Fixedicon flashes.

ErrorDescriptionSolution
El /E2/E3Probe error 1 / 2 / 3Check the condition and wiring of the affected probe.
El3Similar temperatures in probes S1 and S2Check the position of both probes following the recommendations on page 3.
0.00E+00Idem for Ell but relating to probe 53
0.00E+00A lack of stability has been detected in the systemCheck the main components of the refrigeration circuit, in particular the aspiration part.
0.00E+00Idem for E14 but relating to the second evaporator
El 5Persistent lack of system stability has led to the deactivation of the ADAPTIVE modeCheck the main components of the refrigeration circuit, in particular, the aspiration part and the position of probe 2 or 3.
To return to the ADAPTIVE mode restart the device.
0.00E+00Idem for El 5 but relating to the second evaporator
El 6The configuration has been changed from 1 to 2 evaporators or vice versa.If the configuration change is correct, start a manual calibration.
0.00E+00Excessive door openings have been detected and the device cannot regulate in ADAPTIVE mode.Check that the door has not been left open or that it does not open more than necessary.

Technical specifications

FeaturesSpecifications
Power supply100 – 240 V- 50/60 Hz
Maximum input power in the operation6.3 VA
Maximum nominal current15 A
Relay SSV / DEFROST – SPDT – 20 ANOEN60730-1: 15 (15) A 250 V-
NCEN60730-1: 15 (13) A 250 V-
Relay FAN – SPST – 16 AEN60730-1: 12 (9) A 250 V-
Relay COOL – SPST – 16 AEN60730-1: 12 (9) A 250 V-
Relay AUX 1 – SPDT – 20 ANOEN60730-1: 15 (15) A 250 V-
NCEN60730-1: 15 (13) A 250 V-
– –
Relay AUX 2 SPDT 16 A
NOEN60730-1: 12 (9) A 250 V-
NCEN60730-1: 10 (8) A 250 V-
No. of relay operationsEN60730-1:100.000 operations
Probe temperature range-50.0 – +99.9 °C
The resolution, setting, and differential0.1 °C
Thermometric precision±1 °C
Loading tolerance of the NTC probe at 25 °C±0.4 °C
Working ambient temperature-10 – +50 °C
Storage ambient temperature-30 – +60 °C
Protection degreeIP 65
Installation categoryII s/ EN 60730-1
Pollution degreeII s/ EN 60730-1
Control device classificationBuilt-in assembly, with Type 1. B automatic operation action feature, for use in clean situations, logical support (Software) class A and continuous operation. Degree of contamination 2 acc. to UNE-EN 60730-1.
Double isolation between the power supply, secondary circuit, and relay output.
The temperature during the ball-pressure testAccessible parts: 75 °C
Parts which position active elements: 125 °C
The current of radio jamming suppression tests270 mA
Voltage and current as per EMC tests207 V, 17 mA
Type of AssemblyFixed internal
MODBUS addressShown on label
Dimensions290 mm (W) x 141 mm (H) x 84.4 mm (D)
Internal buzzerYes

Ordering

Controller

ModelDescriptionCommentsCode no.
AK-RC 305W-SDAK-RC 305W-SD Gen. 2,5 0/P, Single phaseInclude: 2 x 1.5 m, NTC 10K sensor080Z5003

Accessory (for spares and replacement purposes):

NameFeaturesQtyCode no.
NTC sensors10K, High Prec. 1.5 m1080Z3216

Danfoss AK-RC 305W-SD Temperature Controller for Walk In Coolers and Freezers - QR CODE

http://scn.by/krzp87a5z2akq1

For more details, see the full User Manual and other information, and scan the QR code.

© Danfoss
Climate Solutions 

AN41504517847601-000102 

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals