Victron Energy Smart Batteryprotect 48/100 Instruction Manual

Victron Energy Smart Batteryprotect 48/100 Instruction Manual

victron energy - logoSmart BatteryProtect 48/100
Instruction Manualvictron energy Smart BatteryProtect 48 100

Installation

  1. The Smart BatteryProtect (SBP) must be installed in a well-ventilated area and preferably close (max 50 cm) to the battery (but, due to possible corrosive gasses not above the battery!). The voltage drop over a long or undersized cable between the battery plus and the SBP may result in a short circuit alarm when starting up the load, or an unexpected shutdown.
  2. A properly sized fuse must be inserted according to local regulations in the cable between the battery and the SBP.
  3. The SBP is designed to allow current to flow from IN (battery) to OUT (load) terminals only.
    Reverse currents from OUT to IN terminals are strictly forbidden and will damage the device. If you wish to use the SBP as a disconnection for a charge source, you must orient the unit in the system so that the current is flowing in the intended direction, IN to OUT.
  4. The short circuit protection of the SBP will be activated if you try to directly connect loads with capacitors on their input (eg inverters). For that use case, please use the  SBP to control the remote on/off switch on the inverter, instead of disconnecting the higher power DC line.
  5. Use a 1,5mm² wire (included) for the minus connection, which should be connected directly to the battery minus (or the chassis of a vehicle). No other equipment should be connected to this wire.
  6. The SBP automatically detects the system voltage after the connection of plus and minus to the battery. During the voltage detection, the 7-segment display shows a series of flashes between the top and lower parts.
  7. Do not connect the load output until the SBP has been fully programmed.
  8. A remote on-off switch can be connected between Remote H and Remote L (see figure 1).
    Alternatively, terminal H can be switched to battery plus, or terminal L can be switched to battery minus.
  9. A buzzer, LED or relay can be connected between the alarm output and the battery plus (see figure 1).
    Maximum load on the alarm output: 50 mA (short circuit proof).

Load disconnect events and alarm output options

Buzzer or LED mode (buzzer or LED connected to the alarm output):

  • In case of under voltage, a continuous alarm will start after 12 seconds. The SBP will disconnect the load after 90 seconds and the alarm will stop. Reconnect delay: 30 seconds.
  • In case of overvoltage, the load will be disconnected immediately and an intermittent alarm will remain on until the overvoltage problem has been corrected. There is no reconnect delay.
    Relay mode (relay connected to the alarm output):
  • In case of under voltage, the relay will engage after 12 seconds. The SBP will disconnect the load after 90 seconds and the relay will disengage.
  • In case of over voltage, the load will be disconnected immediately and the alarm output will remain inactive. Overvoltage trip level: 65.2V Li-ion mode:
  • Connect the load disconnect output of the VE. Bus BMS to Remote H terminal.
    The load is disconnected immediately when the load-disconnect output of the VE. Bus BMS switches from ‘high’ to ‘free floating’ (due to battery cell under voltage, over-voltage, or over temperature). The under voltage thresholds and alarm output of the SBP are inactive in this mode.

Operation

There are 6 possible error modes, indicated by the 7-segment display and on a Bluetooth-enabled device:

  • E1 Short circuit detected
  • E2 Overload or over temperature / P2 over temperature warning
  • E3 Under voltage / P3 under voltage warning
  • Overvoltage
  • Settings Failure
  • Reference Voltage Failure
  • BMS Lockout

Programming

When switched off (remote open), the SBP can be programmed by connecting the PROG pin to the ground.
Alternatively, it can be programmed with a Bluetooth-enabled smartphone or tablet regardless of the remote status.
The 7-segment display will first step through the shutdown and restart voltages. Disconnect the PROG pin when the desired voltage is displayed.
The display will confirm the chosen voltage and default mode (R) twice.
Reconnect the PROG pin to the ground if another mode is (b or c) is required. Disconnect when the required mode is displayed.
The display will confirm the chosen voltage and mode twice.
Bluetooth can be disabled/re-enabled with the VictronConnect app or by connecting the PROG pin to the ground and selecting F(enable) or h (disable). See table below

Programming table

7 segment displayUnder voltage shut down
48V system
Under voltage restart
48V system
042V48V
I40V46V
238V46V
345V53V
446V55,2V
S42V51,2V
646V51,2V
147,2V51,2V
648V52V
940V52,8V
User-defined settings with Bluetooth
FlBuzzer or LED mode
bRelay mode
CLi-ion mode
FBluetooth Enable
hBluetooth Disable
Smart BatteryProtectSBP 48|100
Maximum cont. load current100A
Peak current250A
Operating voltage range24 – 70V
Current consumptionWhen on: 1,9mA   When off or low voltage shutdown: 1,7mA
Alarm output delayWhen on: 1,7mA   When off or low voltage shutdown: 1,6mA
Max. load on alarm output12 seconds
Load disconnect delay50mA (short circuit proof)
Default thresholds90 seconds (immediate if triggered by the VE.Bus BMS)
Operating temperature rangeDisengage: 42V   Engage: 48V
ConnectionFull load: -40°C to +40°C (up to 60% of nominal load at 50°C)
WeightM8
Dimensions (hxwxd)0,8kg   1.8 lbs

Example Wiring Diagrams

victron energy Smart BatteryProtect 48 100 - Figure 1victron energy Smart BatteryProtect 48 100 - Figure 2

victron energy Smart BatteryProtect 48 100 - Figure 3

Figure 1 Connection diagram of the SBP 48|100 (use the remote input for system on/off functionality)

victron energy Smart BatteryProtect 48 100 - Figure 4

Figure 2: Connection diagrams and pin numbering

victron energy Smart BatteryProtect 48 100 - Figure 5

Figure 3: System with 48V Li-ion battery set
(Applicable with VE.Bus BMS or mini BMS)
Note: When in Li-ion mode, the SBP will disengage when the H input becomes free-floating, and will remain disengaged for 30 seconds even if it receives a re-engage signal within that time period. After 30 seconds it will respond immediately to a re-engage signal. Therefore, there will normally be no waiting time if the SBP is used as a system on-off switch (use the System on/off switch in the positive supply of the BMS for this purpose).
Similarly, if a system shutdown occurred due to low cell voltage, the SBP will remain disengaged for 30 seconds even if it receives a re-engage signal within that time period  (which will happen when no other loads are connected to the battery). After 3 attempts to re-engage, the SBP will remain disengaged until battery voltage has increased to more than 52V during at least 30 seconds (which is a sign that the battery is being recharged). The under voltage thresholds and alarm output of the SBP are inactive in this mode. To manually make it start again, briefly disconnect and reconnect the remote on/off terminal or switch the BMS off and on again.

victron energy Smart BatteryProtect 48 100 - Figure 6Figure 4: DC solar system with Lithium battery (applicable with VE.Bus BMS or miniBMS)
Caution: uncontrolled reverse current will flow through a Smart BatteryProtect if Vout > Vin. Therefore, never use a Smart BatteryProtect for battery-to-battery charging.

Victron Energy B.V. / De Paal 35 / 1351 JG ALMERE / Nederland
Telefoon: (+31) (0)36 535 97 00 / www.victronenergy.com / e-mail: [email protected]

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals