Schneider Electric Mfr40472 Vigilohm Local Remote Display Instruction Manual

Schneider Electric Mfr40472 Vigilohm Local Remote Display Instruction Manual

Schneider Electric LogoMFR40472 Vigilohm Local Remote Display
Instruction Manual
Schneider Electric MFR40472 Vigilohm Local Remote Display

MFR40472 Vigilohm Local Remote Display

Schneider Electric MFR40472 Vigilohm Local Remote Display - Icon 1 Local Remote Display (Version 2.0.0) to display messages inside the operation theatre. The messages include insulation fault, transformer overload and overheat, product error, system error, circuit breaker trip, digital input fault, and communication error.
Commercial reference IMDLRDH

www.se.com Schneider Electric MFR40472 Vigilohm Local Remote Display - Icon 2Local Remote Display

Schneider Electric MFR40472 Vigilohm Local Remote Display - Figure 1

DescriptionCommercial Reference/Part number/Range
AHMI ControllerHMISCU8A5
BContinuous BuzzerXB5KSB
CResistor39 kΩ 2 W
DResistor2 MΩ 0.5 W
EInstruction SheetMFR40472

Note: Do not use the product if it is damaged. Contact Schneider Electric customer care representative for support (www.se.com/support).

Safety precautions

Schneider Electric MFR40472 Vigilohm Local Remote Display - Icon 3DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E in the USA, CSA Z462 or applicable local standards.
  • Turn off all power supplying this device and the equipment in which it is installed before working on the device or equipment.
  • Always use a properly rated voltage sensing device to confirm that all powers are off.
  • Treat I/O wiring connected to multiple devices as hazardous live until determined otherwise.
  • Do not exceed the device’s ratings for maximum limits.
  • Do not use this device for critical control or protection applications where human or equipment safety relies on the operation of the control circuit.

Failure to follow these instructions will result in death or serious injury.

Installation

  1. Install the HMI Controller.
  2. Connect devices as per the configurations supported. Refer Section 4 for various configurations.
    Note: Refer Harmony SCU HMI controller quick reference guide (S1B90406) for installation and wiring information.
  3. Connect the 2 MΩ resistor between the pins 1 and 3 of the IM20-H.
  4. Connect the buzzer between the power supply (0 Vc) and pin A4 (C1) of the IMDLRDH.
  5. Connect the power supply (+24 Vc) to the pin B4 (DQ3) of the IMDLRDH.
  6. Connect the 39 kΩ resistor between the pin 1 of the IM20-H and the pin B1 (DQ0) of the IMDLRDH.
  7. Connect the pin A1 (C0) of the IMDLRDH to system ground.
    Note: IMDLRDH can detect 2 digital outputs from the application.
  8. Connect digital output from the application between the pins D4 (DI0) or C5 (DI1) and D5 (C1) of the IMDLRDH.Schneider Electric MFR40472 Vigilohm Local Remote Display - Dimension

Configuration

Schneider Electric MFR40472 Vigilohm Local Remote Display - Configuration 1Schneider Electric MFR40472 Vigilohm Local Remote Display - Configuration 2

Compatible DevicesCommercial reference
IM20-H+1IMD-IM20-H
IFL12H+2IMDIFL12H
Smart linkA9XMSB11 and A9XMEA08
Link150EGX150

+1: Firmware Version ≥ 2.3.0
+2: Up to 4 devices

Setup

Prerequisites:

  • Ensure that the installation is complete as per section 3.
  • Make note of the Modbus address of the all the connected devices. This information is required for configuring the devices.

Note: To edit or enter any value, touch the editable value and a data entry keypad displays. Use this keypad to enter the desired value and touch the Enter button to validate.

Steps:

  1. Power ON the HMI controller.
    The Password page displays.
    Note: The default password is 0000.
  2. Enter the password and touch the ok button.
    The Change Password page displays.
  3. Enter the new password and touch the ok button.
    The Settings page displays.
    ParameterDescriptionDefault valueAllowed values
    LANGUAGESelect the desired languageEnglish• English
    • German
    • Spanish
    • French
    • Portuguese
    • Italian
    ROOMEnter the desired room nameROOM-1Length: 1 to 16 characters
    • Alphabets
    • Numerical
    • Special characters
    COMMSelect the desired communication protocolRS485• RS485
    • TCP/IP
    Note: For TCP/IP, refer to TCP/IP configuration
    CABINET – 1
    IMDEnter the Modbus address01…247
    IFLEnter the Modbus address and the desired channel name0 (Modbus Address) For channel names:
    IFL12H-1 : A1…A12
    IFL12H-2 : B1…B12
    IFL12H-3 : C1…C12
    IFL12H-4 : D1…D12
    Modbus Address: 1…247
    Channel names: Length: 1 to 20 characters
    • Alphabets
    • Numerical
    • Special characters
    SMLEnter the Modbus address0SML1 : 1…247
    SML2 : 255
    Touch and enable the configured channels.
    Note: SML1 refers to the A9XMSB11 and SML2 refers to A9XMEA08.
    ParameterDescriptionDefault valueAllowed values
    DISelect the desired configuration for digital inputs (DI- 0, DI-1, DI-6 and DI-7) and enter the message.Digital Input Configuration:
    Disable
    Alarm State Configuration:
    Low
    Message:
    For DI-0: DI-0 message
    For DI-1: DI-1 message
    For DI-6: DI-6 message
    For DI-7: DI-7 message
    Digital Input Configuration:
    • Disable
    • Enable Alarm State
    Configuration:
    • Low
    • High Message: Length: 1 to 20 characters
    • Alphabets
    • Numerical
    • Special characters
    MESSAGEConfigure the messages for both the panels.
    Note: You can configure 3 lines of message.
    Call Electrical Maintenance at 00000
    Tell them what is displayed Carry on operation until further notification
    Length: 1 to 40 characters
    • Alphabets
    • Numerical
    • Special characters

    Touch the following parameters to view the information:

    ParameterDescription
    ABOUTDisplays the product name, version, and the QR code. QR code reads the device web page.
    ESCDisplays the Installation Ready message displays with green background.
  4. Touch and hold at bottom right corner of the device and the HMI controller settings page displays.
  5. Set the date/time of the HMI controller. Refer Harmony SCU HMI controller hardware guide (EIO0000001232) for date/time configuration.
    Note: To update settings after connecting different devices, touch the sumsung HW A450 Soundbar wDolby Audio - Icon 12 icon.

TCP/IP configuration:
If you chose TCP/IP communication protocol, perform the following steps:

  1. Enter the IP address of the gateway (Smart link or Link150).
    Note: If you have configured 2 panels, enter the IP address of gateway of both the panel.
  2. Touch the Magelisip button.
    The HMI controller settings page displays.
  3. Enter the IP address of the IMDLRDH in the network settings. Refer Harmony SCU HMI controller hardware guide (EIO0000001232) for network configuration.

Note: All IP addresses should be in the same domain.

Insulation Test
This will test the insulation monitoring system in compliance with IEC60364-7-710.
To perform insulation test, touch the icon on the top right corner.
The insulation test begins. A percentage bar is displayed with the progress.
During self test,

  1. An insulation fault is induced and the INSULATION FAULT message displays and buzzer turns ON.
  2. The induced insulation fault is recovered and the Installation Ready message displays and buzzer turns OFF.
  3. A success message displays.
    Note: Success message displays for two panels if it is configured.

Note: If error message displays, contact Schneider Electric customer care representative for support.

Message Screens

Following are the list of message screens supported:
Note: Follow the instructions displayed whenever you see these message screens.

Schneider Electric MFR40472 Vigilohm Local Remote Display - Figure 2

This screen continue to display until the system recovers from the insulation fault.

Schneider Electric MFR40472 Vigilohm Local Remote Display - Figure 4

This screen continue to display until the system recovers from the transformer overload or overheat.

Schneider Electric MFR40472 Vigilohm Local Remote Display - Figure 6

Contact Schneider Electric customer care representative for support.

Schneider Electric MFR40472 Vigilohm Local Remote Display - Figure 8

Check the underground system for any issues. This screen continue to display until the system recovers from the error.

On any message, the buzzer turns ON. Touch the LG SuperSign Q Manager - icon 1 icon to turn OFF the buzzer If multiple messages are displayed, touch and hold the Schneider Electric MFR40472 Vigilohm Local Remote Display - Icon 6 and Schneider Electric MFR40472 Vigilohm Local Remote Display - Icon 7 icons to navigate and view all the displayed messages.

Schneider Electric MFR40472 Vigilohm Local Remote Display - Figure 3

Check the connected devices for any issues. This screen continue to display until the issue is resolved.
To check the settings, touch and hold the Schneider Electric MFR40472 Vigilohm Local Remote Display - Icon 4 icon for 2 seconds and release it.

Schneider Electric MFR40472 Vigilohm Local Remote Display - Figure 5

To check the settings, touch and hold the Schneider Electric MFR40472 Vigilohm Local Remote Display - Icon 4 icon for 2 seconds and release it.
To identify the tripped channels of the connected device, touch on the Circuit Breaker Tripped message and the following screen displays:

Schneider Electric MFR40472 Vigilohm Local Remote Display - Figure 7Schneider Electric MFR40472 Vigilohm Local Remote Display - Figure 9

To check the communication settings of the highlighted devices, touch and hold the icon for 2 seconds and release it.
Schneider Electric MFR40472 Vigilohm Local Remote Display - Icon 5Note: If the existing communication error is not fixed in 1 minute, this message displays again.

Specifications

Refer the following device documentation for specifications:

DeviceCommercial ReferenceTitlePart Number
HMI ControllerHMISCU8A5Harmony SCU HMI controller quick reference guideS1B90406
Harmony SCU HMI controller hardware guideEIO0000001232
IFL12HIMDIFL12HVigilohm IFL12H instruction sheetQGH34270
Vigilohm IFL12H user manual7EN02–0407
IM20HIMD-IM20-HVigilohm IM20-H instruction sheetS1A40442
Vigilohm IM20-H user manualVIGED310023EN
SmartlinkA9XMSB11Smartlink instruction sheetS1B33423
A9XMEA08Smartlink instruction sheetNVE12086
A9XMSB11/A9XMEA08Smartlink user manualDOCA0073EN
Link150EGX150Ethernet Gateway Link150 Instruction sheetNHA50221

Notices
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it.
Electrical equipment should be installed, operated, serviced and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.
Schneider Electric is trademark or registered trademark of Schneider Electric in France, the USA and other countries.

  • This product must be installed, connected and used in compliance with prevailing standards and/or installation regulations.
  • If this product is used in a manner not specified by the manufacturer, the protection provided by the product may be impaired.
  • The safety of any system incorporating this product is the responsibility of the assembler/installer of the system.

As standards, specifications and designs change from time to time, always ask for confirmation of the information given in this publication.

Schneider Electric MFR40472 Vigilohm Local Remote Display - Qr Code

Schneider Electric LogoSchneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison,France
Phone: +33 (0) 1 41 29 70 00
www.se.com
Schneider Electric Limited
uk ca icon Stafford Park 5
Telford TF3 3BL
United Kingdom
MFR40472-03
© 2022 Schneider Electric. All rights reserved.
04/2022

References

Documents / Resouces

Download manual
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.


Related Manuals