DDNG485 RS-485-DMX512 Gateway
Product Information:
Product Name: DDNG485 RS-485/DMX512 Gateway
Installation Instructions: Devices must be installed by a qualified
electrician in accordance with all national and local electrical
and construction codes and regulations.
Dimensions:
- Length: 105 mm (4.13 in)
- Width: 95 mm (3.74 in)
- Height: 68 mm (2.68 in)
Usage Instructions:
1. Ensure that the product is installed by a qualified electrician
as per the provided installation instructions.
2. Connect the necessary cables to the gateway using the following
connections:
- SHLD GND
- D+
- D+V
- AUX
- 12V
3. Make sure to adhere to the IEC Pollution Degree II standards for
safe operation.
4. The current requirements for the gateway are as follows:
- 70 mA + (1.6 x DyNet Port 2 load current) at 12 V
- 60 mA + (0.7 x DyNet Port 2 load current) at 24 V
5. The product operates on a 12 V power supply.
6. The maximum current consumption of the product is 200 mA.
7. The product is classified as SELV/Class 2 (UL) and adheres to
IEC Overvoltage Category III standards.
8. Ensure that the product is used within an environment with a
humidity level of 90% or below.
9. For any additional connections or information, refer to the
provided user manual.
DDNG485
RS-485/DMX512 Gateway
Installation Instructions
Instructions d’installation Installationsanweisungen Instrucciones de instalación Istruzioni per l’installazione Installatie-instructies
Devices must be installed by a qualified electrician in accordance with all national and local electrical and construction codes and regulations.
Les appareils doivent être installés par un électricien diplômé conformément à tous les codes et réglementations électriques et de construction nationaux et locaux.
Die Geräte sind von einem qualifizierten Elektriker in Übereinstimmung mit allen geltenden Vorschriften zu installieren.
Los dispositivos deben ser instalados por un electricista calificado y cumpliendo todas las normas y regulaciones, tanto nacionales como locales, sobre instalaciones eléctricas y obras.
I dispositivi devono essere installati da un elettricista qualificato in conformità con le norme locali e nazionali vigenti in materia di costruzioni edilizie e installazione di impianti elettrici.
De apparaten moeten worden aangebracht door een gekwalificeerde elektricien en in overeenstemming met alle nationale en plaatselijke elektriciteits- en bouwvoorschriften.
/
.
105 mm (4.13 in) 95 mm (3.74 in) 68 mm (2.68 in)
108 mm (4.25 in)
64 mm (2.52 in)
1
2
45 mm (1.77 in)
µP
SHLD GND
D+ D+V AUX SHLD GND D+ D+ 12V
45 mm (1.77 in)
IEC Pollution Degree II
70 mA +(1.6 x DyNet Port 2 load current) @ 12 V
60 mA +(0.7 x DyNet Port 2 load current) @ 24 V
12 V
200 mA
SELV/Class 2 (UL)
IEC Overvoltage Category III
1 ¡ ¢ £¤¥¥¡ ¦§
90%
¡ ¢ £0¥¡ ¦§
SHLD GND D+ D+12 V AUX SHLD GND D+ D+12 V
3
GND AUX <20 m
Port 1
0.3-2.5mm2 22-12 AWG
0.4 Nm 3.5 Lb-in
2 A
4B
RS-485 DyNet Spur
RS-485 DyNet Spur
Port 2
2 A
4A
DDNG485
RS-485 · DyNet Spur
Port 1
RS-485 · DyNet Trunk · DMX512 · etc.
Port 2
Port 1 Port 1
Port 2 RS-485 DyNet Trunk
800m Port 2
4C
5
Port 1 To network devices
DyNet – up to 800m
Port 2
Port 1
Power supplied by controllers or DDNP150D1DNP1501
Port 2 To network devices
For cable runs over 300 m (1000 ft), or baud rates over 9600 bps, 120 , 2 W end-of-line resistors must be installed across the D+ and D- terminals on the first and last devices.
Federal Communications Commission (FCC) Compliance Notice: Radio Frequency Notice This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/TV technician for help. Any modifications not approved by the manufacturer of this device could void the user’s authority to operate this device.
This Class B digital apparatus complies with Canadian ICES-003: CAN ICES-3(B)/NMB-3(B). Cet appareil numerique de la classe B est conforme a la norme NMB003 du Canada: CAN ICES-3(B)/NMB-3(B).
Installation of a home and building automation and control system shall comply with IEC 60364 (all parts). The temperature limits and current-carrying capacities for the communication wires specified in IEC 60364-5-52 shall not be exceeded.
© 2022 Signify Holding. All rights reserved. Specifications are subject to change without notice. No representation or warranty as to the accuracy or completeness of the information included herein is given and any liability for any action in reliance thereon is disclaimed. Philips and the Philips Shield Emblem are registered trademarks of Koninklijke Philips N.V. All other trademarks are owned by Signify Holding or their respective owners.
www.dynalite.com
AZZ 411 1222 R21