SM2130B-WT using the standard RS485 bus MODBUS-RTU protocol,easy access to PLC,DCS and other instruments or systems for monitoring flooding state quantities.The internal use of high -precision sensing core and related devices to ensure high reliability and excellent long-term stability,can be customized RS232,RS485,CAN,4-20mA,DC0~5V\10V,ZIGBEE,Lora,WIFI,GPRS and other output methods

Technical Parameters

Technical parameterParameter value
BrandSONBEST
Detection CarrierWater or Rain
Output signalswitching or RS485 or RS485 & switching
Communication InterfaceRS485
Default baud rate9600 8 n 1
PowerDC9~24V 1A
Running temperature-40~80°C
Working humidity5%RH~90%RH

Communication Protocol

The product uses RS485 MODBUS MODBUS-RTU standard protocol format, all operation or reply commands are hexade cimal data. The default device address is 1 when the device is shipped, the default baud rate is 9600, 8, n, 1

Read Data (Function id 0x03)
Inquiry frame (hexadecimal), sending example: Query 1# device 1 data, the host computer sends the comman d:01 03 00 00 00 01 84 0A .

Device IDFunction idStart AddressData LengthCRC16
010300 0000 0184 0A

For the correct query frame, the device will respond with data:01 03 02 00 79 79 A6 , the response format is parsed as follows

Device IDFunction idData Length数据 1Check Code
01030200 7979 A6

Data Description: The data in the command is hexadecimal. Take data 1 as an example. 00 79 is converted to a decimal value of 121. If the data magnification is 100, the actual value is 121/100=1.21. Others and so on

AddressStart AddressDescriptionData typeValue range
4000100 001#floodingregisterRead only0~65535

Data Address Table

4010100 64model coderead/write0~65535
4010200 65total pointsread/write1~20
4010300 66Device IDread/write1~249
4010400 67baud rateread/write0~6
4010500 68moderead/write1~4
4010600 69protocolread/write1~10

read and modify device address

Read or query device address
If you don’t know the current device address and there is only one device on the bus, you ca n use the command FA 03 00 64 00 02 90 5F Query device address.

Device IDFunction idStart AddressData LengthCRC16
FA0300 6400 0290 5F

FA is 250 for the general address. When you don’t know the address, you can use 250 to get the real device address , 00 64 is the device model For the correct query command, the device will respond, for example the response data is: 01 03 02 07 12 3A 79, the format of which is as shown in the following table:

Device IDFunction idStart AddressModel CodeCRC16
01030255 3C 00 013A 79

Response should be in the data, the first byte 01 indicates that the real address of the current device is, 55 3C converted to decimal 20182 indicates that the current device main model is 21820, the last two bytes 00 01 Indicates that the device has a status quantity.

Device IDFunction idStart AddressDestinationCRC16
010600 6600 02E8 14

Change device address
For example, if the current device address is 1, we want to change to 02, the command is:01 06 00 66 00 02 E8 14 .

Device IDFunction idStart AddressData LengthCRC16
010300 6700 0135 D5

After the change is successful, the device will return information: 02 06 00 66 00 02 E8 27 , its format is parsed as shown in the following table:

Device IDFunction idData LengthRate IDCRC16
01030200 03F8 45

Change the baud rate
For example, changing the baud rate from 9600 to 38400, ie changing the code from 3 to 5, the command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15 .

Device IDFunction idStart AddressData LengthCRC16
010300 6B00 01F5 D6

For the correct query command, the device will respond, for example the response data is: 01 03 02 00 64 B9 AF, the format of which is as shown in the following table:

Device IDFunction idData LengthData valueCRC16
01030200 64B9 AF

Chang e the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take
effect immediately, at which point the device will lose its response and the baud rate of the device should
be queried accordingly. Modified.

Read Correction Value

Read Correction Value
When there is an error between the data and the reference standard, we can reduce the display error by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, that is, the value range is 0 1000 or 64535 65535. For example, when the display value is too small, we can correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If you need to reduce, you can set a negative value, such as 100, corresponding to the hexadecimal value of FF 9C, which is calculated as 100 65535=65435, and then converted to hexadecimal to 0x FF 9C. The correction value starts from 00 6B. We take the first parameter as an example. The correction value is read and modified in the same way for multiple parameters.

Device IDFunction idStart AddressDestinationCRC16
010600 6B00 64F9 FD

In the r esponse data, the first byte 01 indicates the real address of the current device, and 00 6B is the first state quantity correction value register. If the device has multiple parameters, other parameters operate in this way. The same, the general temperatur e, humidity have this parameter, the light generally does not have this item
first state quantity correction value register.

Change correction value
For example, the current state quantity is too small, we want to add 1 to its true value, and the current value plus 100 correction operation c ommand is:01 06 00 6B 00 64 F9 FD .

Device IDFunction idStart AddressDestinationCRC16
010600 6B00 64F9 FD

Disclaimer
This document provides all information about the product, does not grant any license to intellectual property, does not express or imply, and prohibits any other means of granting any intellectual property rights, such as the statement of sales terms and conditions of this product, other issues. No liability is assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use of this product, including the suitability for the specific use of the product, the marketability or the infringement liability for any patent, copyright or other intellectual property rights, etc. Product specifications and product descriptions may be modified at any time without notice.