PT-EML-R Moving Head Light
Product Information: PT-EML Series Emergency Lighting
System
The PT-EML Series Emergency Lighting System is a reliable and
efficient lighting solution for use during electrical power
failures. The system comes with LED lamps that automatically turn
on during power outages and can provide backup lighting for a
minimum of 90 minutes. The system must be tested monthly for at
least 30 seconds and annually for 90 minutes in accordance with
NFPA 101 regulations. The system must be installed by qualified
personnel and should not be used for anything other than its
intended use. It is important to read and follow all instructions
and warnings carefully to avoid any risk of death, serious injury
or significant property damage.
Installation Instructions
Before installation, it is important to turn off the power
supply from the main circuit breaker. Follow the instructions below
for proper installation:
J-Box Mounting
- Feed fixture leads through back plate and connect AC power
supply (Fig A). - Connect wires through J-Box. Mount back plate on J-Box and
secure with screws. - Connect battery only after continuous AC power can be provided
to the unit (Fig B). - Align snaps and push housing directly onto main bottom case
(Fig C). - Apply continuous AC power and press TEST button to check
light.
Conduit Mounting
- Secure back plate to wall surface. Route wires through hole in
conduit flange and make conduit connection. - Connect battery only after continuous AC power can be provided
to the unit (Fig B). - Align snaps and push housing directly onto back plate (Fig
C). - Apply continuous AC power and press TEST button to check
light.
Operation Instructions
- During an electrical power failure, the LED lamps will
automatically come on for a minimum of 90 minutes. - To test, depress the TEST switch. The emergency LED lamps will
illuminate. When the switch is released, the lamps will go
off.
Important Safety Precautions
When using the PT-EML Series Emergency Lighting System, the
following safety precautions should always be followed:
- Do not use outdoors.
- Equipment should be mounted in locations and at heights where
it will not be subject to tampering by unauthorized personnel. - Do not mount near gas or electric heaters.
- The use of accessory equipment not recommended by the
manufacturer may cause an unsafe condition. - Do not use this equipment for anything other than its intended
use. - Servicing of this equipment should be performed by qualified
personnel. - Disconnect AC power before servicing.
Warnings
Failure to follow the instructions and warnings may result in
death, serious injury or significant property damage. For your
protection, read and follow these warnings and instructions
carefully before installing or maintaining this equipment. These
instructions do not attempt to cover all installation and
maintenance situations. If you do not understand these instructions
or additional information is required, contact the
manufacturer.
Lamps are hot. Keep combustible material away from hot parts.
Observe lamp manufacturer’s warnings, recommendations, and
restrictions on lamp operation and maintenance. Make sure lamps are
correctly installed. NEVER CONNECT TO, DISCONNECT FROM, OR SERVICE
WHILE EQUIPMENT IS ENERGIZED.
INSTALLATION INSTRUCTIONS
PT-EML SERIES
(PT-EML-R)
READ THESE INSTRUCTIONS COMPLETELY AND CAREFULLY
IMPORTANT
Let the battery charge up for at least 24 hours. Then normal operation of this unit should take effect. To check, press the” TEST “button. The LED lamps on the unit should tum ON. During an electrical power failure, the led lamps will automatically come on for a minimum of 90 minutes. In accordance with NFPA 101, your emergency lighting system must be tested monthly for a minimum of 30 seconds and annually for 90 minutes. Refer lo your local codes for any additional requirements that may apply.
WARNING: FAILURE TO FOLLOW THESE INSTRUCTIONS AND WARNINGS MAY RESULT IN DEATH, SERIOUS INJURY OR SIGNIFICANT PROPERTY DAMAGE. FOR YOUR PROTECTION, READ AND FOLLOW THESE WARNINGS AND INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR MAINTAINING THIS EQUIPMENT. THESE INSTRUCTIONS DO NOT ATTEMPT TO COVER ALL INSTALLATION AND MAINTENANCE SITUATIONS. IF YOU DO NOT UNDERSTAND THESE INSTRUCTIONS OR ADDITIONAL INFORMATION IS REQUIRED, CONTACT THE MANUFACTURER.
IMPORTANT SAFEGUARDS: WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING: 1. Do not use outdoors. 2. Equipment should be mounted in locations and at heights where it will not be subject to tampering by
unauthorized personnel. 3. Do not mount near gas or electric heaters. 4. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. 5. Do not use this equipment for anything other than its intended use. 6. Servicing of this equipment should be performed by qualified personnel. 7. Disconnect AC power before servicing.
WARNING RISK OF FIRE
Lamps are hot. Keep combustible material away from hot parts. Observe lamp manufacture’s warnings, recommendations and restrictions on lamp operation and maintenance. Make sure lamps are correctly installed.
WARNING RISK OF ELECTRIC SHOCK
NEVER CONNECT TO, DISCONNECT FROM, OR SERVICE WHILE EQUIPMENT IS ENERGIZED.
INSTALLATION (ALWAYS TURN OFF THE POWER SUPPLY FROM MAIN CIRCUIT BREAKER FIRST!)
NOTE: · Unused wires must be capped using enclosed wire nuts.
FIG. A (J-Box)
INSTALLATION (J-BOX MOUNTING)
1. Feed fixture leads through back plate and connect AC power supply (Fig A). 2. Connect wires through J-Box. Mount back plate on J-Box and secure with screws. 3. Connect battery only after continuous AC power can be provided to the unit (Fig B). 4. Align snaps and push housing directly onto main bottom case (Fig C). Apply
continuous AC power and press “TEST” button to check light.
WIRING DIAGRAM
BATTERY
LAMP LAMP
FIG. B
FIG. C
INSTALLATION (CONDUIT) 1. Secure back plate to wall surface. Route wires through hole in conduit flange and make
conduit connection. 2. Connect battery only after continuous AC power can be provided to the unit (Fig B). 3. Align snaps and push housing directly onto back plat (Fig C). Apply continuous AC power
and press “TEST” button to check light.
OPERATION
1. DURING AN ELECTRICAL POWER FAILURE, THE LED LAMPS WILL AUTOMATICALLY COME ON FOR A MINIMUM OF 90 MINUTES.
2. TO TEST, DEPRESS THE “TEST” SWITCH. THE EMERGENCY LED LAMPS WILL ILLUMINATE. WHEN THE SWITCH IS RELEASED THE, LAMPS WILL GO OFF.
Yellow (+) Blue (-)
Yellow (+) Blue (-)
Red (+) Black (-) Red (120-277V) White (Comm)
“READY” LIGHT
TEST
www.portorlighting.com
NOTE: Use 18-22 AWG stranded wire to connect remote lamp heads.
Specification subject to change without notice
1/1