Ronds Rw506 Wireless Vibration Temperature Sensor User Manual

RW506 Wireless Vibration Temperature Sensor

Product Information: Product Name: Wireless Vibration
Temperature Sensor Executive Standard: GB/T 3836.1-2021, GB/T
3836.4-2021, Q/RH081–2022 Version Number: VER 1.1 Publication
Date: 2022.6 Manufacturer: Anhui Ronds Science & Technology
Incorporated Company Overview: The wireless Vibration
Temperature Sensor is designed to monitor equipment vibration
signals and transmit vibration data over a long period of time. It
has an intrinsically safe explosion-proof function and meets the
standards of GB/T 3836.1-2021 and GB/T 3836.4-2021. The sensor is
suitable for installation in normal places and dangerous places in
Zone 0 with A, B, C hazardous gases. It communicates wirelessly.
Functional Features: – Wireless transmission, eliminating
the need for extensive wiring – Transmission frequency of 2.4G with
a long transmission distance and strong anti-interference ability –
Low power design for continuous monitoring and transmission of
vibration data – Small size for easy installation in various
industrial sites – Supports temperature measurement Model
Description:
Model: RW X06X Operating Status Monitoring: Empty
– not supported, M – supported Vibration Measuring Axial: 506 – one
axial vibration, 606 – three axials vibration Wireless
Communication Company Code Application Environment
Conditions:
Working Environment Conditions: – Ambient
temperature: -40°C to +70°C – Average relative humidity: 95%HR
(+25°C) – Atmospheric pressure: 70kPa to 110kPa – Occasions without
ponding – Hazardous places in Zone 0 with IIA, IIb, and IIC
hazardous gases, but without corrosive gases damaging insulation
Bearable Storage and Transportation Conditions: – High temperature:
+85°C – Low temperature: -40°C – Average relative humidity: +95%HR
(+25°C) – Vibration: 50m/s2 – Impulse: 500m/s2 Safety Features: –
Explosion-proof type: intrinsically safe – Explosion-proof sign: Ex
ia IIC T4 Ga Working Principle and Structural Features:
Operating Voltage and Current: – Operating voltage: rated voltage
3.6V (battery options: EVE ER34615, LISUN ER34615) – Maximum open
circuit voltage: 3.9V – Operating current of the whole machine:
50mA Measurement Range: Not specified in the manual. Basic Error:
Not specified in the manual. Linearity: 2% Signal Output Way: Not
specified in the manual. Product Usage Instructions: 1.
Before using the wireless Vibration Temperature Sensor, read the
manual carefully. 2. Ensure that the sensor is installed in
accordance with the guidelines provided by Anhui Ronds Science
& Technology Incorporated Company. 3. The sensor can be
installed in normal places and dangerous places in Zone 0 with A,
B, C hazardous gases. 4. Connect the sensor to the designated power
source or battery (EVE ER34615 or LISUN ER34615) with a rated
voltage of 3.6V. 5. Make sure the operating environment conditions
are within the specified ranges: – Ambient temperature: -40°C to
+70°C – Average relative humidity: 95%HR (+25°C) – Atmospheric
pressure: 70kPa to 110kPa – No ponding in the surroundings – No
corrosive gases damaging insulation in hazardous places 6. If
storing or transporting the sensor, ensure that the conditions are
suitable: – High temperature: +85°C – Low temperature: -40°C –
Average relative humidity: +95%HR (+25°C) – Avoid excessive
vibration (50m/s2) and impulse (500m/s2). 7. The sensor
communicates wirelessly using a transmission frequency of 2.4G.
Ensure that there is no interference in the industrial field. 8.
The sensor supports temperature measurement in addition to
monitoring vibration signals.

Please read carefully before using the Manual
Wireless Vibration Temperature Sensor
Manual
Executive standard: GB/T 3836.1-2021 GB/T 3836.4-2021 Q/RH081–2022 Version number: VER 1.1 Publication date: 2022.6
Anhui Ronds Science & Technology Incorporated Company
I

Preface
This manual describes the use method and precautions of the wireless Vibration Temperature sensor. Users must read it carefully before use. The wireless Vibration Temperature sensor implements the enterprise standard Q/RH081-2022 of Anhui Ronds Science & Technology Incorporated Company.
II

Wireless Vibration Temperature Sensor

Manual

Warning:
*Read the operation manual before installation and use, and install and operate in strict accordance with the methods in the manual. *Do not modify the circuit without authorization. *The model, specification and electrical parameters of related short circuits and components shall not be modified during maintenance. *It is forbidden to replace batteries in explosion-proof places, and batteries other than those specified in the specifications shall not be replaced. *The product shell contains plastic material, which has the potential danger of electrostatic charge! Avoid friction during use! Please wipe with a damp cloth when cleaning.

Overview
1.1 Uses and Application Scope
The wireless Vibration Temperature sensor (hereinafter referred to as the sensor) can monitor the equipment vibration signal, and can monitor the vibration data for a long time and transmit it.
The sensor has intrinsically safe explosion-proof function and meets the standards of GB/T 3836.1-2021 Explosive Atmospheres Part 1: Equipment–General Requirements and GB/T 3836.4-2021 Explosive Atmospheres Part 4: Equipment Protected by Intrinsically safe “i”; The explosion-proof sign is Ex ia C T4 Ga, which can be installed in normal places and dangerous places in Zone 0 with A, B, C dangerous gases. The sensor communicates wirelessly.
1.2 Functional Features
(1) Wireless transmission. saves a lot of wiring work such as signal, power supply and network
(2) Adopt transmission frequency of 2.4G free frequency band, with long transmission distance and strong anti-interference ability, which is convenient for
3

Wireless Vibration Temperature Sensor

Manual

industrial field use (3) Low power design. Able to monitor and transmit vibration data for a long
time. (4) Small size. Suitable for installation in various industrial sites. (5) Support temperature measurement.
1.3 Model description
RW X06X

Operating Status Monitoring: Empty – not supported M – supported
Vibration Measuring Axial: 506 – one axial Vibration 606- three axials Vibration
Wireless communication Company code
The current product models are as follows: RW506: Frequency response range: Z-axis direction 2-20000Hz (±3dB ); Analysis frequency: Z axis 1000Hz10000Hz ,20000Hz; Battery life: 5 years (estimated under the condition that the temperature is 25 (± 2 ) and the conventional index is 30 minutes / time, the service life decreases under the conditions of extreme low temperature and extreme high temperature); Temperature measurement range: -40125; RW506M: RW506M has the same performance parameters as RW506W, and RW506M has working condition monitoring function.
4

Wireless Vibration Temperature Sensor

Manual

RW606: Frequency response range: Z-axis direction 0.1-20000Hz (±3dB ), X & Y-axis direction 0.1-1000Hz (±3dB ); Analysis frequency: Z axis 1000Hz, 10000Hz, 20000Hz; X & Y-axis direction 1000Hz; Battery life: 5 years (estimated under the condition that the temperature is 25 (± 2 ) and the conventional index is 30 minutes / time, the service life decreases under the conditions of extreme low temperature and extreme high temperature); Temperature measurement range: -40125; RW606M: RW606M has the same performance parameters as RW606, and RW606M has working condition monitoring function.

1.4 Application Environment Conditions
1.4.1 Working Environment Conditions
a) Ambient temperature: -40+70; b) Average relative humidity: 95%HR (+25 ); c) Atmospheric pressure: 70kPa110kPa; d) Occasions without ponding; e) Zone 0 hazardous places with IIA, IIb and IIC hazardous gases, but without
corrosive gases damaging insulation.
1.4.2 Bearable Storage and Transportation Conditions
a) High temperature: +85; b) Low temperature: -40; c) Average relative humidity: +95%HR (+25 ); d) Vibration: 50m/s2; e) Impulse: 500m/s2
1.5 Safety Features
Explosion proof type: intrinsically safe, explosion-proof sign: Ex ia IIC T4 Ga

5

Wireless Vibration Temperature Sensor

Manual

2 Working Principle and Structural Features
2.1 Operating Voltage and Current
a) Operating voltage: rated voltage 3.6V (battery is one of the following three models)
EVE ER34615 Maximum open circuit voltage 3.9V; LISUN ER34615 Maximum open circuit voltage 3.9V; b) Operating current of the whole machine: 50mA
2.2 Measurement Range
vibration acceleration (Z-axis direction) measurement range: ±50g; (ggravitational acceleration g=9.8m/s2) vibration acceleration (X & Y-axis direction) measurement range: ±16g (ggravitational acceleration g=9.8m/s2) Resolution ratio is 0.01m/s2; Temperature measurement range: -40125
2.3 Basic Error
Allowable basic error of vibration measurement:±3dB;
2.4 Linearity
Linearity: 2%;
2.5 Signal Output Way
12.4G (IEEE 802.15.4 )Wireless communication: (1)Frequency: 2405MHz2475MHz (2)Transmission distance: 300 meters line of sight. 2BLE Wireless communication: (1)Frequency: 2402MHz2480MHz (2)Transmission distance: 50 meters line of sight.

6

Wireless Vibration Temperature Sensor

Manual

2.6 IP Grade:IP68 (1m, 40min)
3. Dimensions, Weight and Material
3.1 Dimensions: 45.5*110.3mm (diameter × Height, including mounting base );
3.2 Weight: About 320g (including mounting base); 3.3 Upper cover material: flame retardant PC; Battery compartment material: flame retardant PA66 + 30% glass fiber + SUS304
(integrated injection molding); Base and mounting base material: SUS316 stainless steel.
4. Installation and Operation Notices
(1)Please read the operation manual carefully before using this product. (2)This product should be used and maintained by trained personnel or special
personnel. (3)Avoid knocking, falling, being close to high temperature source for a long
time and being used in high corrosion environment for a long time. (4)Install the sensor correctly to ensure the sensitivity of the sensor and the
accuracy of the measured data. (5)It is not allowed to replace the original device or structure to avoid affecting
the explosion-proof performance. (6)Only use the following brands of specified models of batteries:
EVE ER34615, 3.6V 19Ah Lithium Thionyl Chloride (LiSOCI2) LISUN ER34615, 3.6V 19Ah Lithium Thionyl Chloride (LiSOCI2) (7)The upper cover of the product and the shell of the battery compartment are made of flame retardant PA66 + 30% glass fiber + SUS304 (integrated injection molding), which has potential electrostatic hazards. Avoid friction during use! Please wipe with a damp cloth when cleaning.
5. Installation and Use
5.1 Production Date and Certificate Validity

7

Wireless Vibration Temperature Sensor

Manual

a) Production date: see “product delivery inspection report” for details; b) Certificate validity: see “explosion proof certificate” for details.
5.2 Installation Methods
Magnetic base + gluing, adapter base + screw hole, adapter base + welding Note: If the vibration amplitude of equipment is large, it is recommended to adopt the installation method of adapter + screw hole or adapter + welding.
5.3 Use Methods
a) Configure by using the supporting dongle. b) Set the same wireless band with matched gateway. c) When replacing the battery, it must be carried out in strict accordance with the relevant requirements of “repair and maintenance” in Article 4.
6. Repair and Maintenance
6.1 Repair
1) Please read the manual carefully before use and follow the operating steps. 2) Do not change any parameters of the sensor circuit. 3) Only use the battery model described in Article 4. 4) Battery replacement shall be carried out in a safe place.
6.2 Maintenance
6.2.1 A designated person must be responsible for the daily maintenance of the sensor. 6.2.2 Maintenance personnel must carefully read and be familiar with Wireless Vibration Temperature Sensor Manual and relevant circuit diagrams, and be familiar with the internal and external structure and circuit principle of the sensor. 6.2.3 The maintenance personnel should always check whether the sealing part of the sensor is compressed and whether the cover plate screws are fastened.
7. Common Fault Treatment
1)If the data cannot be uploaded, first check whether the battery is powered. If not, please replace the battery. 2)If the data is not uploaded in time, first check the wireless signal quality at the
8

Wireless Vibration Temperature Sensor

Manual

installation position to ensure that there is no shielding equipment around.

8. Transportation and Storage

8.1 Avoid violent vibration and impact when transporting and handling the sensor. 8.2 Strictly prohibited to put the sensor in the place directly dripping with water when store it.

9. Unpacking and Inspection

9.1 Pay attention to safety when unpacking to avoid damage to equipment or

injury.

9.2 After unpacking, check whether the appearance of the equipment is damaged

and whether the accessories are complete.

9.3 Accessories list

a) Instruction Manual

1 pcs

b) Sensor

1 pcs

c) Product certificate

1 pcs

d) Packing list

1 pcs

Manufacturer: Anhui Ronds Science & Technology Incorporated Company Address: #59, Branch Road of Biomedical park, High-tech district, Hefei, Anhui, China

FCC Statement
FCC ID2AKW5-RW506 Please take attention that changes or modification not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20cm between the radiator & your body.