OUELLET RFG-P003 120V Preassembled Heating

MODELS
| Product #1 | Length | Watts | |
| ft. | m | ||
| RFG-P003 | 3 | 0.9 | 21 |
| RFG-P006 | 6 | 1.8 | 42 |
| RFG-P009 | 9 | 2.7 | 63 |
| RFG-P012 | 12 | 3.7 | 84 |
| RFG-P015 | 15 | 4.6 | 105 |
| RFG-P018 | 18 | 5.5 | 126 |
| RFG-P024 | 24 | 7.3 | 168 |
| RFG-P030 | 30 | 9.0 | 210 |
| RFG-P040 | 40 | 12.2 | 280 |
| RFG-P060 | 60 | 18.3 | 420 |
| RFG-P080 | 80 | 24.4 | 560 |
Must be plugged into a 120V outlet fitted with ground fault protection device (GFCI).
OPTIONS
| Product # | Description |
| ELB-02B | Self-adhesive glass fiber tape, max. temp. = 90 °C (194 °F), 50 m (165 ft.) |
| ELB-06C | Self-adhesive aluminum tape, max. temp. = 80 °C (176 °F), 50 m (165 ft.) |
WARRANTY
1-year on the heating cable
FEATURES
INSTALLATION
- Designed for indoor and outdoor use, 120V preassembled heating cables for pipe freeze protection help to prevent damage from winter weather.
- Approved for residential, commercial and industrial installations, it must be plugged into a 120V outlet fitted with a ground fault circuit interrupter (GFCI). The cable allows for moderate bends (minimum bend radius of 5/16 in. (8 mm)).
- For optimal performance, the cable must be installed flat on a metallic or non-metallic pipe and covered with insulation no more than 1/2 in. thick (13 mm).

PEACE OF MIND
- The cable is fitted with a built-in bimetallic thermostat that activates the cable when the temperature falls below 4 °C (40 °F) and a grounded 3-pronged plug with an indi-cator light to show when the cable is powered on.

- Once the cable has been installed and powered on, no further action is required throughout the winter season!
Cable Mounting