606 Insulation Tester and Multimeter
606
User Manual / /
YEARS
LIMITED WARRANTY
EN Insulation Tester & Multimeter TC SC JP RU
606
EN
Introduction
This Insulation Tester is an accurate, professional industry tool for measuring ACV, DCV, Frequency, Low Pass Filter, EarthBond Resistance, Capacitor, Insulation Resistance.
Safety Information
Understand and follow operating instructions carefully.
WARNING
· If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
· Always use proper terminals, switch position, and range for measurements.
· To reduce the risk of fire or electric shock, do not use this product around explosive gas or in damp locations.
· Verify the Meter operation by measuring a known voltage. If in doubt, have the Meter serviced.
· Do not apply more than the rated voltage, as marked on Meter, between terminals or between any terminal and earth ground.
· To avoid false readings that can lead to electric shock and injury, replace battery as soon as low battery indicator blinks / appears.
· Avoid working alone so that assistance can be rendered. · Do not use the Tester if the Tester is not operating properly or
if it is wet. · Individual protective device must be used if hazardous live
parts in the installation where the measurement is to be carried out could be accessible. · Disconnect the test leads from the test points before changing the position of the function rotary switch. · Never connect a source of voltage when the function rotary switch is not in voltage position.
1
606
EN
· When using test leads or probes, keep your fingers behind the finger guards.
· Use caution with voltages above 30Vac rms, 42 Vac peak, or 60Vdc. These voltages pose a shock hazard.
· Remove test lead from Meter before opening the battery door or Meter case.
· DO NOT USE the test leads when the internal white insulation layer is exposed.
· DO NOT USE the test leads above maximum ratings of CAT. Environment, voltage and current, that are indicated on the probe and the probe tip guard cap.
· DO NOT USE the test leads without the probe tip guard cap in CAT III and CAT IV environments.
· Probe assemblies to be used for MAINS measurements shall be RATED as appropriate for MEASUREMENT CATEGORY III OR IV according to IEC 61010-031 and shall have a voltage RATING of at least the voltage of the circuit to be measured.
· Only replace the blown fuse with the proper rating as specified in this manual.
· Do not attempt a resistance measurement when the open voltage is above the fuse protection rating. Suspected open voltage can be checked with voltage function.
· Never attempt a voltage measurement with the test lead inserted into the input terminal.
· Disconnect circuit power and discharge all high-voltage capacitors before testing resistance, continuity, or capacitance.
2
606
EN
Symbols as marked on the Meter and Instruction manual
Risk of electric shock See instruction manual DC measurement Equipment protected by double or reinforced insulation Battery Fuse Earth AC measurement Bluetooth Conforms to EU directives Do not discard this product or throw away. Both direct and alternating current This product CONFORMS TO UL STD 61010-1, 61010-2-034
Unsafe Voltage
To alert you to the presence of a potentially hazardous voltage, when the Tester detects a voltage 30 V in insulation test, or a voltage overload (OL), the ” ” symbol is displayed and High voltage indicator is turned on.
Maintenance
Do not attempt to repair this Meter. It contains no user service able parts. Repair or servicing should only be performed by qualified personnel.
Cleaning
Periodically wipe the case with a dry cloth and detergent. Do not use abrasives or solvents.
3
606
EN
The Meter Description
Front Panel Illustration
m L nk 0
1M 10M 100M LOCK TEST
AutoSense
APO
1GK 10GK MEM
A
6100GK
RENPIDAR COMPARE
MGK HzV LPF
R
VAC S DC 0
MGK
m FA
SETUP
5 Sec Del Last
RECALL PI/DAR/t PASS
TEST
LPF
V OFF
TRUE RMS
V >660V INSULATION COM
315mA FUSED
CAT IV 600V
Display
Function button
Pass indicator
High Voltage indicator Funtions & Power On/Off Input
V insulation Input
Common Input
4
606
EN
Measuring ACV/DCV : Auto sense function
0
AutoSense
6 00
Hz
VAC
0
AutoSense
6 00
VDC
30V
LPF
LPF
V
V
V
INSULATION
COM
Auto sense mode: The meter displays ACV or DCV whichever is higher (>1V). If the measured voltage is above 660Vac/dc, “> 660Vac/dc” will appear on the display.
5
606
EN
WARNING
When connecting the test leads to the DUT (Device Under Test) connect the common test leads before connecting the live leads; When removing the test leads, remove the test live leads before removing the common test leads. Don’t apply more than AC/DC 600V between the V-COM terminals.
Measuring Capacitance
F
COMP STORE LOCK
V
INSULATION
COM
6
606
EN
Wireless Link
L nk
L nk
L nk
The meter uses Bluetooth low energy (BLE) V5.0 wireless technology to download the stored data. The open-air communication range is up to 6m. Download “APPA Connect” App via the following QR Code. Turn on LINK function of the meter and open “APPA Connect” to connect the DMM. The LINK icon of the meter will freeze on LCD after the connection establishes successfully.
APPA Connect on Google Play
APPA Connect on iTune Store
7
606
EN
Switch Auto Voltage sense/ACV/DCV/LPF function when the rotary switch is in voltage position
0
AutoSense
6 00
Hz
VAC
SETUP
Press
0
6 00
Hz
VAC
SETUP
Press
Press>2Sec
SETUP
0
6 00
VDC
SETUP
Press
0
6 00
LPF
VAC
SETUP
Press
WARNING
Do not use the High Frequency Rejection (Low Pass Filter) to verify the presence of hazardous voltages. Voltages greater than what is indicated may be present. First, make a voltage measurement without the filter to detect the possible presence of hazardous voltage. Then select the filter function.
8
606
EN
Measuring Earth-Bond Resistance (Continuity)
0
1
10
100
1 K
mA 10 K 100 K
R
Press
TEST
&
hold
0
1
10
100 TEST
1 K
mA 10 K 100 K
R
0
0
COM
1. Before starting the test : (a) The circuit under test must be completely de-energized. (b) Check the fuse is good. See the chapter “Testing the fuse”. (c) Short the test leads before measurement, and press the Function button to zero the wire resistance of probe. If the wire resistance is <10, the resistance offset value will be saved, and the “->0<-” symbol will be displayed on LCD.
9
606
EN
2. Lock mode : Press the Lock button to enter the Lock Mode. Then press the TEST button to start the test. The test voltage will continue to be applied until the TEST/LOCK button is pressed again. 3. The meter displays the ” ” symbol and the maximum resistance for the range when measured resistance is higher than the maximum display range.
Measuring Insulation Resistance
0
1M
10M 100M 1G
10G 100G
V
G
Press>1Sec
TEST
0
1M
10M 100M 1G TEST
10G 100G
V
M
TEST
=
500V
V
INSULATION
COM
500V
10
606
EN
1. Before starting the test : The circuit under test must be completely de-energized. If the voltage detected is above 30V, “>30V” will appear on the display. In this condition, the test is inhibited.
2. Press the Function button to display insulation resistance or Leakage current during the test or when the test stops.
3. Lock mode: Press the Lock button to enter the Lock Mode. Then press TEST button >1sec to start the test. The test voltage will continue to be applied until the TEST/LOCK button is pressed again.
4. Stop the output test voltage before removing the test leads (to enable the tester to discharge capacitive circuits). If the screen displays volts, wait until it reaches zero.
5. The meter displays the ” ” symbol and the maximum resistance for the range when measured resistance is higher than the maximum display range.
Using the Compare function
0
1M
10M 100M 1G
10G 100G
V
Press
0
1M
10M 100M 1G
10G 100G
COMPARE
M
Before starting the Insulation Resistance test, select the comparative value in Setup mode: 0.5M, 10M, 20M, 50M, 100M, 200M, 500M, 1000M.
Before starting the Earth-Bond Resistance test, select the comparative value in Setup mode: 0.5, 1, 2, 3, 4, 5, 10, 20, 30, 40.
11
606
EN
If the measured value is better than the selected compare value, the Pass indicator will be green, otherwise it is red.
Measuring PI/DAR/Timer
0
1M
10M 100M 1G
10G 100G
V
G
Press>2Sec
LOCK
PI/DAR/t
1M 0
PI
10M 100M 1G
10G 100G
G
Press
LOCK
PI/DAR/t
1M 10M 100M 1G 0
DAR
10G 100G
G
Press
LOCK
PI/DAR/t
0
1M
10M 100M 1G
10G 100G
G
Press
LOCK
PI/DAR/t
Press>2Sec
LOCK
PI/DAR/t
Press TEST button to start/interrupt the PI/DAR test. Press Function button during the PI/DAR test to switch display the output voltage / leakage current / the time left of the test.
12
606
EN
PI(Polarization Index)=R10-min/R1-min DAR(Dielectric Absorption Rations)=R1-min/(R30-sec or R15-sec) Timer : Countdown timer
R10-min : the insulation resistance measured at the 10 minute after pressing the TEST button. R1-min : the insulation resistance measured at the 1 minute after pressing the TEST button. R30-sec : the insulation resistance measured at the 30 seconds after pressing the TEST button. R15-sec : the insulation resistance measured at the 15 second after pressing the TEST button.
NOTE: R30-sec or R15-sec can be set in setup mode NOTE: Countdown time interval can be set in setup mode
If the reading for DAR is bigger than 1.3 or PI is bigger than 2, it indicate a good insulation quality. When the measured resistance is higher than the maximum range, the screen will display “Err” symbol for PI/DAR value.
13
606
EN
Show the measured values after the PI test is completed
PI=R10-min/R1-min
1M 0
PI
10M 100M 1G
10G 100G
Press
1M 0
PI
10M 100M 1G
10G 100G
R1-min
M
SETUP
Press
Press
1M 0
PI
10M 100M 1G
10G 100G
R10-min
M
Show the measured values after the DAR test is completed
DAR=R1-min/R30-sec
1M 10M 100M 1G 0
DARD
10G 100G
Press
0
1M
10M 100M 1G
10G 100G
AR
R30-sec
M
SETUP
Press
Press
10M 100M 1G 1M 0
DAR
10G 100G
R1-min
M
14
606
EN
Show the measured values after the countdown timer test is completed
0
1M
10M 100M 1G
APO
10G 100G
Press
M
0
1M
10M 100M 1G
APO
10G 100G
V
M
SETUP
Press
Press
0
1M
10M 100M 1G
APO A 10G 100G
M
Using the Store function
Store/Recall button : 1. Press Store/Recall button to store the test result. The screen
will show MEM symbol and the number of stored data when the Store/Recall button is pressed. 2. In PI / DAR mode, Insulation, and Earth-bond resistance, Store / Recall button is only available when the individual test is completed. 3. Up to 1500 recordings / recording sets of each function (Voltage, Continuity, Capacitance, Insulation, PI, DAR). 4. In Insulation, PI / DAR mode, the meter saves 3 different readings at the same time (Recording Set).
15
606
EN
Mode
Insulation
PI mode
DAR mode Earth-bond Resistance
Voltage Capacitance
Recording Set
Output Voltage Leakage Current
PI value DAR value Resistance
R1-min
R30-Sec or R15-Sec
Voltage Capacitance
Insulation Resistance
R10-min
R1-min
Delete the last one recording set in the mode
0
1M
10M 100M 1G
10G 100G
V
G
Press>5Sec until the LCD shows dEL
5 Sec Del Last
MEM
MEM
M
16
606
EN
Using the Recall function
Press the Store/Recall button 2 sec to enter/exit the RECALL mode. If the memory is empty, the meter will display the “nOnE ” symbol.
Search the stored value under RECALL mode
MEM
M
Press
SETUP
Press
MEM
M
MEM
M
17
606
EN
Read the stored value of insulation test under RECALL mode
In RECALL mode, press STORE button can show the insulation resistance, test voltage, and leakage current of the selected reading set.
0
1M
10M 100M 1G
APO
10G 100G
V
M
Press>2Sec
Insulation Resistance
RECALL MEM
Leakage Current
M
Press
RECALL
MEM
VDC
Press
RECALL
MEM
Press>2Sec
RECALL
Test Voltage
A
Press
RECALL
18
606
EN
Read the stored value of PI test under RECALL mode
In RECALL mode, press STORE button can show insulation resistance of the selected reading set.
MEM Press
PI
PI
RECALL
PI
Press
MEM
R1-min
M
Press
MEM
M
R10-min
Read the stored value of DAR test under RECALL mode
In RECALL mode, press STORE button can show insulation resistance of the selected reading set.
MEM Press
RECALL
Press
MEM
M
R15-Sec or
R30-Sec
Press
MEM
M
R1-min
19
606
EN
Auto Power Off (Battery Saver)
APO
APO
VAC
30min
LPF V
OFF
OFF
Restore power by switching rotator or by pressing any button.
Auto Backlight
The backlight is automatically turned on at dark environment.
Power-up options :
Press the following button while turning meter on from OFF position. Test button : display of the software version. Store button : Reset all stored data Lock button : Show the full display of the LCD Function button : Enter Setup Mode
20
606
EN
Setup Mode
Function
Options
Default
Automatic Backlight
On, Off
On
Continuity short current
20mA, 200mA
200mA
Pass threshold of Insulation Resistance
0.5, 10, 20, 50, 100, 200, 500, 1000M
100M
Pass threshold of Earth-bond Continuity
0.5, 1, 2, 3, 4, 5, 10, 20, 30, 40
2
Direction of Continuity
Single, Bi-directional Single
DAR Timer Count-down Timer APO Timer
15, 30s
1 minute to 40 minutes
Off, 10, 20, 30, 40, 50, 60 minutes
30s 1 minute 30 minutes
Delete All Recording Of Earthbond Continuity
Yes, No
No
Delete All Recording Of Insulation Resistor
Yes, No
No
Delete All Recording Of Voltage Yes, No
No
Delete All Recording Of Capacitance
Yes, No
No
Delete All Recording Of PI
Yes, No
No
Delete All Recording Of DAR Yes, No
No
Reset
Yes, No
No
1. Press the Test button to select the function to be adjusted. 2. Press the Function button and Comp button to adjust the
options. 3. Press the Lock button to record the option.
21
606
EN
Battery and Fuse Replacement
Refer to the following figure to replace fuse and the batteries :
2
3
1
Caution
· Use only a fuse with the amperage, interrupt, voltage, and speed rating specified.
· Fuse rating : Fast, 315mA, 1000V, at least 10kA Interrupt Rating.
· Replace battery as soon as low battery indicator blinks / appears to avoid false reading.
· When the battery is too low for reliable operation , the meter displays ” bAtt “. The meter will not operate at all until the battery is replaced.
· 1.5V x 4 alkaline batteries. 22
606
Testing the fuse
TEST
TEST
0
EN
TEST
· Remove the test leads before testing the fuse. · If the display reading is FUSE, the fuse is bad and should be
replaced.
23
606
EN
Specifications
General Specifications Display Count : 4000 counts. Overrange display : ” >OL Reading ” or ” >-OL Reading ” Conversion Rate : 2 times / second Dimensions (W x H x D) : 96mm x207mm x 54mm with holster Weight : 630g including battery. Power requirement : AA size ALKALINE Battery * 4 Batteries Life : 1.5 AA ALKALINE battery
Resistance Measurements : Tester can perform at least 2600 earth-bond resistance measurements with new alkaline batteries at room temperature. These are standard tests of 1 with a duty cycle of 5 seconds on and 25 seconds off.
Insulation test: Tester can perform at least 1100 insulation tests with new alkaline batteries at room temperature. These are standard tests of 1 M at 1000 V with a duty cycle of 5 seconds on and 25 seconds off.
Installation Category : IEC/EN 61010-1, IEC/EN 61010-2-034 Compliance to EN 61557 : IEC/EN 61557-2:2019
IEC/EN 61557-4:2019 EMC : EN 61326-1
CAT II
Application field
It is applicable to test and measuring circuits connected directly to utilization points (socket outlets and similar points) of the low-voltage MAINS installation.
It is applicable to test and measuring circuits connected III to the distribution part of the building’s low-voltage MAINS
installation.
IV
It is applicable to test and measuring circuits connected at the source of the building’s low-voltage MAINS installation
24
606
EN
Environmental Conditions
Indoor Use Pollution degree : 2 Operating altitude : 2000m (6562ft) Operating temperature : Non-condensing <5°C,
5°C ~ 30°C ( 80% RH), 30°C ~ 40°C ( 75% RH), 40°C ~ 50°C ( 45%RH) Storage temperature : -20°C to 60°C , 0 to 80% R.H. (batteries not fitted) Temperature Coefficient : 0.15 x (Specified accuracy) /°C, < 20°C or > 26°C . IP Rating : IP40 Shock vibration : Random Vibration per MIL-PRFF Class 2 Drop Protection : 4 feet drop to hardwood on concrete floor.
Electrical Specifications
Accuracy is given as ±(% of reading + counts of least significant digit) at 23°C ± 3°C, with relative humidity Less than 70% R.H., and is specified for 1 year after calibration.
ACV Function · ACV and ACA specifications are ac coupled, true RMS. · For square wave, accuracy is unspecified. · For non-sinusoidal waveforms, Additional Accuracy by Crest
Factor (C.F.): Add 1.0% for C.F. 1.0 to 2.0 Add 2.5% for C.F. 2.0 to 2.5 Add 4.0% for C.F. 2.5 to 3.0
· Max. Crest Factor of Input Signal: 3.0 @ 3000 counts 2.0 @ 4500 counts 1.5 @ 6000 counts
· Frequency Response is specified for sine waveform.
25
606
EN
AC Voltage
Range 600.0V
OL Reading Resolution
Accuracy
660.0V
0.1V
±(1.5%+5D)(50~60Hz) ±(2.0%+5D)(61~400Hz)
Input Impedance: 10M// less than 100pF Frequency Response: 50Hz to 400Hz Overload Protection: AC/DC 600V
DC Voltage
Range 600.0V
OL Reading Resolution
660.0V
0.1V
Input Impedance: 10M Overload Protection: AC/DC 600V
Accuracy ±(1.0%+5D)
Frequency
Range 100.0Hz 1000Hz
OL Reading Resolution
100.0Hz
0.1Hz
1100Hz
1Hz
ACV Minimum Sensitivity: > 60V Minimum Frequency: 10Hz Overload Protection: AC/DC 600V
Accuracy ±(1.0%+3D)
Low Pass Filter Available for ACV Add ±4% to specified accuracy @ 50 to 60Hz Accuracy is specified for 50 to 60Hz Cut- off Frequency(-3dB): 1kHz Overload Protection: AC/DC 600V
26
606
Capacitor
Range 100.0nF 1000nF 10.00uF
OL Reading Resolution
100.0nF
0.1nF
1000nF
1nF
11.00uF
0.01uF
Overload Protection: AC/DC 600V
EN
Accuracy ±(3.0%+10D) ±(3.0%+5D)
Earth-bond Resistance (Continuity)
Range 40.00 400.0 4.000k 40.00k
OL Reading Resolution
40.00
0.01
400.0
0.1
4.000k
0.001k
44.00k
0.01k
Accuracy ±(1.5%+5D)*
±(1.5%+3D)
* <1.00 add 3dgt * output current mode in 20mA add 10dgt * Automatic bi-directional test mode add 0.5%+5D Output Current: >200mA @ <2 or >20mA@ <2 Output Voltage: >4V
Insulation Resistance
Range 400.0k 4.000M 40.00M 400.0M 4.000G 40.0G 200G
OL Reading Resolution
400.0k
0.1k
4.000M 0.001M
40.00M
0.01M
400.0M
0.1M
4.000G
0.001G
40.0G
0.1G
220G
1G
Accuracy* ±(2.5%+5D) ±(20%+3D)
27
606
EN
* Above specifications only apply when high quality silicone leads with test clips are being used with no hands touch. Test Voltage vs. Maximum resistance range: 50V/10.0G, 100V/20.0G, 250V/40.0G, 500V/100G, 1000V/200G Test Voltage vs. Minimum resistance range: 50V/50.0k, 100V/100.0k, 250V/250.0k, 500V/0.500M, 1000V/1.000M Short Circuit Test Current: <2mA, +0%, -50% Test Voltage Accuracy: -0%, +2%+2V Auto discharge function: discharge time <1 sec for C 1uF Maximum Capacitive load: Operable with up to 1uF load Live Circuit Detection: if 30V ac/dc at inputs, test inhibited
28
606
EN
Limited Warranty This meter is warranted to the original purchaser against defects in material and workmanship for 3 years from the date of purchase. During this warranty period, Manufacturer will, at its option, replace or repair the defective unit, subject to verification of the defect or malfunction. This warranty does not cover fuses, disposable batteries, or damage from abuse, neglect, accident, unauthorized repair, alteration, contamination, or abnormal conditions of operation or handling. Any implied warranties arising out of the sale of this product, including but not limited to implied warranties of merchantability and fitness for a particular purpose, are limited to the above. The manufacturer shall not be liable for loss of use of the instrument or other incidental or consequential damages, expenses, or economic loss, or for any claim or claims for such damage, expense or economic loss. Some states or countries laws vary, so the above limitations or exclusions may not apply to you.
29
606
TC
ACV DCV
·
· ·
·
·
·
· · ·
·
· · · 30Vac rms 42 Vac 60 Vdc
· · · CAT
·CAT III CAT IV
30
606
TC
· IEC 61010-031
· · · ·
DC AC UL STD 61010-1 61010-2-034
30 V (OL)
31
606
TC
m L nk 0
1M 10M 100M LOCK TEST
AutoSense
APO
1GK 10GK MEM
A
6100GK
RENPIDAR COMPARE
MGK HzV LPF
R
VAC S DC 0
MGK
m FA
SETUP
5 Sec Del Last
RECALL PI/DAR/t PASS
TEST
LPF
V OFF
TRUE RMS
V >660V INSULATION COM
315mA FUSED
CAT IV 600V
32
V
606
TC
ACV DCV
0
AutoSense
6 00
Hz
VAC
0
AutoSense
6 00
VDC
30V
LPF
LPF
V
V
V
INSULATION
COM
ACV DCV>1V 660Vac/dc> 660Vac/dc
33
606
TC
DUT V-COM AC/DC 600V
F
COMP STORE LOCK
V
INSULATION
COM
34
606
TC
L nk
L nk
L nk
(BLE) V5.0 6m QR APPA Connect APPA Connect DMM LCD
Google Play APPA Connect
iTune Store APPA Connect
35
606
TC
ACV DCV LPF
0
AutoSense
6 00
Hz
VAC
SETUP
Press
0
6 00
Hz
VAC
SETUP
Press
0
6 00
VDC
SETUP
Press
0
6 00
LPF
VAC
SETUP
Press
Press>2Sec2
SETUP
36
606
TC
0
1
10
100
1 K
mA 10 K 100 K
R
Press &
TEST
hold
0
1
10
100 TEST
1 K
mA 10 K 100 K
R
0
0
COM
1. (a) (b) (c) <10 LCD ->0<-
37
606
TC
2. 3.
0
1M
10M 100M 1G
10G 100G
V
G
Press>1S1ec
TEST
0
1M
10M 100M 1G TEST
10G 100G
V
M
TEST
=
500V
V
INSULATION
COM
500V
38
606
TC
1. 30V>30V
2.
3. 1
4.
5.
0
1M
10M 100M 1G
10G 100G
V
Press
0
1M
10M 100M 1G
10G 100G
COMPARE
M
0.5M 10M20M50M100M200M500M 1000M
0.5 1234510203040
39
606
TC
Pass
PI DAR
0
1M
10M 100M 1G
10G 100G
V
G
Press>22Sec
LOCK
PI/DAR/t
1M 0
PI
10M 100M 1G
10G 100G
G
Press
LOCK
PI/DAR/t
1M 10M 100M 1G 0
DAR
10G 100G
G
Press
LOCK
PI/DAR/t
0
1M
10M 100M 1G
10G 100G
G
Press
LOCK
PI/DAR/t
Press>2S2ec
LOCK
PI/DAR/t
PI DAR PI DAR
40
606
TC
PI R10-min R1-min DAR R1-min R30-sec R15-sec
R10-min 10 R1-min 1 R30-sec 30 R15-sec 15
R30-sec R15-sec
DAR 1.3 PI 2 PI DAR Err
PI
PI R10-min R1-min
1M 0
PI
10M 100M 1G
10G 100G
Press
1M 0
PI
10M 100M 1G
10G 100G
R1-min
M
SETUP
Press
Press
1M 0
PI
10M 100M 1G
10G 100G
R10-min
M
41
606
TC
DAR
DAR R1-min R30-sec
1M 10M 100M 1G 0
DARD
10G 100G
Press
0
1M
10M 100M 1G
10G 100G
AR
R30-sec
M
SETUP
Press
Press
1M 10M 100M 1G 0
DAR
10G 100G
R1-min
M
0
Press 1M
10M 100M 1G
APO
10G 100G
M
0
1M
10M 100M 1G
APO
10G 100G
V
M
SETUP
Press
Press
0
1M
10M 100M 1G
APO A 10G 100G
M
42
606
TC
1.
MEM 2. PI DAR
3. 1500
PIDAR 4. PI DAR 3
PI DAR
PI DAR
R1-min R30-Sec
R15-Sec
R10-min R1-min
1M 10M 100M 1G 10G
0
100G
V
G
Press>55Sec until thLCeDLCDshdoEwL sdEL
5 S5 ec Del Last
MEM
MEM
M
43
606
TC
2 nOnE
MEM
Press
SETUP
MEM
M
M Press
MEM
M
44
606
TC
0
1M
10M 100M 1G
APO
10G 100G
V
M
Press>2S2ec
Insulation Resistance
RECALL
MEM
Leakage Current
M
Press
RECALL
MEM
VDC
Press
RECALL
MEM
Press>2S2ec
RECALL
TVeoslttage
A
Press
RECALL
45
606
TC
PI
MEM Press
PI
PI
RECALL
PI
Press
MEM
R1-min
M
Press
MEM
R10-min
M
DAR
MEM Press
RECALL
Press
MEM
M
R15-Sec or
R30-Sec
Press
MEM
M
R1-min
46
606
TC
APO
APO
VAC
30min
LPF V
OFF
OFF
(OFF) LCD
47
606
TC
DAR APO
20mA200mA
200mA
0.5102050 100200500 1000M
100M
0.512345 10203040
2
1530
30
1 40
1
102030 405060
30
PI
DAR
1. 2. Comp 3.
48
606
TC
2
3
1
·
·315mA1000V 10kA
· · bAtt
·1.5V x 4
49
606
TEST
TEST
0
TC
TEST
· · FUSE
50
606
TC
4000 >OL >-OL 2 x x 96mm x 207 mm x 54mm 630g 4 AA 1.5 AA
2600 1 5 25
1100 1000 V 1M 5 25
IEC/EN 61010-1IEC/EN 61010-2-034 EN 61557 IEC/EN 61557-2:2019
IEC/EN 61557-4:2019 EMCEN 61326-1
CAT
II
III
IV
51
606
TC
2 2000m (6562ft) <5
5 ~ 30 ( 80% RH) 30 ~ 40 ( 75% RH) 40 ~ 50 ( 45%RH) -20 600 80% R.H. 0.15 x/< 20 > 26 IP IP40 MIL-PRFF 2 4
23° C ± 3° C 70% R.H. ±(% + )
ACV ·ACV ACA · · (C.F.)
C.F. 1.0 ~ 2.0 1.0% C.F. 2.0 ~ 2.5 2.5% C.F. 2.5 ~ 3.0 4.0% · 3000 3.0
4500 2.0 6000 1.5 ·
52
606
AC
OL
600.0V
660.0V
0.1V
10M // 100pF 50Hz 400Hz AC/DC 600V
DC
600.0V
OL 660.0V
10M AC/DC 600V
0.1V
TC
±(1.5%+5 )
(50~60Hz) ±(2.0%+5 )
(61~400Hz)
±(1.0%+5 )
100.0Hz 1000Hz
OL 100.0Hz 1100Hz
ACV > 60V 10Hz AC/DC 600V
0.1Hz 1Hz
±(1.0%+3 )
ACV 50 60Hz ±4% 50 60Hz (-3dB)1kHz AC/DC 600V
53
606
100.0nF 1000nF 10.00uF
OL 100.0nF 1000nF 11.00uF
AC/DC 600V
0.1nF 1nF 0.01uF
TC
±(3.0%+10 ) ±(3.0%+5 )
40.00 400.0 4.000k 40.00k
OL 40.00 400.0 4.000k 44.00k
0.01 0.1 0.001k 0.01k
±(1.5%+5 )*
±(1.5%+3 )
*<1.00 + 3 * 20mA 10 * 0.5%+5 >200mA @ <2 >20mA@ <2 >4V
400.0k 4.000M 40.00M 400.0M 4.000G 40.0G 200G
OL 400.0k 4.000M 40.00M 400.0M 4.000G 40.0G 220G
0.1k 0.001M 0.01M 0.1M 0.001G 0.1G 1G
* ±(2.5%+5 ) ±(20%+3 )
54
606
TC
* vs. 50V/10.0G100V/20.0G250V/40.0G 500V/100G1000V/200G vs. 50V/50.0k100V/100.0k250V/250.0k 500V/0.500M1000V/1.000M <2mA+0%-50% -0%+2%+2V C 1uF <1 1uF 30V ac/dc
3
55
606
SC
ACV DCV
·
· ·
·
·
·
· · ·
·
· · · 30Vac rms 42 Vac 60 Vdc
· · · CAT
·CAT III CAT IV
56
606
SC
· IEC 61010-031
· · · ·
DC AC UL STD 61010-1 61010-2-034
30 V (OL)
57
606
SC
m L nk 0
1M 10M 100M LOCK TEST
AutoSense
APO
1GK 10GK MEM
A
6100GK
RENPIDAR COMPARE
MGK HzV LPF
R
VAC S DC 0
MGK
m FA
SETUP
5 Sec Del Last
RECALL PI/DAR/t PASS
TEST
LPF
V OFF
TRUE RMS
V >660V INSULATION COM
315mA FUSED
CAT IV 600V
V
58
606
SC
ACV DCV
0
AutoSense
6 00
Hz
VAC
0
AutoSense
6 00
VDC
30V
LPF
LPF
V
V
V
INSULATION
COM
ACV DCV>1V 660Vac/dc> 660Vac/dc
59
606
SC
DUT V-COM AC/DC 600V
F
COMP STORE LOCK
V
INSULATION
COM
60
606
SC
L nk
L nk
L nk
(BLE) V5.0 6m QR APPA Connect APPA Connect DMM LCD
Google Play APPA Connect
iTune Store APPA Connect
61
606
SC
ACV DCV LPF
0
AutoSense
6 00
Hz
VAC
SETUP
Press
0
6 00
Hz
VAC
SETUP
Press
0
6 00
VDC
SETUP
Press
0
6 00
LPF
VAC
SETUP
Press
Press>2Sec2
SETUP
62
606
SC
0
1
10
100
1 K
mA 10 K 100 K
R
Press &
TEST
hold
0
1
10
100 TEST
1 K
mA 10 K 100 K
R
0
0
COM
1. (a) (b) (c)
<10 LCD ->0<-
63
606
SC
2. 3.
0
1M
10M 100M 1G
10G 100G
V
G
Press>1S1ec
TEST
0
1M
10M 100M 1G TEST
10G 100G
V
M
TEST
=
500V
V
INSULATION
COM
500V
64
606
SC
1. 30V>30V
2.
3. 1
4.
5.
0
1M
10M 100M 1G
10G 100G
V
Press
0
1M
10M 100M 1G
10G 100G
COMPARE
M
0.5M 10M20M50M100M200M500M 1000M
0.5 1234510203040
65
606
SC
Pass
PI DAR
0
1M
10M 100M 1G
10G 100G
V
G
Press2>2Se`c
LOCK
PI/DAR/t
1M 0
PI
10M 100M 1G
10G 100G
G
Press
LOCK
PI/DAR/t
1M 10M 100M 1G 0
DAR
10G 100G
G
Press
LOCK
PI/DAR/t
0
1M
10M 100M 1G
10G 100G
G
Press
LOCK
PI/DAR/t
Press>2S2ec
LOCK
PI/DAR/t
PI DAR PI DAR
66
606
SC
PI R10-min R1-min DAR R1-min R30-sec R15-sec
R10-min 10 R1-min 1 R30-sec 30 R15-sec 15
R30-sec R15-sec
DAR 1.3 PI 2 PI DAR Err
PI
PI R10-min R1-min
1M 0
PI
10M 100M 1G
10G 100G
Press
1M 0
PI
10M 100M 1G
10G 100G
R1-min
M
SETUP
Press
Press
1M 0
PI
10M 100M 1G
10G 100G
R10-min
M
67
606
SC
DAR
DAR R1-min R30-sec
1M 10M 100M 1G 0
DARD
10G 100G
Press
0
1M
10M 100M 1G
10G 100G
AR
R30-sec
M
SETUP
Press
Press
1M 10M 100M 1G 0
DAR
10G 100G
R1-min
M
0
Press 1M
10M 100M 1G
APO
10G 100G
M
0
1M
10M 100M 1G
APO
10G 100G
V
M
SETUP
Press
Press
0
1M
10M 100M 1G
APO A 10G 100G
M
68
606
SC
1.
MEM 2. PI DAR
3. 1500
PIDAR 4. PI DAR 3
PI DAR
PI DAR
R1-min R30-Sec
R15-Sec
R10-min R1-min
1M 10M 100M 1G 10G
0
100G
V
G
Press>55Sec until thLCeDLCDshdoEwL sdEL
5 S5 ec Del Last
MEM
MEM
M
69
606
SC
2 nOnE
MEM
Press
SETUP
MEM
M
M Press
MEM
M
70
606
SC
0
1M
10M 100M 1G
APO
10G 100G
V
M
Press>2S2ec
Insulation Resistance
RECALL
MEM
Leakage Current
M
Press
RECALL
MEM
VDC
Press
RECALL
MEM
Press>2S2ec
RECALL
TVeoslttage
A
Press
RECALL
71
606
SC
PI
MEM Press
PI
PI
RECALL
PI
Press
MEM
R1-min
M
Press
MEM
M
R10-min
DAR
MEM Press
RECALL
Press
MEM
M
R15-Sec or
R30-Sec
Press
MEM
M
R1-min
72
606
SC
APO
APO
VAC
30min
LPF V
OFF
OFF
(OFF) LCD
73
606
SC
DAR APO
20mA200mA
200mA
0.5102050 100200500 1000M
100M
0.512345 10203040
2
1530
30
1 40
1
102030 405060
30
PI
DAR
1. 2. Comp 3.
74
606
SC
2
3
1
·
·315mA1000V 10kA
· · bAtt
·1.5V x 4
75
606
TEST
TEST
0
SC
TEST
· · FUSE
76
606
SC
4000 >OL >-OL 2 x x 96mm x 207 mm x 54mm 630g 4 AA 1.5 AA
2600 1 5 25
1100 1000 V 1M 5 25
IEC/EN 61010-1IEC/EN 61010-2-034 EN 61557 IEC/EN 61557-2:2019 IEC/EN 61557-4:2019 EMCEN 61326-1
CAT
II
III
IV
77
606
SC
2 2000m (6562ft) <5
5 ~ 30 ( 80% RH) 30 ~ 40 ( 75% RH) 40 ~ 50 ( 45%RH) -20 600 80% R.H. 0.15 x/< 20 > 26 IP IP40 MIL-PRFF 2 4
23° C ± 3° C 70% R.H. ±(% + )
ACV ·ACV ACA · · (C.F.)
C.F. 1.0 ~ 2.0 1.0% C.F. 2.0 ~ 2.5 2.5% C.F. 2.5 ~ 3.0 4.0% · 3000 3.0
4500 2.0 6000 1.5 ·
78
606
AC
OL
600.0V
660.0V
0.1V
10M // 100pF 50Hz 400Hz AC/DC 600V
DC
600.0V
OL 660.0V
10M AC/DC 600V
0.1V
SC
±(1.5%+5 )
(50~60Hz) ±(2.0%+5 )
(61~400Hz)
±(1.0%+5 )
100.0Hz 1000Hz
OL 100.0Hz 1100Hz
ACV > 60V 10Hz AC/DC 600V
0.1Hz 1Hz
±(1.0%+3 )
ACV 50 60Hz ±4% 50 60Hz (-3dB)1kHz AC/DC 600V
79
606
100.0nF 1000nF 10.00uF
OL 100.0nF 1000nF 11.00uF
AC/DC 600V
0.1nF 1nF 0.01uF
SC
±(3.0%+10 ) ±(3.0%+5 )
40.00 400.0 4.000k 40.00k
OL 40.00 400.0 4.000k 44.00k
0.01 0.1 0.001k 0.01k
±(1.5%+5 )*
±(1.5%+3 )
*<1.00 + 3 * 20mA 10 * 0.5%+5 >200mA @ <2 >20mA@ <2 >4V
400.0k 4.000M 40.00M 400.0M 4.000G 40.0G 200G
OL 400.0k 4.000M 40.00M 400.0M 4.000G 40.0G 220G
0.1k 0.001M 0.01M 0.1M 0.001G 0.1G 1G
* ±(2.5%+5 ) ±(20%+3 )
80
606
SC
* vs. 50V/10.0G100V/20.0G250V/40.0G500V/100G 1000V/200G vs. 50V/50.0k100V/100.0k250V/250.0k 500V/0.500M1000V/1.000M <2mA+0%-50% -0%+2%+2V C 1uF <1 1uF 30V ac/dc
3
81
606
JP
ACVDCV
·
·
·
·
·
· /
· 1
·
·
·
·
·
82
606
JP
·30Vac42 Vac60Vdc
· · · · III IV
DC AC Bluetooth EU UL 61010-161010-2-034
83
606
JP
30V OL
84
606
JP
m L nk 0
1M 10M 100M LOCK TEST
AutoSense
APO
1GK 10GK MEM
A
6100GK
RENPIDAR COMPARE
MGK HzV LPF
R
VAC S DC 0
MGK
m FA
SETUP
5 Sec Del Last
RECALL PI/DAR/t PASS
TEST
LPF
V OFF
TRUE RMS
V >660V INSULATION COM
315mA FUSED
CAT IV 600V
/
85
606
JP
ACV/DCV
0
AutoSense
6 00
Hz
VAC
0
AutoSense
6 00
VDC
30V
LPF
LPF
V
V
V
INSULATION
COM
ACV DCV (>1V) 660Vac/dc > 660Vac/dc
86
606
JP
DUT V-COM AC/DC 600V
F
COMP STORE LOCK
V
INSULATION
COM
87
606
JP
L nk
L nk
L nk
Bluetooth Low Energy(BLE)V5.0 6m QR APPA Connect LINK APPA Connect DMM LINK LCD
Google Play APPA Connect
iTune Store APPA Connect
88
606
JP
/ACV/DCV/LPF
0
AutoSense
6 00
Hz
VAC
SETUP
Press
0
6 00
Hz
VAC
SETUP
Press
2Press>2Sec
SETUP
0
6 00
VDC
SETUP
Press
0
6 00
LPF
VAC
SETUP
Press
89
606
JP
0
1
10
100
1 K
mA 10 K 100 K
R
Press
& hold
TEST
0
1
10
100 TEST
1 K
mA 10 K 100 K
R
0
0
COM
1. (a) (b) (c) 10 “->0<-”
90
606
JP
2. / 3. >
0
1M
10M 100M 1G
10G 100G
V
G
1 Press>1Sec
TEST
0
1M
10M 100M 1G TEST
10G 100G
V
M
TEST
=
500V
V
INSULATION
COM
500V
91
606
JP
1. 30V>30V
2.
3. 1/
4.
5.>
0
1M
10M 100M 1G
10G 100G
V
Press
0
1M
10M 100M 1G
10G 100G
COMPARE
M
0.5M 10M 20M 50M 100M 200M 500M 1000M
0.5 1 2 3 4 5 10 20 30 40
92
606
JP
PASS
PI/DAR
0
1M
10M 100M 1G
10G 100G
V
G
2 Press>2Sec
LOCK
PI/DAR/t
1M 0
PI
10M 100M 1G
10G 100G
G
Press
LOCK
PI/DAR/t
1M 10M 100M 1G 0
DAR
10G 100G
G
2Press>2Sec
LOCK
PI/DAR/t
Press
LOCK
PI/DAR/t
0
1M
10M 100M 1G
10G 100G
G
Press
LOCK
PI/DAR/t
PI/DAR / PI/DAR / /
93
606
JP
PI( )=R10-min/R1-min DAR( )=R1-min/(R30-sec R15-sec)
R10-min 10 R1-min 1 R30-secc 30 R15-sec 15
R30-sec R15-sec
DAR 1.3 PI 2 PI/DAR Err
PI
PI=R10-min/R1-min
1M 0
PI
10M 100M 1G
10G 100G
Press
1M 0
PI
10M 100M 1G
10G 100G
R1-min
M
SETUP
Press
Press
1M 0
PI
10M 100M 1G
10G 100G
R10-min
M
94
606
JP
DAR
DAR=R1-min/R30-sec
1M 10M 100M 1G 0
DARD
10G 100G
Press
0
1M
10M 100M 1G
10G 100G
AR
R30-sec
M
SETUP
Press
Press
1M 10M 100M 1G 0
DAR
10G 100G
R1-min
M
0
Press 1M
10M 100M 1G
APO
10G 100G
M
0
1M
10M 100M 1G
APO
10G 100G
V
M
SETUP
Press
Press
0
1M
10M 100M 1G
APO A 10G 100G
M
95
606
JP
/ 1. /
/ MEM 2. PI/DAR / 3. ( PIDAR) 1500 / 4. PI/DAR 3 ( )
PI
DAR
PI DAR
R1-min R30-Sec or R15-
Sec
R10-min R1-min
1
0
1M
10M 100M 1G
10G 100G
V
G
LCDPredsEsL>5Sec until the5LCD showsdEL
>5 5 SDecel DLeal Lsat st
MEM
MEM
M
96
606
JP
/ 2 / nOnE
MEM
Press
SETUP
MEM
M
M Press
MEM
M
97
606
JP
0
1M
10M 100M 1G
APO
10G 100G
V
M
2 Press>2Sec
RECALL
Insulation
Resistance
MEM
Leakage Current
M
Press
RECALL
MEM
VDC
Press
RECALL
MEM
2Press>2Sec
RECALL
TVeoslttage
A
Press
RECALL
98
606
JP
PI
MEM Press
PI
PI
RECALL
PI
Press
MEM
M
R1-min
Press
MEM
M
R10-min
DAR
MEM Press
RECALL
Press
MEM
M
RR115–SSeecc or
RR3300–SSeecc
Press
MEM
M
R1-min
99
606
JP
APO
APO
VAC
3300min
LPF V
OFF
OFF
OFF LCD
100
606
JP
20mA 200mA
200mA
0.5 10 20 50 100 200 500 100M 1000M
0.5 1 2 3 4 5 10 20 30 2 40
DAR 15 30
30
1 40
1
APO
Off10 20 30 40 50 60
30
PI
DAR
1. 2. Comp
3.
101
606
JP
2
3
1
·
·315 mA1000 V10 kA
· /
· bAtt
·1.5V x 4 102
606
TEST
TEST
0
JP
TEST
· · FUSE
103
606
JP
4000 >OL >-OL 2 x x 96mm x207mm x 54mm 630g 3 *4 1.5 3
2600 5 /25 1
1100 5 /25 1000V/1M
IEC/EN 61010-1 IEC/EN 61010-2-034 EN 61557 IEC/EN 61557-2:2019
IEC/EN 61557-4:2019 EMCEN 61326-1
II
AC ( )
III
AC
IV
AC
104
606
JP
2 6562ft (2000m) <5
530(80%RH) 3040(75%RH) 4050(45%RH) -2060080% RH 0.15 x () / < 20> 26 IP: IP40 MIL-PRFF2 4 ft1.2m
70% 23 ± 3 ± ( % + ) 1
ACV · ACVACAAC · · C.F.
: 1.0%C.F.1.02.0 2.5%C.F.2.02.5 4.0%C.F.2.53.0 ·3.03000
2.04500 1.56000 ·
105
606
JP
AC
600.0V
OL 660.0V
0.1V
±(1.5%+5 ) (50 60Hz)
±(2.0%+5 ) (61 400Hz)
10M // 100pF 50Hz400Hz AC/DC 600V
DC
600.0V
OL 660.0V
0.1V
10M AC/DC 600V
±(1.0%+5 )
100.0Hz 1000Hz
OL 100.0Hz 1100Hz
0.1Hz 1Hz
ACV> 60V 10Hz AC/DC 600V
±(1.0%+3 )
ACV 5060Hz±4% 5060Hz (-3dB)1kHz AC/DC 600V
106
606
JP
100.0nF 1000nF 10.00uF
OL 100.0nF 1000nF 11.00uF
0.1nF 1nF 0.01uF
AC/DC 600V
±(3.0%+10 )
±(3.0%+5 )
40.00 400.0 4.000k 40.00k
OL 40.00 400.0 4.000k 44.00k
0.01 0.1 0.001k 0.01k
±(1.5%+5 )*
±(1.5%+3 )
* <1.003 *(20 mA)10 *0.5%+5 <2 >200mA <2 >20mA > 4V
400.0k 4.000M 40.00M 400.0M 4.000G 40.0G 200G
OL 400.0k 4.000M 40.00M 400.0M 4.000G 40.0G 220G
0.1k 0.001M 0.01M 0.1M 0.001G 0.1G 1G
* ±(2.5%+5 ) ±(20%+3 )
107
606
JP
* / 50V/10.0G, 100V/20.0G, 250V/40.0G, 500V/100G, 1000V/200G / 50V/50.0k, 100V/100.0k, 250V/250.0k, 500V/0.500M, 1000V/1.000M <2mA +0% -50% -0% +2%+2V C 1uF <1 1uF 30V AC/DC
3
108
606
RU
/ , , , .
.
· , .
· , .
· , , .
· , . .
· , , .
· , , , / .
· , – . · ,
. · ,
109
606
RU
, , . · . · , . · . · 30 . , 42 . 60 . . . · , . · , . · , , . · CAT III CAT IV. · , , , III IV IEC 61010-031
110
606
RU
. ·
, . · , . . · , . · , .
111
606
RU
,
. Bluetooth . , 61010-1 61010-2-034
« » , , , 30 (OL).
112
606
RU
. , . .
. .
113
606
RU
m L nk 0
1M 10M 100M LOCK TEST
AutoSense
APO
1GK 10GK MEM
A
6100GK
RENPIDAR COMPARE
MGK HzV LPF
R
VAC S DC 0
MGK
m FA
SETUP
5 Sec Del Last
RECALL PI/DAR/t PASS
TEST
LPF
V OFF
TRUE RMS
V >660V INSULATION COM
315mA FUSED
CAT IV 600V
/
114
606
RU
/ :
0
AutoSense
6 00
Hz
VAC
0
AutoSense
6 00
VDC
30V
LPF
LPF
V
V
V
INSULATION
COM
: ACV DCV (> 1 ). 660 ./. , «> 660Vac/dc».
115
606
RU
, ; , . 600 / V-COM.
F
COMP STORE LOCK
V
INSULATION
COM
116
606
RU
L nk
L nk
L nk
Bluetooth (BLE) V5.0. — 6 . APPA Connect QR-. LINK APPA Connect DMM. LINK.
APPA Connect Google Play
APPA Connect iTune Store
117
606
RU
/ / ,
0
AutoSense
6 00
Hz
VAC
SETUP
Press
0
6 00
Hz
VAC
SETUP
Press
Press>2Se2c
SETUP
0
6 00
VDC
SETUP
Press
0
6 00
LPF
VAC
Press SETUP
118
606
RU
( ) . . , . .
()
0
1
10
100
1 K
mA 10 K 100 K
R
Press &
hold
TEST
0
1
10
100 TEST
1 K
mA 10 K 100 K
0
R
0
COM
119
606
RU
1. : (a) . (b) . . « ». (c) , . < 10 , , – «->0<-».
2. : , . , . , /. 3. «>», , , .
120
606
RU
0
1M
10M 100M 1G
10G 100G
V
G
Press>1Se1c
TEST
0
1M
10M 100M 1G TEST
10G 100G
V
M
TEST
=
500V
V
INSULATION
COM
550000V
1. : . 30 , «> 30V». .
2. , , .
3. : , .
121
606
RU
, ( 1 ). , /. 4. , ( ). , , . 5. «>», , , .
0
1M
10M 100M 1G
10G 100G
V
Press
0
1M
10M 100M 1G
10G 100G
COMPARE
M
: 0,5, 10, 20, 50, 100, 200, 500, 1000 .
: 0,5, 1, 2, 3, 4, 5, 10, 20, 30, 40 .
, , ,
122
606
RU
PI/DAR/
0
1M
10M 100M 1G
10G 100G
V
G
Press>2S2ec
LOCK
PI/DAR/t
1M 0
PI
10M 100M 1G
10G 100G
G
Press
LOCK
PI/DAR/t
10M 100M 1G 1M 0
DAR
10G 100G
G
Press
LOCK
PI/DAR/t
0
1M
10M 100M 1G
10G 100G
G
Press
LOCK
PI/DAR/t
Press>2Se2c
LOCK
PI/DAR/t
, / PI/ DAR. PI/DAR, / / .
123
606
RU
PI ( ) = R10-/R1- DAR ( )=R1-/ (R30- R15-) :
R10-: , 10 . R1-: , 1 . R30-: , 30 . R15-: , 15 .
. R30- R15- .
DAR 1,3 PI 2, . , «Err» PI/DAR.
124
606
RU
PI
PI=R10-/R1-
1M 0
PI
10M 100M 1G
10G 100G
Press
1M 0
PI
10M 100M 1G
10G 100G
R1-min
M
SETUP
Press
Press
1M 0
PI
10M 100M 1G
10G 100G
R10-min
M
DAR
DAR=R1-/R30-
1M 10M 100M 1G 0
DARD
10G 100G
Press
0
1M
10M 100M 1G
10G 100G
AR
R30-sec
M
SETUP
Press
Press
10M 100M 1G 1M 0
DAR
10G 100G
R1-min
M
125
606
RU
0
Press 1M
10M 100M 1G
APO
10G 100G
M
0
1M
10M 100M 1G
APO
10G 100G
V
M
SETUP
Press
Press
APO 1M 10M 100M 1G 10G
0
A 100G
M
/: 1. /
. / MEM . 2. PI / DAR, / . 3. 1500 / (, , , , PI, DAR). 4. PI / DAR 3 ( ).
126
606
RU
PI
PI
R1-
DAR DAR R30- R15-
R10-
R1-
1M 10M 100M 1G 10G
0
100G
V
G
Press>5Sec >un5til, theLCDshdoEwLsdEL
> 5 –5Sec DelLast
MEM
MEM
M
127
606
RU
/ 2 , . , «nOnE».
.
MEM
Press
SETUP
MEM
M
M Press
MEM
M
128
606
RU
.
, , .
0
1M
10M 100M 1G
APO
10G 100G
V
M
Press>2S2ec Insulation Resistance
RECALL
MEM
Leakage Current
M
Press
RECALL
MEM
VDC
Press
RECALL
Press>2Se2c
RECALL
Test Voltage
MEM
A
Press
RECALL
129
606
RU
PI .
,
.
MEM
Press
PI
PI
RECALL
PI
Press
MEM
R1-min
M
Press
MEM
M
R10-min
DAR .
,
.
MEM Press
RECALL
Press
MEM
M
R15-Sec or R30-Sec
Press
MEM
M
R1-min
130
606
RU
( )
APO
APO
VAC
30 min
LPF V
OFF
OFF
, , .
.
:
, . : . : : :
131
606
RU
DAR
., .
20 , 200
0,5, 10, 20, 50, 100, 200, 500, 1000
0,5, 1, 2, 3, 4, 5, 10, 20, 30, 40
, 15, 30
140
., 10, 20, 30, 40, 50, 60 ,
, , ,
PI ,
DAR ,
,
. 200
100
2
30 1 30
1. , .
2. Comp .
3. .
132
606
RU
. :
2
3
1
· , , .
· : , 315 , 1000 , . 10 .
· , , .
· ,
133
606
RU
«bAtt». , . · 4 1,5 .
TEST
TEST
0
TEST
· .
· «FUSE», , .
134
606
RU
: 4000 . : « >OL» « >-OL» : 2 ( x x ): 96 x 207 x 54 : 630 . : AA * 4 : 1,5 AA
: 2600 . 1 5 25 .
: 1100 . 1 1000 5 25 .
: IEC/EN 61010-1, IEC/EN 61010-2-034
EN 61557: IEC/EN 61557-2:2019 IEC/EN 61557-4:2019
: EN 61326-1
135
606
RU
CAT II
, ( . .) .
III ,
.
IV
, .
: 2 : 2000 (6562) : < 5 °C,
5 30°C (. 80 %), 30 40°C (. 75 %), 40 50°C (. 45 %) : -20 60 °C, 0 80 % R.H. ( ) : 0,15 x ( ) / °C, < 20 > 26 °C. IP: IP40 : MIL-PRFF, 2 : 4 .
± (% + ) 23 ± 3 °C, . 70 % .
136
606
RU
ACV · ACV ACA , . · . ·
(): 1,0 % 1,0 2,0
2,5 % 2,0 2,5 4,0 % 2,5 3,0 · . : 3,0 3000 2,0 4500 1,5 6000 · .
OL
600,0
660,0
0,1
± (1,5 % + 5 .) (5060 )
± (2,0 % + 5 .) (61400 )
: 10 // 100 : 50 400 : 600 ./.
600,0
OL
660,0
0,1
± (1,0% + 5 .)
: 10 : 600 ./.
137
606
RU
100,0 1000
OL
100,0
0,1
1100
1
± (1,0 % + 3 .)
. : > 60 : 10 : 600 ./.
± 4 % 50 60 50 60 (-3 ): 1 : 600 ./.
100,0 1000 10,00
OL
100,0
0,1
1000
1
11.00 0,01
± (3,0 % + 10 .) ± (3,0% + 5 .)
: 600 ./.
138
606
RU
()
40,00 400,0 4,000 40,00
OL
40,00
0,01
400,0
0,1
4,000 0,001
44,00 0,01
± (1,5 % + 5 .)*
± (1,5 % + 3 .)
* < 1,00 3 * 20 10 * 0,5 % + 5 . : > 200 @ < 2 > 20 @ < 2 : > 4
400,0 4,000 40,00 400,0 4,000 40,0 200
OL
400,0 0,1
4,000 0,001
40,00 0,01
400,0 0,1
4,000 0,001
40,0
0,1
220
1
* ± (2,5% + 5 .) ± (20 % + 3 .)
* . : 50 / 10,0 , 100 / 20,0 , 250 / 40,0 , 500 / 100 , 1000 / 200 :
139
606
RU
50 / 50,0 , 100 / 100,0 , 250 / 250,0 , 500 / 0,500 , 1000 / 1,000 : < 2 , +0 %, -50 % : -0 %, +2 % +2 : < 1 C 1 : 1 : 30 , .
140
606
RU
3 . . , , , , , , . , , , , , . , , , , . , .
141
www.appatech.com
APAC MGL APPA Corporation
[email protected] Flat 4-1, 4/F, No. 35, Section 3 Minquan East Road, Taipei, Taiwan Tel: +886 2-2508-0877
:
:
:
:
:
:
:
:
35 4
:
:
02-2508-0877
72 400-099-1987 [email protected]
700020084